4PW48323-1B

Installation manual

4

P

RECAUTIONS

 

ON

 

INSTALLATION

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which are
available on the market.)

It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown
in the figure.

prepare all 4 wires as indicated in the drawing

unscrew the top plate at the 4 locations indicated A and B

put the screws through the nooses and screw them back tight

A

location of the 2 fixation holes on the front side of the unit

B

location of the 2 fixation holes on the rear side of the unit

C

wires: field supply

Drain pipe disposal

If drain pipe disposal from the outdoor unit causes trouble (for
example, if the drain water may splash on people) provide the
drain piping using a drain socket (optional).

Make sure the drain works properly.

I

NSTALLATION

 

SERVICING

 

SPACE

The numerical figures used in here represent the dimensions for the
71-100-125-140 class models. Figures between (  ) indicate the
dimensions for the 100-125-140 class models. (Unit: mm)

(Refer to 

"Precautions on installation" on page 4

)

Precaution

(A) In case of non-stacked installation 

(See figure 1)

(B) In case of stacked installation

1.

In case obstacles exist in front of the outlet side.

2.

In case obstacles exist in front of the air inlet.

Do not stack more than one unit.

About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.

(C) In case of multiple-row installation (for roof top use, etc.)

1.

In case of installing one unit per row.

Discharge side

Bottom view (mm)

Drain hole

20

140

117

219

289

350

(345-355)

47

140

620

614

423

A

B

C

C

B

A

A

Suction side obstacle

Obstacle is present

Discharge side obstacle

1

In these cases, close the 
bottom of the installation 
frame to prevent the 
discharged air from 
being bypassed

Left side obstacle

Right side obstacle

2

In these cases, only 2 
units can be installed.

Top side obstacle

This situation is not 
allowed

1000

100

A

200

(300)

100

A

500

(1000)

100

(200)

1000

(2000)

50

(100)

Summary of Contents for RZQ71D7V1B

Page 1: ...INSTALLATION MANUAL RZQ71D7V1B RZQ71D2V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vasta...

Page 4: ...ns or earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws an...

Page 5: ...salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the re...

Page 6: ...wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be fores...

Page 7: ...water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dime...

Page 8: ...and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuming is comple...

Page 9: ...te the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A insta...

Page 10: ...e effects If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be r...

Page 11: ...ions when connecting field piping and regarding insulation Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping ins...

Page 12: ...y closed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increa...

Page 13: ...amount is R1 R2 1 G1 total length of 9 5 mm liquid piping G2 total length of 6 4 mm liquid piping 2 a G1 30 m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30...

Page 14: ...ove and use the table below G1 total length of 12 7 mm liquid piping Length exceeding Chargeless length Model Liquid piping 0 5 m 5 10 m 10 15 m 15 20 m RZQ71 Main 12 7 0 5 1 0 RZQ100 140 Main 1 5 2 0...

Page 15: ...apacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the stop valve...

Page 16: ...e maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when...

Page 17: ...it decoration panel with infra red receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete tes...

Page 18: ...charge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 mode...

Page 19: ...NOTES NOTES...

Page 20: ...4PW48323 1B Copyright Daikin...

Reviews: