Outdoor Unit Installation

4. 

Refrigerant piping

 CAUTION

•  Use the fl are nut fi xed to the main unit. (To prevent cracking of the fl are nut by aged deterioration.)
•  To prevent gas leakage, apply refrigeration oil only to the inner surface of the fl are. (Use refrigeration oil for R32.)
•  Use torque wrenches when tightening the fl are nuts to prevent damage to the fl are nuts and gas leakage.

•  Align the centres of both fl ares and tighten the fl are nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches. 
•  Refrigerant oil for R410A can also be used for application to the inner fl are.

Flare nut tightening torque

Gas side

Liquid side

9.5mm

6.4mm

32.7-39.9N · m

(333-407kgf · cm)

14.2-17.2N · m

(144-175kgf · cm)

Valve cap tightening torque

Gas side

Liquid side

9.5mm

6.4mm

21.6-27.4N · m

(220-280kgf · cm) 

Service port cap tightening torque

10.8-14.7N · m (110-150kgf · cm)

Torque wrench

Flare nut

Apply refrigeration 
oil to the inner 
surface of the 

fl are.

Do not apply 
refrigeration oil to 
the outer surface.

Flare nut

Do not apply refrigeration oil to 

the fl are nut to avoid tightening 
with excessive torque.

Apply oil

Tighten

Piping union

Spanner

5. 

Refrigerant piping work

5-1  Cautions on pipe handling

• 

Protect the open end of the pipe against dust and moisture.

•  All pipe bends should be as gentle as possible. Use a pipe 

bender for bending.

Be sure to place a cap.

If no fl are cap is 

available, cover the 

fl are mouth with tape 

to keep dirt or water 
out.

Rain

Wall

5-2  Selection of copper and heat insulation materials

When using commercial copper pipes and fi ttings, observe the following:

• 

Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

•  Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below. 

Seal the edge of the insulation 
if there is a possibility that the 
condensation from the stop valve 
might drip onto the indoor unit 
through the gap between the 
insulation and the pipe.

Inter-unit wire

G

 Humidifying hose

Finishing tape

Liquid pipe insulation

Liquid pipe

Gas pipe

Gas pipe insulation

Piping bundle diagram

Gas side

Liquid side

Gas pipe thermal insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Minimum bend radius

Thickness 10mm Min.

30mm or more

Thickness 0.8mm (C1220T-O)

•  Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

01_EN_3P338604-1E.indd   13

2/18/2019   14:09:24

Summary of Contents for RXZ25NV1B9

Page 1: ...llation manual R32 Split series Manuel d installation S rie split R32 Manual de instalaci n Serie Split R32 Manuale d installazione Serie Multiambienti R32 R32 R32 Montaj k lavuzlar R32 Split serisi F...

Page 2: ...tions on Installation of Outdoor Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evac...

Page 3: ...power supply circuit only Insuf ciency of power circuit capacity and improper workmanship may result in electric shocks or re Use a cable of suitable length Do not use tapped wires or an extension le...

Page 4: ...break out While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in in...

Page 5: ...inlet and outlet are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shor...

Page 6: ...t 11 the air is clean and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambien...

Page 7: ...he ceiling surface Do not install the trap to the G humidifying hose as much as possible The are connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidi...

Page 8: ...aining metal frame or metal board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or re Be sure to caulk the gaps around the...

Page 9: ...w eld supply bands at 10mm from the joint or an elbow eld supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose R...

Page 10: ...ide left back or left bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G...

Page 11: ...cting to the HA system Run the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid ts securely then close the service lid 1...

Page 12: ...tube eld supply 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially availab...

Page 13: ...below 2 Drain work 1 Use H drain socket for drainage 2 If the drain port is covered by a mounting base or oor surface place additional foot bases of at least 30mm in height under the outdoor unit s fe...

Page 14: ...nt piping work 5 1 Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a...

Page 15: ...d s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge read...

Page 16: ...al screws securely We recommend a athead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05...

Page 17: ...unoperated for 60 seconds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller to...

Page 18: ...ling the front grille Removal method 1 Remove the front panel 2 Direct the ap and the auxiliary ap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right...

Page 19: ...ite 4 Route the HA connection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions...

Page 20: ...Pull down Dust box 2 Direct the display unit black upward and remove the air lter Display unit black Air lter 3 Install the B air purifying and deodorising lter B Air purifying and deodorising lter Ta...

Page 21: ...operly on solid bases Fall vibration noise narrower detectable range of the INTELLIGENT EYE sensor Are the air lter and the dust box attached properly Noise water leakage CLEANING FILTER operation dis...

Page 22: ...The two dimensional bar code is a manufacturing code 3P338604 1E M12B406D 1903 HT...

Reviews: