Installation manual

7

RZQ71~14 RZQ7 RZQ100~140B8W1B

Split System air conditioners

4PW48323-1B

In case of simultaneous operating system
-

Upward and downward piping should be performed at the 
main piping line.

-

Use branch piping kit (optional) for branching refrigerant 
pipes.

Precautions to be taken. (For details, refer to the manual attached to
branch piping kit.)

-

Install the branch pipes horizontally (with a maximum 
inclination of 15°) or vertically.

-

Length of branch pipe to the indoor unit should be as short as 
possible.

-

Try to keep lengths of both branch pipes to the indoor unit 
equal.

When using existing refrigerant piping
Pay attention to the following points when using existing
refrigerant piping

Perform a visual check on quality of residual oil in existing
refrigerant piping.
This check is extremely important because using existing
piping with deteriorated oil will cause compressor
breakdown.
- Put some residual oil of the pipes you want to reuse on a 

piece of white paper or on the white surface of an oil 
checking reference card and compare that oil colour with 
the circled colour of the oil checking reference card.

- If oil colour is identical to the circled colour or darker, 

replace the piping, install new piping or clean the piping 
thoroughly.

- If oil colour is lighter, the pipes can be reused without 

cleaning.

An oil checking reference card is indispensable for such
evaluation and can be obtained at your dealer.

In the following situations, the existing piping should not be
re-used and new piping should be installed.
- If the previously used model had problems with its 

compressor (this might cause oxidised coolant oil, scale 
residue and other adverse effects).

- If the indoor or outdoor units were disconnected from the 

piping for a long period of time (water or dirt might have 
gotten into the piping).

- If copper piping is corroded.

Flares should not be re-used but rather new ones made in
order to prevent leaks.

Check welded connections for gas leaks, if the local piping
has welded connections.

Replace deteriorated insulation with new material.

R

EFRIGERANT

 

PIPING

Field pipes can be installed in four directions.

Figure - Field pipes in four directions

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To install the connecting pipe to the unit in a downward direction,
make a knockout hole by penetrating the centre area around the
knockout hole using a 

Ø

6 mm drill. (See 

figure "Field pipes in

four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.

Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.

Cautions for handling stop valve

The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.

The names of parts of the stop valve are shown in the figure.

1

Drill

2

Centre area around knockout hole

3

Knockout hole

4

Slit

5

Connecting pipe

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

A

Forward

B

Backward

C

Sideways

D

Downward

1

Putty or insulating material 
(produced locally)

Make sure to keep the valve open during operation.

1

Service port

2

stop valve

3

Field piping connection

4

Valve cover

4

4

3

2

1

7

8

9

10

A

D

C

B

5

6

1

3

4

1

2

Summary of Contents for RZQ71D7V1B

Page 1: ...INSTALLATION MANUAL RZQ71D7V1B RZQ71D2V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vasta...

Page 4: ...ns or earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws an...

Page 5: ...salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the re...

Page 6: ...wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be fores...

Page 7: ...water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dime...

Page 8: ...and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuming is comple...

Page 9: ...te the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A insta...

Page 10: ...e effects If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be r...

Page 11: ...ions when connecting field piping and regarding insulation Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping ins...

Page 12: ...y closed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increa...

Page 13: ...amount is R1 R2 1 G1 total length of 9 5 mm liquid piping G2 total length of 6 4 mm liquid piping 2 a G1 30 m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30...

Page 14: ...ove and use the table below G1 total length of 12 7 mm liquid piping Length exceeding Chargeless length Model Liquid piping 0 5 m 5 10 m 10 15 m 15 20 m RZQ71 Main 12 7 0 5 1 0 RZQ100 140 Main 1 5 2 0...

Page 15: ...apacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the stop valve...

Page 16: ...e maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when...

Page 17: ...it decoration panel with infra red receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete tes...

Page 18: ...charge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 mode...

Page 19: ...NOTES NOTES...

Page 20: ...4PW48323 1B Copyright Daikin...

Reviews: