Outdoor Unit Installation Guidelines

•  Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airfl ow, follow the installation guidelines below.
• 

For any of the below installation patterns, the wall height on the outlet side should be 1200mm or less.

Wall facing one side

More than 50

More than 100

Direction 
of air

1200 
or less

Walls facing two sides

More than 50

More 
than 100

More 
than 200

More than 50

More than 50

More than 150

Walls facing three sides

More than 150

More than 50

More than 300

Side view

Top view

Top view

unit: mm

Precautions on Installation of Outdoor Unit

• 

Check the strength and level of the installation surface so that the unit does not cause any operating 
vibration or noise after installation.

•  In accordance with the foundation drawing, fi x the unit securely by means of the foundation bolts. (Prepare 

4 sets of M8 or M10 foundation bolts, nuts and washers each which are available on the market.)

• 

It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface.

20

Outdoor Unit Installation

1. 

Installing outdoor unit

1) 

When installing the outdoor unit, refer to “

Choosing an Installation Site” 

on page 5 and the “

Indoor/Outdoor Unit Installation 

Drawings” 

on page 6.

2)  If drain work is necessary, follow the procedures below.

2. 

Drain work

1) 

Use 

H

 drain socket for drainage.

2) 

If the drain port is covered by a mounting base or fl oor surface, place 

additional foot bases of at least 30mm in height under the outdoor 
unit’s feet.

3)  In cold areas, do not use a drain hose with the outdoor unit. 

(Otherwise, drain water may freeze, impairing heating performance.)

Drain hole

Air outlet side

ɸ

18 hole

(Bottom view)

Bottom frame

H

 Drain socket

Hose (available commercially, 
inner dia. 16mm)

3. 

Flaring the pipe end

1)  Cut the pipe end with a pipe cutter.
2)  Remove burrs with the cut surface facing 

downward so that the chips do not enter the 
pipe.

3) 

Put the fl are nut on the pipe.

4)  Flare the pipe.
5) 

Check that the fl aring is properly made.

Remove 
burrs

Cut exactly at 
right angles.

The pipe end must 

be evenly fl ared in a 

perfect circle.

Flare’s inner 
surface must be 

fl aw-free.

Make sure that the 

fl are nut is fi tted.

Check

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R32 or R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

 WARNING

•  Do not use mineral oil on fl ared part.
• 

Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.

•  Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
•  Never install a drier to this R32 unit in order to guarantee its lifetime.
• 

The drying material may dissolve and damage the system.

•  Incomplete fl aring may cause refrigerant gas leakage.

01_EN_3P338604-1E.indd   12

2/18/2019   14:09:22

Summary of Contents for RXZ25NV1B9

Page 1: ...llation manual R32 Split series Manuel d installation S rie split R32 Manual de instalaci n Serie Split R32 Manuale d installazione Serie Multiambienti R32 R32 R32 Montaj k lavuzlar R32 Split serisi F...

Page 2: ...tions on Installation of Outdoor Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evac...

Page 3: ...power supply circuit only Insuf ciency of power circuit capacity and improper workmanship may result in electric shocks or re Use a cable of suitable length Do not use tapped wires or an extension le...

Page 4: ...break out While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in in...

Page 5: ...inlet and outlet are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shor...

Page 6: ...t 11 the air is clean and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambien...

Page 7: ...he ceiling surface Do not install the trap to the G humidifying hose as much as possible The are connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidi...

Page 8: ...aining metal frame or metal board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or re Be sure to caulk the gaps around the...

Page 9: ...w eld supply bands at 10mm from the joint or an elbow eld supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose R...

Page 10: ...ide left back or left bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G...

Page 11: ...cting to the HA system Run the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid ts securely then close the service lid 1...

Page 12: ...tube eld supply 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially availab...

Page 13: ...below 2 Drain work 1 Use H drain socket for drainage 2 If the drain port is covered by a mounting base or oor surface place additional foot bases of at least 30mm in height under the outdoor unit s fe...

Page 14: ...nt piping work 5 1 Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a...

Page 15: ...d s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge read...

Page 16: ...al screws securely We recommend a athead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05...

Page 17: ...unoperated for 60 seconds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller to...

Page 18: ...ling the front grille Removal method 1 Remove the front panel 2 Direct the ap and the auxiliary ap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right...

Page 19: ...ite 4 Route the HA connection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions...

Page 20: ...Pull down Dust box 2 Direct the display unit black upward and remove the air lter Display unit black Air lter 3 Install the B air purifying and deodorising lter B Air purifying and deodorising lter Ta...

Page 21: ...operly on solid bases Fall vibration noise narrower detectable range of the INTELLIGENT EYE sensor Are the air lter and the dust box attached properly Noise water leakage CLEANING FILTER operation dis...

Page 22: ...The two dimensional bar code is a manufacturing code 3P338604 1E M12B406D 1903 HT...

Reviews: