background image

14

14

6. 

Evacuating the air with a vacuum pump and checking gas leakage

 WARNING

•  Do not mix any substance other than the specifi ed refrigerant (R32) into the refrigeration cycle.
• 

When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.

• 

R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.

• 

Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter).

• 

When piping work is completed, it is necessary to evacuate 
the air with a vacuum pump and check for gas leakage.

•  Use a hexagonal wrench (4mm) to operate the stop valve rod.
•  All refrigerant pipe joints should be tightened with a torque 

wrench at the specifi ed tightening torque.

Compound 
pressure gauge

Pressure 
meter

Gauge 

manifold

Low-pressure 
valve

High-pressure 
valve

Charging 
hoses

Vacuum pump 
adapter

Vacuum pump

Valve caps

Gas stop 

valve

Service port

Liquid stop 

valve

1) 

Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2)  Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).

(High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).

(The vacuum pump should run for at least 10 minutes.)

4)  Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. 

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*1

5) 

Remove covers from liquid stop valve and gas stop valve.

6) 

Turn the liquid stop valve’s rod 90° counterclockwise with a hexagonal wrench to open valve.

Close it after 5 seconds, and check for gas leakage.

Using soapy water, check for gas leakage from indoor unit’s fl are and outdoor unit’s fl are and valve rods.

After the check is complete, wipe all soapy water off.

7) 

Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) 

Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specifi ed torques.

*1  If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exist. Check all 

pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

01_EN_3P338604-1E.indd   14

2/18/2019   14:09:24

Summary of Contents for RXZ25NV1B9

Page 1: ...llation manual R32 Split series Manuel d installation S rie split R32 Manual de instalaci n Serie Split R32 Manuale d installazione Serie Multiambienti R32 R32 R32 Montaj k lavuzlar R32 Split serisi F...

Page 2: ...tions on Installation of Outdoor Unit 12 Outdoor Unit Installation 12 1 Installing outdoor unit 12 2 Drain work 12 3 Flaring the pipe end 12 4 Refrigerant piping 13 5 Refrigerant piping work 13 6 Evac...

Page 3: ...power supply circuit only Insuf ciency of power circuit capacity and improper workmanship may result in electric shocks or re Use a cable of suitable length Do not use tapped wires or an extension le...

Page 4: ...break out While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent condensation Improper drain piping may result in in...

Page 5: ...inlet and outlet are free of obstructions 3 the unit is not in the path of direct sunlight 4 the unit is away from the source of heat or steam 5 there is no source of machine oil vapour this may shor...

Page 6: ...t 11 the air is clean and there are no sources of unpleasant odours close by NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambien...

Page 7: ...he ceiling surface Do not install the trap to the G humidifying hose as much as possible The are connection should be installed outdoors Install the hose with a downward slope Do not bend the G humidi...

Page 8: ...aining metal frame or metal board be sure to use a wall embedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or re Be sure to caulk the gaps around the...

Page 9: ...w eld supply bands at 10mm from the joint or an elbow eld supply to ing hose from coming off Use not more than 1 elbow to ensure humidifying capacity 4 3 How to replace the drain plug and drain hose R...

Page 10: ...ide left back or left bottom piping Left side piping Left back piping Left bottom piping Remove pipe port cover Refrigerant pipe G Humidifying hose Drain hose Refrigerant pipe Remove pipe port cover G...

Page 11: ...cting to the HA system Run the HA connection cord and attach the S21 Refer to Connecting to the HA system on page 18 6 Shape the wires so that the service lid ts securely then close the service lid 1...

Page 12: ...tube eld supply 5 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially availab...

Page 13: ...below 2 Drain work 1 Use H drain socket for drainage 2 If the drain port is covered by a mounting base or oor surface place additional foot bases of at least 30mm in height under the outdoor unit s fe...

Page 14: ...nt piping work 5 1 Cautions on pipe handling Protect the open end of the pipe against dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Be sure to place a...

Page 15: ...d s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge read...

Page 16: ...al screws securely We recommend a athead screwdriver be used to tighten the screws The screws are packed with the terminal block 1 2 3 1 2 3 L N Power supply wire 3 core 2 5mm or more 60245 IEC 57 H05...

Page 17: ...unoperated for 60 seconds The display will return to the normal display 2 Press Select Hose length 3 Press to enter the humidifying hose length setting mode Be sure to direct the remote controller to...

Page 18: ...ling the front grille Removal method 1 Remove the front panel 2 Direct the ap and the auxiliary ap downward 3 Remove the streamer unit See Fig 1 4 Remove the screws that secure the front grille right...

Page 19: ...ite 4 Route the HA connection cord 5 Reattach the electrical wiring box cover to the original position 3 tabs 6 Reattach the front grille right streamer unit and front panel to the original positions...

Page 20: ...Pull down Dust box 2 Direct the display unit black upward and remove the air lter Display unit black Air lter 3 Install the B air purifying and deodorising lter B Air purifying and deodorising lter Ta...

Page 21: ...operly on solid bases Fall vibration noise narrower detectable range of the INTELLIGENT EYE sensor Are the air lter and the dust box attached properly Noise water leakage CLEANING FILTER operation dis...

Page 22: ...The two dimensional bar code is a manufacturing code 3P338604 1E M12B406D 1903 HT...

Reviews: