RZQ71~12 RZQ100~140B7W1B
Split System air conditioners
4PW21412-1A

Installation manual

2

B

EFORE

 

INSTALLATION

Precautions for R-410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
-

Clean and dry

Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
-

Tight

Read 

"Precautions on refrigerant piping" on page 6

 carefully and

follow these procedures correctly.

Since R-410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant
is in state of gas, its composition changes and the system will
not work properly).

The connected indoor units must be indoor units designed
exclusively for R-410A.

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

Illustrations show class 125 outdoor unit type. Other types also
follow this installation manual.

This outdoor unit requires the pipe branching kit (optional) when
used as the outdoor unit for the simultaneous operation system.
Refer to catalogues for details.

Never operate the unit without the thermistor (R3T, R4T),
burning of the compressor may result.

WARNING

Live parts can be easily touched by accident.
Never leave the unit unattended during installation or
servicing when the service panel is removed.

When planning to relocate former installed units, you
must first recover the refrigerant after the pumping-
down operation. Refer to chapter 

"Precaution for

pumping-down operation" on page 10

.

Never directly touch any accidental leaking
refrigerant. This could result in severe wounds caused
by frostbite.

CAUTION

Ground the air conditioner.
Grounding resistance should be according to national
regulations
Do not connect the earth wire to gas or
water pipes, lightning conductor or
telephone earth wire.
Incomplete grounding may cause electric
shocks.

Gas pipe.
Ignition or explosion may occur if the gas leaks.

Water pipe.
Hard vinyl tubes are not effective grounds.

Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by a
lightning bolt.

Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may cause
electric shocks and fire.

Install drain piping according to this installation
manual to ensure good drainage, and insulate the
pipe to prevent condensation.
Improper drain piping may cause water leakage, and
make the furnitures get wet.

Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions
or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)

Do not rinse the outdoor unit. This may cause electric
shocks or fire.

CAUTION

Do not install the air conditioner in places such as the
following:

Where there is mist of mineral oil, oil spray or
vapor for example a kitchen.
Plastic parts may deteriorate, and cause them to
fall out or water to leak.

Where corrosive gas, such as sulfurous acid gas,
is produced.
Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.

Where there is machinery which emits
electromagnetic waves.
Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.

Where flammable gases may leak, where carbon
fiber or ignitable dust is suspended in the air or
where volatile flammables, such as thinner or
gasoline, are handled.
Such gases may cause a fire.

Where the air contains high levels of salt such as
that near the ocean.

Where voltage fluctuates a lot, such as that in
factories.

In vehicles or vessels.

Where acidic or alkaline vapour is present.

Since maximum working pressure is 4.0 MPa or 40 bar,
pipes of larger wall thickness may be required. Refer to
paragraph 

"Selection of piping material" on page 5

.

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...