Installation manual

5

RZQ71~12 RZQ100~140B7W1B

Split System air conditioners

4PW21412-1A

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

Selection of piping material

Construction material: phosphoric acid deoxidised seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R-410A piping must be in accordance with the
table below.

O=Annealed
1/2H=Half hard

Refrigerant pipe size

Pair system 

(See figure 2)

Simultaneous operation system (twin: see 

figure 3

, triple: see

figure 4

, double twin: see 

figure 5

)

 

The pipes between the outdoor unit and the branch (L1) should have
the same size as the outdoor connections. The pipes between the
branch and the indoor units (L2~L5) should have the same size as
the indoor connections. Branch: see marking '

' on figures 

3

4

and 

5

.

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures

2

3

4

 and 

5

. Assume that the longest line in the figure corresponds

with the actual longest pipe, and the highest unit in the figure
corresponds with the actual highest unit.

L

A

L

H

0<L

1/2H

150 (250)

1/2H<L

200 (300)

H<L

Installation impossible

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

To persons in charge of piping work:

Be sure to open the shut-off valve after piping
installing and vacuming is complete. (Running the
system with the valve closed may break the
compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance
with the freon collection and destruction law.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal
(BCuP) which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if
the flux contains fluoride, it will cause the coolant oil to
deteriorate, adversely affecting the coolant piping
system.

Pipe Ø

Temper grade of piping 

material

Minimal thickness t(mm)

6.4 / 9.5 / 12.7

O

0.80

15.9

O

1.00

19.1

1/2H

1000

(1500)

400 (600)

2000

(3000)

A

H

L

Refrigerant pipe size

(*)

(*)

In case of twin, triple and double twin applications, the listed refrigerant pipe 
sizes relate to the main pipes only. (L1 = the pipes between the outdoor unit and 
the branch in figures 

3

~

5

).

Gas pipe

Model

Size-down

Standard size

Size-up

RZQ71

Ø12.7

Ø15.9

RZQ100~140

Ø19.1

Liquid pipe

Model

Size-down

Standard size

Size-up

RZQ71~140

Ø6.4

Ø9.5

Ø12.7

NOTE

Not using the standard pipe size may result in capacity
decrease. It is up to the installer to judge on this
phenomena carefully in function of the complete
installation.

Allowable pipe length

Liquid pipe 

size

Model

71

100

125

140

Maximum allowable piping length

(*)

Pair

L1

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m (95 m)

size-up

25 m 

(35 m)

35 m (45 m)

• Twin and triple
• Double twin

• L1+L2
• L1+L2+

L4

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m (95 m)

size-up

25 m 

(35 m)

35 m (45 m)

Maximum total one-way piping length

Twin

L1+L2+L3

60 m

75 m

75 m

Triple

L1+L2+L3
+L4

Double twin

L1+L2+L3
+L4+L5+
L6+L7

Maximum branch piping length

• Twin and triple
• Double twin

• L2
• L2+L4

20 m

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...

Reviews: