Outdoor Unit Installation

7. 

Wiring

 WARNING

•  Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fi re.
• 

Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal 

block.) Doing so may cause electric shock or fi re.

• 

Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that an earth leak detector capable of handling harmonics must be used in order to 
prevent any malfunction of the earth leak detector itself.)

•  Use an all-pole disconnection type circuit breaker with at least 3mm between the contact point gaps.
• 

The earth leakage circuit breaker must operate at 30mA or lower.

•  Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fi re.

• 

Do not turn on the circuit breaker until all work is completed.
1)  Strip the insulation from the wire (20mm).
2)  Connect the inter-unit wires between the indoor and outdoor units 

so that the terminal numbers match

. Tighten the terminal 

screws securely. We recommend a fl athead screwdriver be used to tighten the screws. The screws are packed with the terminal 

block.

1

2

3

1 2 3

L N

Power supply wire
3-core 2.5mm² or more 
60245 IEC 57

H05RN

Firmly fi x the wires with the terminal screws.

Inter-unit wire 
4-core 1.5mm² or more 
60245 IEC 57

H05RN

Indoor 

unit

Outdoor 

unit

Circuit breaker 
16A

Earth leakage 
circuit breaker

Power supply 

50Hz 220-240V

Earth

Firmly fi x the wires with 

the terminal screws.

1

2

3

Use the specifi ed wire type 

and connect it securely.

1

2

3

Power supply 
terminal block

Firmly secure wire retainer 
so wire terminations will 
not receive external stress.

Shape wires so 
that the service 

lid fi ts securely.

 CAUTION 

• 

When using stranded wires, make sure to use a 
round crimp-style terminal for connection to the 
power supply terminal block.
Place the round crimp-style terminals on the wires 
up to the covered part and secure in place.

Stranded wire

Round crimp-style 
terminal

•  Use the following method when installing a round crimp-style terminal.

 

A

Flat washer

Screw

Round crimp-style terminal

Good

Flat washer

Screw
Round crimp-style 
terminal

Wrong

Screw

Round crimp-style 
terminal

Flat washer

Arrow view 

A

 

•  Use the following method when installing a single 

core wire.

Good

Wrong

01_EN_3P338604-1E.indd   15

2/18/2019   14:09:26

Summary of Contents for RXZ25NV1B9

Page 1: ...llation manual R32 Split series Manuel d installation S rie split R32 Manual de instalaci n Serie Split R32 Manuale d installazione Serie Multiambienti R32 R32 R32 Montaj k lavuzlar R32 Split serisi F...

Page 2: ...tions on Installation of Outdoor Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evac...

Page 3: ...power supply circuit only Insuf ciency of power circuit capacity and improper workmanship may result in electric shocks or re Use a cable of suitable length Do not use tapped wires or an extension le...

Page 4: ...break out While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in in...

Page 5: ...inlet and outlet are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shor...

Page 6: ...t 11 the air is clean and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambien...

Page 7: ...he ceiling surface Do not install the trap to the G humidifying hose as much as possible The are connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidi...

Page 8: ...aining metal frame or metal board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or re Be sure to caulk the gaps around the...

Page 9: ...w eld supply bands at 10mm from the joint or an elbow eld supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose R...

Page 10: ...ide left back or left bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G...

Page 11: ...cting to the HA system Run the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid ts securely then close the service lid 1...

Page 12: ...tube eld supply 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially availab...

Page 13: ...below 2 Drain work 1 Use H drain socket for drainage 2 If the drain port is covered by a mounting base or oor surface place additional foot bases of at least 30mm in height under the outdoor unit s fe...

Page 14: ...nt piping work 5 1 Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a...

Page 15: ...d s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge read...

Page 16: ...al screws securely We recommend a athead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05...

Page 17: ...unoperated for 60 seconds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller to...

Page 18: ...ling the front grille Removal method 1 Remove the front panel 2 Direct the ap and the auxiliary ap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right...

Page 19: ...ite 4 Route the HA connection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions...

Page 20: ...Pull down Dust box 2 Direct the display unit black upward and remove the air lter Display unit black Air lter 3 Install the B air purifying and deodorising lter B Air purifying and deodorising lter Ta...

Page 21: ...operly on solid bases Fall vibration noise narrower detectable range of the INTELLIGENT EYE sensor Are the air lter and the dust box attached properly Noise water leakage CLEANING FILTER operation dis...

Page 22: ...The two dimensional bar code is a manufacturing code 3P338604 1E M12B406D 1903 HT...

Reviews: