Installation manual

9

RZQ71~14 RZQ7 RZQ100~140B8W1B

Split System air conditioners

4PW48323-1B

If a torque wrench is not available, be aware that the tightening
torque may increase suddenly. Do not tighten nuts any further
than to the angle as listed.

When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

After completing the installation, carry out a gas leak inspection
of the piping connections with nitrogen and such.

Cautions for necessity of a trap

Since there is fear of the oil held inside the riser piping flowing back into
the compressor when stopped and causing liquid compression
phenomenon, or cases of deterioration of oil return, it will be necessary
to provide a trap at an appropriate place in the riser gas piping.

Trap installation spacing. 

(See figure 6)

A

Outdoor unit

B

Indoor unit

C

Gas piping

D

Liquid piping

E

Oiltrap

H

Install trap at each difference in height of 10 m.

A trap is not necessary when the outdoor unit is installed in a
higher position than the indoor unit.

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidised
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation. When brazing pipes however, do not use oxidation
preventers. Residue of such preventers may result in choking of
pipes or malfunction of components.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

E

VACUATING

Do not purge the air with refrigerants. Use a vacuum pump to
vacuum the installation. No additional refrigerant is provided for
air purging.

Pipes inside the units were checked for leaks by the
manufacturer. The refrigerant pipes fit on site are to be checked
for leaks by the installer.

Confirm that the valves are firmly closed before leak test or
vacuuming.

Set up for vacuuming and leak test: 

see 

figure 8

Procedure for leak test

Leak test must satisfy EN378-2.

1

Evacuate the pipes and check vacuum

(1)

. (No pressure increase

for 1 minute.)

2

Break the vacuum with a minimum of 2 bar of nitrogen. (Never
pressurize more than 4.0 MPa.)

3

Conduct leak test by applying soap water, etc. to the connecting
part of the pipes.

4

Discharge nitrogen.

5

Evacuate and check vacuum again

(1)

.

6

If the vacuum gauge no longer rises, the stop valves can be
opened.

Piping size

Further tightening angle

Recommended arm 

length of tool

Ø6.4

60°~90°

150 mm

Ø9.5

200 mm

Ø12.7

30°~60°

250 mm

Ø15.9

300 mm

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

2

3

4

5

6

6

A

Pair system

B

Simultaneous operation system

1

Pressure gauge

2

Nitrogen

3

Refrigerant

4

Weighing machine

5

Vacuum pump

6

Stop valve

7

Main pipe

8

Branched pipes

9

Pipe branching kit (optional)

(1) Use a 2-stage vacuum pump with a non return valve which 

can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
Evacuate the system from the liquid and gas pipes by using 
a vacuum pump for more than 2 hours and bring the system 
to –100.7 kPa. After keeping the system under that condition 
for more than one hour, check if the vacuum gauge rises or 
not. If it rises, the system may either contain moisture inside 
or have leaks.

Following should be executed if there is a possibility of
moisture remaining in the pipe (if piping work is carried out
during the raining season or over a long period of time,
rainwater may enter the pipe during work).
After evacuating the system for 2 hours, pressurize the
system to 0.05 MPa (vacuum break) with nitrogen gas and
evacuate the system again using the vacuum pump for
1 hour to –100.7 kPa (vacuum drying). If the system
cannot be evacuated to –100.7 kPa within 2 hours, repeat
the operation of vacuum break and vacuum drying. Then
after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

After air purging with a vacuum pump it may happen that
the refrigerant pressure does not rise, not even if the stop
valve is opened. Reason for this phenomenon is the closed
state of for instance the expansion valve in the outdoor unit
circuit, but this is not a problem for running the unit.

Summary of Contents for RZQ71D7V1B

Page 1: ...INSTALLATION MANUAL RZQ71D7V1B RZQ71D2V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vasta...

Page 4: ...ns or earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws an...

Page 5: ...salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the re...

Page 6: ...wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be fores...

Page 7: ...water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dime...

Page 8: ...and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuming is comple...

Page 9: ...te the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A insta...

Page 10: ...e effects If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be r...

Page 11: ...ions when connecting field piping and regarding insulation Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping ins...

Page 12: ...y closed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increa...

Page 13: ...amount is R1 R2 1 G1 total length of 9 5 mm liquid piping G2 total length of 6 4 mm liquid piping 2 a G1 30 m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30...

Page 14: ...ove and use the table below G1 total length of 12 7 mm liquid piping Length exceeding Chargeless length Model Liquid piping 0 5 m 5 10 m 10 15 m 15 20 m RZQ71 Main 12 7 0 5 1 0 RZQ100 140 Main 1 5 2 0...

Page 15: ...apacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the stop valve...

Page 16: ...e maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when...

Page 17: ...it decoration panel with infra red receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete tes...

Page 18: ...charge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 mode...

Page 19: ...NOTES NOTES...

Page 20: ...4PW48323 1B Copyright Daikin...