VACUATING

Do not purge the air with refrigerants. Use a vacuum pump to
vacuum the installation. No additional refrigerant is provided for
air purging.

Pipes inside the units were checked for leaks by the
manufacturer. The refrigerant pipes fit on site are to be checked
for leaks by the installer.

Confirm that the valves are firmly closed before leak test or
vacuuming.

Set up for vacuuming and leak test: 

see 

figure 8

Procedure for leak test

Leak test must satisfy EN378-2.

1

Evacuate the pipes and check vacuum

(1)

. (No pressure increase

for 1 minute.)

2

Break the vacuum with a minimum of 2 bar of nitrogen. (Never
pressurize more than 4.0 MPa.)

3

Conduct leak test by applying soap water, etc. to the connecting
part of the pipes.

4

Discharge nitrogen.

5

Evacuate and check vacuum again

(1)

.

6

If the vacuum gauge no longer rises, the stop valves can be
opened.

C

HARGING

 

REFRIGERANT

Precaution for servicing

This unit requires additional charging of refrigerant according to the
length of pipe connected at the site. Charge the refrigerant to the
liquid pipe in its liquid state through the service port of the liquid stop
valve. Since R-410A is a mixed refrigerant, its composition changes if
charged in a state of gas and normal system operation would no
longer be assured.

On this model it is not necessary to charge additionaly if the piping
length 

30 m.

<5 m: See 

"Total charging weight of the refrigerant (after a leak, etc.)"

on page 10

.

Additional charging of refrigerant

The additional charging amounts relate to the refrigerant piping
length as in 

"Maximum total one-way piping length"

 of the table

in paragraph 

"Allowable pipe length and height difference" on

page 5

. (E.g. twin: L1+L2+L3).

Over 30 

m, please add refrigerant quantity according to

following table.

For future servicing, mark with a circle the selected amount on the
tables below

For pair system

Table 1: Additional charging of refrigerant <unit: kg>

For twin, triple, and double twin system

Please charge additionaly according to the following calculation.
(additional amount is R1+R2)

1.

G1: total length of 

Ø

9.5 mm liquid piping

G2: total length of 

Ø

6.4 mm liquid piping

2.a G1>30 m

calculate length over 30 m (=G1–30 m)
Based on this length decide R1, R2 in the table

G1

30 m and G1+G2>30 m

calculate total length over 

30

 m (=G1+G2–30 m)

Based on this decide R2 in the table, R1=0

3.

Total additional charge amount
R=R1+R2 (kg)

Table 2: Length <unit: m>, additional charging of refrigerant
<unit: kg>

A

Pair system

B

Simultaneous operation system

1

Pressure gauge

2

Nitrogen

3

Refrigerant

4

Weighing machine

5

Vacuum pump

6

Stop valve

7

Main pipe

8

Branched pipes

9

Pipe branching kit (optional)

(1) Use a 2-stage vacuum pump with a non return valve which 

can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
Evacuate the system from the liquid and gas pipes by using 
a vacuum pump for more than 2 hours and bring the system 
to –100.7 kPa. After keeping the system under that condition 
for more than one hour, check if the vacuum gauge rises or 
not. If it rises, the system may either contain moisture inside 
or have leaks.

Following should be executed if there is a possibility of
moisture remaining in the pipe (if piping work is carried out
during the raining season or over a long period of time,
rainwater may enter the pipe during work).
After evacuating the system for 2 hours, pressurize the
system to 0.05 MPa (vacuum break) with nitrogen gas and
evacuate the system again using the vacuum pump for
1 hour to –100.7 kPa (vacuum drying). If the system
cannot be evacuated to –100.7 kPa within 2 hours, repeat
the operation of vacuum break and vacuum drying. Then
after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

After air purging with a vacuum pump it may happen that
the refrigerant pressure does not rise, not even if the stop
valve is opened. Reason for this phenomenon is the closed
state of for instance the expansion valve in the outdoor unit
circuit, but this is not a problem for running the unit.

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

Standard liquid pipe size

Connected piping length is between

Model

30~40 m

40~50 m

50~60 m

60~75 m

RZQ71

0.5

1.0

RZQ100~140

1.5

2.0

Size up liquid pipe size

Connected piping length is between

Model

15~20 m

20~25 m

25~30 m

30~35 m

RZQ71

0.5

1.0

RZQ100~140

1.5

2.0

Liquid 
piping

Ø

Length exceeding “Chargeless length”

Model 

0~10

10~20

20~30

30~40

40~55

RZQ71~140

Main

9.5

0.5

1.0

1.5

2.0

2.5

R1

Branch

Branch

6.4

0.3

0.6

0.9

1.2

1.5

R2

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...

Reviews: