RZQ71~14 RZQ7 RZQ100~140B8W1B
Split System air conditioners
4PW48323-1B
Installation manual
6
Allowable pipe length and height difference
See the table below concerning lengths and heights. Refer to figures
2
,
3
,
4
and
5
. Assume that the longest line in the figure corresponds
with the actual longest pipe, and the highest unit in the figure
corresponds with the actual highest unit.
Allowable pipe length
Existing or pre-installed piping can be used
1.
Piping must comply with the criteria below.
•
Pipe diameter must comply with the limitations as indicated in
paragraph
"Refrigerant pipe size" on page 5
.
•
Piping length must be within limits of the allowable piping length
as in paragraph
"Allowable pipe length and height difference" on
page 6
.
•
Piping must be designed for R410A. See paragraph
"Selection of
piping material" on page 5
.
2.
Piping can be reused without cleaning when:
•
Total 1-way piping length: <50 m.
•
No compressor breakdown has occurred in the history of the unit
to be replaced.
•
A correct pump down operation can be executed:
- Operate the unit continuously for 30 minutes in cooling mode.
- Execute a pump down operation.
- Remove the air conditioning units to be replaced.
•
Check the contamination inside the existing piping.
If you cannot meet all these requirements, the existing pipes must be
cleaned or replaced after removing the air conditioning units to be
replaced.
3.
Prepare the flare connections for higher pressure. See paragraph
"Cautions for flare connection" on page 8
.
P
RECAUTIONS
ON
REFRIGERANT
PIPING
■
Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.
■
Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).
■
During tests never pressurize the appliances with a pressure
higher than the maximum allowable pressure (see unit name
plate: PS).
■
In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.
Great caution is needed when passing copper tubes through
walls.
Allowable pipe length
Liquid pipe
size
Model
71
100
125
140
Maximum total one-way piping length
Pair
L1
size-down
10 m (15 m)
standard
50 m
(70 m)
75 m (95 m)
size-up
25 m
(35 m)
35 m (45 m)
• Twin and triple
• Double twin
• L1+L2
• L1+L2+
L4
size-down
10 m (15 m)
standard
50 m
(70 m)
75 m (95 m)
size-up
25 m
(35 m)
35 m (45 m)
Maximum allowable piping length
(a)
(a) Parenthesized figure represents the equivalent length.
Twin
L1+L2+L3
—
60 m
75 m
75 m
Triple
L1+L2+L3
+L4
—
Double twin
L1+L2+L3
+L4+L5+
L6+L7
—
Maximum branch piping length
• Twin and triple
• Double twin
• L2
• L2+L4
—
20 m
Maximum difference between branch lengths
Twin
L2–L3
—
10 m
10 m
10 m
Triple
L2–L4
—
Double twin
• L2–L3
• L4–L5
• L6–L7
• (L2+L4)–
(L3+L7)
—
Maximum height between indoor and outdoor
All
H1
—
30 m
Maximum height between indoors
Twin, triple and
double twin
H2
—
0.5 m
Chargeless length
All
L1+L2+L3
+L4+L5+
L6+L7
size-down
≤
10 m
standard
≤
30 m
size-up
≤
15 m
Place
Installation period
Protection method
Outdoor unit
More than a month
Pinch the pipe
Less than a month
Pinch or tape the pipe
Indoor unit
Regardless of the
period