Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures

2

3

4

 and 

5

. Assume that the longest line in the figure corresponds

with the actual longest pipe, and the highest unit in the figure
corresponds with the actual highest unit.

Allowable pipe length

Existing or pre-installed piping can be used

1.

Piping must comply with the criteria below.

Pipe diameter must comply with the limitations as indicated in
paragraph 

"Refrigerant pipe size" on page 5

.

Piping length must be within limits of the allowable piping length
as in paragraph 

"Allowable pipe length and height difference" on

page 6

.

Piping must be designed for R410A. See paragraph 

"Selection of

piping material" on page 5

.

2.

Piping can be reused without cleaning when:

Total 1-way piping length: <50 m.

No compressor breakdown has occurred in the history of the unit
to be replaced.

A correct pump down operation can be executed:
- Operate the unit continuously for 30 minutes in cooling mode.
- Execute a pump down operation.
- Remove the air conditioning units to be replaced.

Check the contamination inside the existing piping.

If you cannot meet all these requirements, the existing pipes must be
cleaned or replaced after removing the air conditioning units to be
replaced.

3.

Prepare the flare connections for higher pressure. See paragraph

"Cautions for flare connection" on page 8

.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

During tests never pressurize the appliances with a pressure
higher than the maximum allowable pressure (see unit name
plate: PS).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

Allowable pipe length

Liquid pipe 

size

Model

71

100

125

140

Maximum total one-way piping length

Pair

L1

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m (95 m)

size-up

25 m 

(35 m)

35 m (45 m)

• Twin and triple
• Double twin

• L1+L2
• L1+L2+

L4

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m (95 m)

size-up

25 m 

(35 m)

35 m (45 m)

Maximum allowable piping length

(a)

(a) Parenthesized figure represents the equivalent length.

Twin

L1+L2+L3

60 m

75 m

75 m

Triple

L1+L2+L3
+L4

Double twin

L1+L2+L3
+L4+L5+
L6+L7

Maximum branch piping length

• Twin and triple
• Double twin

• L2
• L2+L4

20 m

Maximum difference between branch lengths

Twin

L2–L3

10 m

10 m

10 m

Triple

L2–L4

Double twin

• L2–L3
• L4–L5
• L6–L7
• (L2+L4)–

(L3+L7)

Maximum height between indoor and outdoor

All

H1

30 m

Maximum height between indoors

Twin, triple and 
double twin

H2

0.5 m

Chargeless length

All

L1+L2+L3
+L4+L5+
L6+L7

size-down

10 m

standard

30 m

size-up

15 m

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor unit

Regardless of the 

period

Summary of Contents for RZQ71D7V1B

Page 1: ...INSTALLATION MANUAL RZQ71D7V1B RZQ71D2V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vasta...

Page 4: ...ns or earthquakes Improper installation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws an...

Page 5: ...salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the re...

Page 6: ...wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be fores...

Page 7: ...water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dime...

Page 8: ...and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacuming is comple...

Page 9: ...te the room thoroughly right away Use R410A only when adding refrigerant Installation tools Make sure to use installation tools gauge manifold charge hose etc that are exclusively used for R410A insta...

Page 10: ...e effects If the indoor or outdoor units were disconnected from the piping for a long period of time water or dirt might have gotten into the piping If copper piping is corroded Flares should not be r...

Page 11: ...ions when connecting field piping and regarding insulation Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping ins...

Page 12: ...y closed before leak test or vacuuming Set up for vacuuming and leak test see figure 8 Procedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increa...

Page 13: ...amount is R1 R2 1 G1 total length of 9 5 mm liquid piping G2 total length of 6 4 mm liquid piping 2 a G1 30 m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30...

Page 14: ...ove and use the table below G1 total length of 12 7 mm liquid piping Length exceeding Chargeless length Model Liquid piping 0 5 m 5 10 m 10 15 m 15 20 m RZQ71 Main 12 7 0 5 1 0 RZQ100 140 Main 1 5 2 0...

Page 15: ...apacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the stop valve...

Page 16: ...e maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when...

Page 17: ...it decoration panel with infra red receiver first 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after finishing the complete tes...

Page 18: ...charge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 mode...

Page 19: ...NOTES NOTES...

Page 20: ...4PW48323 1B Copyright Daikin...

Reviews: