background image

RZQ71~12 RZQ100~140B7W1B
Split System air conditioners
4PW21412-1A

Installation manual

10

Example 1

1

G1=L1=35 m

G2=L2+L3=7+5=12

2

Over 

30 

 m

a

G1

30=5 m

  Ø9.5 R1=0.5 kg

b

G2=12 m 

  Ø6.4 R2=0.6 kg

3

Refrigerant charge amount=R=R1+R2=0.5+0.6=1.1 kg

Example 2

1

G1=L1=5 m

G2=L2+L3+L4=17+17+20=54

2

Over 

30 

m

a

G1=5 m

 R1=0.0 kg

b

(G1+G2)

30=(5+54)

30=29

 Ø6.4 R2=0.9 kg

3

Refrigerant charge amount=R=R1+R2=0.0+0.9=0.9 kg

Total charging weight of the refrigerant (after a leak, 
etc.)

The total charging amounts relate to the refrigerant piping length
as in 

"Maximum allowable piping length"

  of the table in

paragraph 

"Allowable pipe length and height difference" on

page 5

. (E.g. twin: L1+L2).

Table 3: Total charging amount <unit: kg>

Precaution for pumping-down operation

The outdoor unit is equipped with a low pressure switch or a low
pressure sensor to protect the compressor.

Take the following steps to perform the pumping-down operation.

Preliminary measures

Make sure to cut off power supply.
Open the front panel and cover the PCB and terminal board with
insulation sheet to avoid electric shock by accidental touching of
live parts.

Close the front panel before leaving the outdoor unit. You cannot
leave the unit unattended in case the front panel remains opened.

Turn on the power supply and carry out pumping-down operation
according to the following procedure.

Pump down operation

(†)  If after finishing pumping-down operation the outdoor unit does
not operate, not even when the remote controller switch is turned on,
the remote controller may or may not indicate “U4”. But this is not a
malfunction.

After finishing the pumping-down operation, make sure to have
removed the insulation sheet that was placed in the switch box as
a protective measure like in chapter 

"Preliminary measures" on

page 10

.

When in need of operation, turn off the main power supply and
turn it on again. Make sure that stop valves both on liquid and gas
side are open and be sure to operate the unit in cooling operation
during test run.

L2=7 (Ø6.4)

50 type

100 type

L1=35 (Ø9.5)

indoor

L3=5 (Ø6.4)

50 type

outdoor heat pump

L2=17 (Ø6.4)

50 type

indoor

125 type

L1=5 (Ø9.5)

L3=17 (Ø6.4)

50 type

outdoor heat pump

indoor

L4=20 (Ø6.4)

50 type

In case of complete recharge of the refrigerant, please first
execute vacuuming. Execute this vacuuming from the
service port. Do not use the port of the stop valve for
vacuuming. Vacuuming can not be executed completely
using such port.

Position of service port:

Heat pump: Heat pump units have 2 ports on the
piping. One between the liquid receiver and the
electronic expansion valve and another one between
the heat exchanger and the 4-way valve.

Systems with sized-up liquid pipe

Replace 30 m by 15 m in calculations above and use
the table below.

G1: total length of Ø12.7 mm liquid piping.

Length exceeding 

“Chargeless length”

Model

Liquid 
piping

Ø

0~5 m

5~10 m

10~15 m

15~20 m

RZQ71

Main

12.7

0.5

1.0

R1

RZQ100~140

Main

1.5

2.0

RZQ71~140

Branch

6.4

0.3

0.6

R2

RZQ140

Branch

9.5

0.5

1.0

R2

Refrigerant piping length

Model

Liquid pipe 

size

3~5

(*)

 m

5~10 m

10~20 m

20~30 m

30~40 m

40~50 m

50~60 m

60~75 m

RZQ71

size-down

1.8

1.8

standard

1.8

1.8

2.3

2.8

3.3

3.8

RZQ100~140

size-down

3.3

3.3

standard

3.3

3.3

3.8

4.3

4.8

5.3

5.8

6.3

Refrigerant piping length

Model

Liquid pipe 

size

3~5

(*)

 m

(*)

When piping length is less than 5 m, a complete recharging of the unit is required. 
Charge the unit with the refrigerant charge as indicated.

5~10 m

10~15 m

15~20 m

20~25 m

25~30 m

30~35 m

RZQ71

size-up

2.3

2.3

2.8

3.3

3.8

RZQ100~140

3.8

3.8

4.3

4.8

5.3

5.8

6.3

Never short-circuit the low pressure switch or low pressure
sensor during pump-down operation.

Procedure

Precaution

1

Make sure that stop valves both on 
liquid and on gas side are open.

2

Push the pumping-down operation 
button on the PC board of the 
outdoor unit.

Compressor and outdoor fan will 
start operation automatically.
The indoor unit fan may 
automatically start running.
Please pay attention to this.

3

Once operation stops after 3 or 5 
minutes

(†)

, close the stop valve on 

the liquid side and gas side 
securely. (See 

"How to use the 

shut-off valve" on page 7

)

Never leave the outdoor unit 
unattended with opened front 
panel when power supply is on.

4

Turn off the power supply.

Summary of Contents for RZQ71B8V3B

Page 1: ...INSTALLATION MANUAL RZQ71B8V3B RZQ100B8V3B RZQ125B8V3B RZQ100B7W1B RZQ125B7W1B RZQ140B7W1B Split System air conditioners...

Page 2: ...5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmi...

Page 4: ...ourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage...

Page 5: ...r telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conducto...

Page 6: ...more blowing against the outdoor unit s air outlet causes short circuit suction of discharge air and this may have the following consequences Deterioration of the operational capacity Frequent frost...

Page 7: ...pipe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain...

Page 8: ...To persons in charge of piping work Be sure to open the shut off valve after piping installing and vacuming is complete Running the system with the valve closed may break the compressor It is forbidd...

Page 9: ...g the piping cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultaneous operating system Upward and downward piping should be perfor...

Page 10: ...the gas stop valve flare nut see figure Freezing of the flare nut may cause refrigerant leak How to use the shut off valve Use hexagonal wrenches 4 mm and 6 mm Opening the valve 1 Place the hex wrenc...

Page 11: ...y to provide a trap at an appropriate place in the riser gas piping Trap installation spacing See figure 6 A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each di...

Page 12: ...m calculate length over 30 m G1 30 m Based on this length decide R1 R2 in the table b G1 30 m and G1 G2 30 m calculate total length over 30 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Tot...

Page 13: ...2 7 6 4 50 type 100 type L1 35 9 5 indoor L3 5 6 4 50 type outdoor heat pump L2 17 6 4 50 type indoor 125 type L1 5 9 5 L3 17 6 4 50 type outdoor heat pump indoor L4 20 6 4 50 type In case of complete...

Page 14: ...ing accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to the shut off valve attachment plate...

Page 15: ...ring test run Tightening torque N m M4 X1M 1 2 1 8 M5 X1M 2 0 3 0 M5 EARTH 3 0 4 0 I Pair II Twin III Triple IV Double twin M Master S Slave 1 Earth leakage breaker 2 Fuse 3 Remote controller 1 2 3 1...

Page 16: ...4 In case of a wireless remote controller execute the test run only after having installed the indoor unit decoration panel with infra red receiver first 5 In case the panels of indoor units are not y...

Page 17: ...ld supply R1 R2 Resistor R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor l...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN21412 1A...

Reviews: