RZQ71~12 RZQ100~140B7W1B
Split System air conditioners
4PW21412-1A

Installation manual

8

When the outdoor unit is installed above the indoor unit the
following can occur:
The condensated water on the stop valve can move to the
indoor unit. To avoid this, please cover the stop valve with
sealing material.

If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should
be at least 20 mm in order to avoid condensation on the surface
of the sealing.

Be sure to insulate the liquid and gas-side field piping and the
refrigerant branch kit.

(The highest temperature that the gas-side piping can reach is
around 120°C, so be sure to use insulating material which is
very resistant.)

Cautions for flare connection

Please refer to the table for the dimensions for processing flares
and for the tightening torques. (Too much tightening will end up
in splitting of the flare.)

If a torque wrench is not available, be aware that the tightening
torque may increase suddenly. Do not tighten nuts any further
than to the angle as listed.

When connecting the flare nut, apply refrigerating machine oil to
the flare (inside and outside) and first screw the nut 3 or 4 turns
by hand.
Coat here with ether or ester oil.

After completing the installation, carry out a gas leak inspection
of the piping connections with nitrogen and such.

Cautions for necessity of a trap

Since there is fear of the oil held inside the riser piping flowing back into
the compressor when stopped and causing liquid compression
phenomenon, or cases of deterioration of oil return, it will be necessary
to provide a trap at an appropriate place in the riser gas piping.

Trap installation spacing. 

(See figure 6)

A

Outdoor unit

B

Indoor unit

C

Gas piping

D

Liquid piping

E

Oiltrap

H

Install trap at each difference in height of 10 m.

A trap is not necessary when the outdoor unit is installed in a
higher position than the indoor unit.

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidised
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation. When brazing pipes however, do not use oxidation
preventers. Residue of such preventers may result in choking of
pipes or malfunction of components.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

Any exposed piping may cause condensation or burns
if touched.

Piping 

size

Flare nut 

tightening torque

A dimensions for 

processing flares 

(mm)

Flare shape

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

19.3~19.7

Ø19.1

97.2~118.6 N•m 

(989.8~1208 kgf•cm)

23.6~24.0

Piping size

Further tightening angle

Recommended arm 

length of tool

Ø6.4

60°~90°

150 mm

Ø9.5

200 mm

Ø12.7

30°~60°

250 mm

Ø15.9

300 mm

Ø19.1

20°~35°

450 mm

2

1

3

5

5

A

4

4

6

1

Compressor

2

Terminal cover

3

Indoor and outdoor 
field piping

4

Corking, etc.

5

Insulation material

6

Bolts

A

Be careful with pipe, 
bolt and outer panel 
connections

R=0.4~0.8

45

° ±

2

90

°±

2

A

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

2

3

4

5

6

6

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...

Reviews: