Installation manual

1

RZQ71~12 RZQ100~140B7W1B

Split System air conditioners

4PW21412-1A

C

ONTENTS

Page

Safety considerations ........................................................................ 1

Before installation.............................................................................. 2

Selecting installation site................................................................... 3

Precautions on installation ................................................................ 4

Installation servicing space ............................................................... 4

Refrigerant pipe size and allowable pipe length ................................ 5

Precautions on refrigerant piping ...................................................... 6

Refrigerant piping.............................................................................. 6

Evacuating......................................................................................... 9

Charging refrigerant .......................................................................... 9

Electrical wiring work....................................................................... 11

Test operation.................................................................................. 12

Disposal requirements .................................................................... 13

Wiring diagram ................................................................................ 14

S

AFETY

 

CONSIDERATIONS

The precautions listed here are divided into the following two types.
Both cover very important topics, so be sure to follow them carefully.

RZQ71B8V3B

RZQ100B7W1B

RZQ100B8V3B

RZQ125B7W1B

RZQ125B8V3B

RZQ140B7W1B

Split System air conditioners

Installation manual

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

WARNING

If the warning is not observed, it may cause 
serious casualties.

CAUTION

If the caution is not observed, it may cause 
injury or damage to the equipment.

WARNING

For year round cooling applications with low indoor
humidity conditions, such as Electronic Data
Processing rooms, contact your dealer or see the
engineering databook or the service manual.

For use of air-conditioning units in applications with
temperature alarm settings it is advised to foresee a
delay of 10 minutes for signalling the alarm in case
the alarm temperature is exceeded. The air-
conditioning unit may stop for several minutes during
normal operation for “defrosting of the indoor unit” or
when in “thermostat-stop” operation.

WARNING

Ask your dealer or qualified personnel to carry out
installation work.  Do not install the machine by
yourself.
Improper installation may result in water leakage,
electric shocks or fire.

Perform installation work in accordance with this
installation manual.
Improper installation may lead to water leakage,
electric shocks or fire.

When a unit is installed in a small room, it is
necessary to take measures so that the leaked
refrigerant amount does not exceed the limit even if it
leaks. As for the measures to prevent the leak from
not exceeding the limit, please consult with your
distributor.
If the leaked amount exceeds the limit, it may cause
an oxygen deficiency accident.

Be sure to use only the specified accessories and
parts for installation work.
Failure to use the specified parts may result in water
leakage, electric shocks, fire, or the unit falling.

Install the air conditioner on a foundation that can
withstand its weight.
Insufficient strength may result in the fall of equipment
and causing injury.

Carry out the specified installation work in consideration
of strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due
to fall of equipment.

Make certain that all electrical work is carried out by
qualified personnel according to the local laws and
regulations and this installation manual, using a
separate circuit.
Insufficient capacity of the power supply circuit or
improper electrical construction may lead to electric
shocks or fire.

Make sure that all wiring is secure, using the specified
wires and ensuring that external forces do not act on
the terminal connections or wires.
Incomplete connection or fixing may cause a fire.

When wiring between the indoor and outdoor units,
and wiring the power supply, form the wires so that
the frontside panel can be securely fastened.
If the frontside panel is not in place, overheat of the
terminals, electric shocks or a fire may be caused.

If refrigerant gas leaks during installation work,
ventilate the area immediately.
Toxic gas may be produced if refrigerant gas comes
into contact with fire.

After completing the installation work, check to make
sure that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks
into the room and comes into contact with a source of
fire, such as a fan heater, stove or cooker.

Before touching electric terminal parts, turn off power
switch.

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...