Installation manual

7

RZQ71~12 RZQ100~140B7W1B

Split System air conditioners

4PW21412-1A

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To install the connecting pipe to the unit in a downward direction,
make a knockout hole by penetrating the center area around the
knockout hole using a 

Ø

6 mm drill. (See 

figure "Field pipes in

four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.

Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.

Cautions for handling stop valve

The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.

The names of parts of the stop valve are shown in the figure.

Since the side boards may be deformed if only a torque wrench
is used when loosening or tightening flare nuts, always lock the
shut-off valve with a wrench and then use a torque wrench.
Do not place wrenches on the valve cover.

Applying an excessive torque may distort the interior stop valve
surface causing gas to leak inside the valve and causing the
flare nut to crack eventually.
Do not apply force on the valve cover, this may result in a
refrigerant leak.

For cooling operation under low ambient temperature or any
other operation under low pressure, apply silicon pad or similar
to prevent freezing of the gas stop valve flare nut (see figure).
Freezing of the flare nut may cause refrigerant leak.

How to use the shut-off valve

Use hexagonal wrenches 4 mm and 6 mm.

Opening the valve

1.

Place the hex wrench on the valve bar and turn counter-
clockwise.

2.

Stop when the valve bar no longer turns. It is now open.

Closing the valve

1.

Place the hex wrench on the valve bar and turn clockwise.

2.

Stop when the valve bar no longer turns. It is now closed.

Cautions for handling the valve cover

The valve cover is sealed where indicated by the arrow. 
Refer to the figure.
Take care not to damage it.

After operating the valve, be sure to tighten the valve cover
properly.

Check for refrigerant leakage after tightening the cap.

Cautions for handling service port

Always use a flexible charge hose with a push-rod and valve to
enable recovery of remaining refrigerant in the charge hose.

After the work, tighten the valve cover in place.
Tightening torque: 10.8~14.7 N•m

Precautions when connecting field piping and regarding 
insulation

Be careful not to let the indoor and outdoor branch piping come
into contact with the compressor terminal cover.
If the liquid-side piping insulation might come into contact with it,
adjust the height as shown in the figure below. Also, make sure
the field piping does not touch the bolts or outer panels of the
compressor.

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

A

Forward

B

Backward

C

Sideways

D

Downward

1

Putty or insulating material 
(produced locally)

Make sure to keep the valve open during operation.

1

Service port

2

Shut-off valve

3

Field piping connection

4

Valve cover

1

Spanner

2

Torque wrench

1

3

4

1

2

2

Silicon sealing pad
(Make sure there is no gap)

 Closing direction

A

Liquid side

B

Gas side

Tightening torque

Liquid pipe

13.5~16.5 N•m

Gas pipe

22.5~27.5 N•m

A

B

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...

Reviews: