![background image](http://html1.mh-extra.com/html/daikin/super-multi-plus-e-series-ftxg25ev1bw/super-multi-plus-e-series-ftxg25ev1bw_service-manual_4705813099.webp)
SiBE18-821_C
Special Control
Function
87
3.5
Restart Standby
Restart is prohibited to prevent frequent power-on/off and to equalize pressure in the refrigerant
system.
3.6
Stopping Operation
Operation of the actuator is cleared up when the system is down.
3.6.1 When System is in Stop Mode
Actuator
Operation
Remarks
Compressor
OFF
Outdoor fan
Ta > 30
°
C: STEP 4
Ta
≤
30
°
C: OFF
Four way valve (Y1S)
Former condition remains.
Main electronic expansion valve (Y1E)
0 pls
Subcooling electronic expansion valve
(Y3E)
0 pls
Hot gas bypass valve (Y2S)
OFF
Ending conditions
2 min.
Actuator
Operation
Compressor
OFF
Outdoor fan
OFF
Four way valve (Y1S)
Former condition remains.
Main electronic expansion valve (Y1E)
0 pls
Subcooling electronic expansion valve (Y3E)
0 pls
Hot gas bypass valve (Y2S)
OFF
Ending conditions
Indoor unit thermostat is turned ON.