To perform a trial operation for humidifying operation, activate trial operation mode from the 
remote controller following the instructions below and press 

Trial operation from remote controller

1)  Press 

 for at least 5 seconds. (The default menu will be displayed.)

2)  Press 

 to select “

Test mode

” and press 

 . 

• 

The unit enters trial operation mode, and 

 is displayed on the screen.

3) 

Press the button for the operation mode (COOLING/HEATING/HUMIDFY) you want to test.

• 

Trial operation will stop automatically after about 30 minutes.

To quit a trial operation, press 

 .

3-4 

Operate the unit in accordance with the operation manual to check that it operates normally

3-5 

Make sure that the air conditioner is not in operation before performing CLEANING FILTER 
operation

1)  Press 

 and make sure that CLEANING FILTER operation functions without error.

3-6 

After trial operation, reset the total power consumption

1)  Press 

.

2)  Press 

 to select “

RESET USED POWER

” and press 

.

3) 

RESET with APPLY

” is displayed. When you press 

, the total power consumption is reset.

• 

Even when the air conditioner is not operating, it consumes some electric power. If the customer is not going to use the unit 
soon after it is installed, turn off the circuit breaker to avoid wasting electricity.

4. 

Test items

Test items

Symptom

Check

Indoor and outdoor units are installed properly on solid bases.

Fall, vibration, noise, narrower detectable 

range of the INTELLIGENT EYE sensor

Are the air fi lter and the dust box attached properly?

Noise, water leakage, CLEANING FILTER

 

operation disabled

Did you install the air-purifying and deodorising fi lter?

Noise, water leakage, CLEANING FILTER

 

operation disabled

Have you performed a leak test to ensure that there are no refrigerant gas leaks?

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are thermally 

insulated.

Water leakage

Draining line is properly installed.

Water leakage

Did you ask the customer whether drain work for the outdoor unit is necessary?

Dripping of drain water from the hole in the 
bottom of the outdoor unit

Does the drain hose produce abnormal noise (clopping sound) when using the 

ventilation fan or others?

Noise (Use of optional air cut drain plug.)

System is properly earthed.

Electric shock hazard

The specifi ed wires are used for inter-unit wiring connections.

Inoperative or burn damage

Indoor or outdoor unit’s air inlet or outlet has clear path of air.

Incomplete cooling/heating function

Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote controller commands.

Inoperative

Did you check the address setting?

Inoperative

Did you set the humidifying hose length?

•  The OPERATION lamp blinks for about 

2 minutes from power-on while the air 
conditioner is stopped.

• 

Poor performance and noise

Did you set the room shape properly?

Poor cooling performance

01_EN_3P338604-1E.indd   20

2/18/2019   14:09:35

Summary of Contents for RXZ25NV1B9

Page 1: ...llation manual R32 Split series Manuel d installation S rie split R32 Manual de instalaci n Serie Split R32 Manuale d installazione Serie Multiambienti R32 R32 R32 Montaj k lavuzlar R32 Split serisi F...

Page 2: ...tions on Installation of Outdoor Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evac...

Page 3: ...power supply circuit only Insuf ciency of power circuit capacity and improper workmanship may result in electric shocks or re Use a cable of suitable length Do not use tapped wires or an extension le...

Page 4: ...break out While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in in...

Page 5: ...inlet and outlet are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shor...

Page 6: ...t 11 the air is clean and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambien...

Page 7: ...he ceiling surface Do not install the trap to the G humidifying hose as much as possible The are connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidi...

Page 8: ...aining metal frame or metal board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or re Be sure to caulk the gaps around the...

Page 9: ...w eld supply bands at 10mm from the joint or an elbow eld supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose R...

Page 10: ...ide left back or left bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G...

Page 11: ...cting to the HA system Run the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid ts securely then close the service lid 1...

Page 12: ...tube eld supply 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially availab...

Page 13: ...below 2 Drain work 1 Use H drain socket for drainage 2 If the drain port is covered by a mounting base or oor surface place additional foot bases of at least 30mm in height under the outdoor unit s fe...

Page 14: ...nt piping work 5 1 Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a...

Page 15: ...d s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge read...

Page 16: ...al screws securely We recommend a athead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05...

Page 17: ...unoperated for 60 seconds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller to...

Page 18: ...ling the front grille Removal method 1 Remove the front panel 2 Direct the ap and the auxiliary ap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right...

Page 19: ...ite 4 Route the HA connection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions...

Page 20: ...Pull down Dust box 2 Direct the display unit black upward and remove the air lter Display unit black Air lter 3 Install the B air purifying and deodorising lter B Air purifying and deodorising lter Ta...

Page 21: ...operly on solid bases Fall vibration noise narrower detectable range of the INTELLIGENT EYE sensor Are the air lter and the dust box attached properly Noise water leakage CLEANING FILTER operation dis...

Page 22: ...The two dimensional bar code is a manufacturing code 3P338604 1E M12B406D 1903 HT...

Reviews: