Installation manual

5

RZQ71~14 RZQ7 RZQ100~140B8W1B

Split System air conditioners

4PW48323-1B

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

Selection of piping material

Piping and other pressure containing parts shall comply with the
national and international codes and shall be suitable for
refrigerant, use phosphoric acid deoxidised seamless copper for
refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.

O=Annealed
1/2H=Half hard

Only use annealed material for flare connections.

Refrigerant pipe size

Refer to 

figure 3

 for twin system, to 

figure 4

 for triple system and to

figure 5

 for double twin system.

Main pipe (pipe between outdoor and first branch).
The pipes should have the same size as the outdoor
connections.

Pipe between first branch and second branch (L2+L3) (only for
double twin).

Pipe between branch and indoor units (L2~L3 for twin, L2~L4 for
triple and L4~L7 for double twin).
These pipe sizes must have the same size as the connected
indoor units pipe sizes. Branch: see marking '

' on figures 

3

4

and 

5

.

Selection of branch pipe

L

A

L

H

0<L

1/2H

150 (250)

1/2H<L

200 (300)

H<L

Installation impossible

Installation shall be done by a licensed refrigeration
technician, the choice of materials and installation shall
comply with the applicable national and international
codes. In Europe, EN378 is the applicable standard that
shall be used.

To persons in charge of piping work:

Be sure to open the stop valve after piping installing
and vacuming is complete. (Running the system with
the valve closed may break the compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with the freon collection and destruction law.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.

Pipe Ø

Temper grade 

of piping material

Minimal thickness t (mm)

6.4 / 9.5 / 12.7

O

0.80

15.9

O

1.00

19.1

1/2H

1000

(1500)

400 (600)

2000

(3000)

A

H

L

Refrigerant pipe size

(a)

(a) In case of twin, triple and double twin applications, the listed refrigerant pipe 

sizes relate to the main pipes only. (L1 = the pipes between the outdoor unit and 
the branch in figures 

3

~

5

).

Gas pipe

Model

Size-down

Standard size

Size-up

RZQ71

Ø12.7

Ø15.9

RZQ100~140

Ø19.1

Liquid pipe

Model

Size-down

Standard size

Size-up

RZQ71~140

Ø6.4

Ø9.5

Ø12.7

Liquid

Ø9.5

Gas

Ø15.9

NOTE

For new installations, use the standard pipe sizes.

When using existing pipes, size-up is allowed as
mentioned in the table above.
Size up is only allowed for pair combination (L1).
Additional restrictions towards allowable pipe
lengths, as mentioned in the table 

"Allowable pipe

length" on page 6

, must be taken into account.

Not using the standard pipe size may result in
capacity decrease. The installer must
acknowledge this and judge this very carefully in
function of the complete installation.

RZQ100~140B8

W1B

 + 

FCQ35~71C / FCQH71C/D

Twin

KHRQ22M20TA

KHRQ58T

Triple

KHRQ127H

KHRQ58H

Double twin

KHRQ22M20TA (3x)

KHRQ58T (3x)

Summary of Contents for RZQ71D7V1B

Page 1: ...INSTALLATION MANUAL RZQ71D7V1B RZQ71D2V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vasta...

Page 4: ...ns or earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws an...

Page 5: ...salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the re...

Page 6: ...wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be fores...

Page 7: ...water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dime...

Page 8: ...and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuming is comple...

Page 9: ...te the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A insta...

Page 10: ...e effects If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be r...

Page 11: ...ions when connecting field piping and regarding insulation Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping ins...

Page 12: ...y closed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increa...

Page 13: ...amount is R1 R2 1 G1 total length of 9 5 mm liquid piping G2 total length of 6 4 mm liquid piping 2 a G1 30 m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30...

Page 14: ...ove and use the table below G1 total length of 12 7 mm liquid piping Length exceeding Chargeless length Model Liquid piping 0 5 m 5 10 m 10 15 m 15 20 m RZQ71 Main 12 7 0 5 1 0 RZQ100 140 Main 1 5 2 0...

Page 15: ...apacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the stop valve...

Page 16: ...e maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when...

Page 17: ...it decoration panel with infra red receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete tes...

Page 18: ...charge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 mode...

Page 19: ...NOTES NOTES...

Page 20: ...4PW48323 1B Copyright Daikin...

Reviews: