• HRV • Heat Reclaim Ventilation
187
• HRV • VKM-GAV1
2
7
ELECTRICAL SPECIFICATIONS
VKM100GAV1
VKM80GAV1
VKM50GAV1
Power Supply
Name
V1
Phase
1
1
1
Frequency
Hz
50
50
50
Voltage
V
220-240
Nominal running
current (RLA)
Heat exchange
mode
Ultra-high
A
3.00
3.00
3.00
High
A
2.50
2.60
2.50
Low
A
2.10
2.10
2.10
Bypass mode
Ultra-high
A
3.00
3.00
3.00
High
A
2.50
2.60
2.50
Low
A
2.10
2.10
2.10
Current
Minimum circuit amps (MCA)
A
4.30
4.30
4.30
Maximum fuse amps (MFA)
A
15
15
15
Fan motor rated output
kW
0.28 x 2
Full load amps (FLA)
A
1.9 x 2
Voltage range
Minimum
V
198
198
198
Maximum
V
264
264
264
Notes
Voltage range : Units are suitable for use on the electrical systems where the voltage supplied to
the unit terminals is not below or above the listed range limits.
Maximum allowable voltage range variation between phases is 2%
MCA/MFA : MCA = 1.25 x FLA (FM1) + FLA (FM2) ; MFA <= 4 x FLA ; (Next lower standard fuse
rating. Min. 15A
Select wire size based on the value of MCA.
Instead of the fuse, use the circuit breaker.