• HRV • VAM-FA8VE
• HRV • Heat Reclaim Ventilation
12
1
6
6
Selection Procedures
6-2
Based on Room size
<Table 3> Criteria for Model Selection
Required
ventilating AFR
per person
(m
3
/ h / person)
Area per person
(m
2
/ person)
Model Name
Frequency
Air Flow Rate
Application area (m
2
)
Hz
L
H
20
3
VAM 150FA
50
110
150
16.5
–
22.5
60
110
150
16.5
–
22.5
VAM 250FA
50
155
250
23.3
–
37.5
60
145
250
21.8
–
37.5
VAM 350FA
50
230
350
34.5
–
52.5
60
210
350
31.5
–
52.5
VAM 500FA
50
350
500
52.5
–
75.0
60
300
500
45.0
–
75.0
VAM 650FA
50
500
650
75.0
–
97.5
60
440
650
66.0
–
97.5
VAM 800FA
50
670
800
100.5
–
120.0
60
660
800
99.0
–
120.0
VAM1000FA
50
870
1000
130.5
–
150.0
60
800
1000
120.0
–
150.0
VAM1500FA
50
1200
1500
180.0
–
225.0
60
1200
1500
180.0
–
225.0
VAM2000FA
50
1400
2000
210.0
–
300.0
60
1400
2000
210.0
–
300.0
5
VAM 150FA
50
110
150
27.5
–
37.5
60
110
150
27.5
–
37.5
VAM 250FA
50
155
250
38.8
–
62.5
60
145
250
36.3
–
62.5
VAM 350FA
50
230
350
57.5
–
87.5
60
210
350
52.5
–
87.5
VAM 500FA
50
350
500
87.5
–
125.0
60
300
500
75.0
–
125.0
VAM 650FA
50
500
650
125.0
–
162.5
60
440
650
110.0
–
162.5
VAM 800FA
50
670
800
167.5
–
200.0
60
660
800
165.0
–
200.0
VAM1000FA
50
870
1000
217.5
–
250.0
60
800
1000
200.0
–
250.0
VAM1500FA
50
1200
1500
300.0
–
375.0
60
1200
1500
300.0
–
375.0
VAM2000FA
50
1400
2000
350.0
–
500.0
60
1400
2000
350.0
–
500.0
10
VAM 150FA
50
110
150
55.0
–
75.0
60
110
150
55.0
–
75.0
VAM 250FA
50
155
250
78.0
–
125.0
60
145
250
72.0
–
125.0
VAM 350FA
50
230
350
115.0
–
175.0
60
210
350
105.0
–
175.0
VAM 500FA
50
350
500
175.0
–
250.0
60
300
500
150.0
–
250.0
VAM 650FA
50
500
650
250.0
–
325.0
60
440
650
220.0
–
325.0
VAM 800FA
50
670
800
335.0
–
400.0
60
660
800
330.0
–
400.0
VAM1000FA
50
870
1000
435.0
–
500.0
60
800
1000
400.0
–
500.0
VAM1500FA
50
1200
1500
600.0
–
750.0
60
1200
1500
600.0
–
750.0
VAM2000FA
50
1400
2000
700.0
– 1000.0
60
1400
2000
700.0
– 1000.0
Summary of Contents for VAM-FA8VE
Page 1: ...EEDEN07 201 technical data heat reclaim ventilation VAM FA8VE VKM GAMV1 VKM GAV1 ...
Page 2: ......
Page 152: ......
Page 272: ...2 11 270 HRV VKM GA M V1 HRV Heat Reclaim Ventilation Length Flow rate ...
Page 275: ...2 11 HRV VKM GA M V1 HRV Heat Reclaim Ventilation 273 Temperature conversion table ...