background image

Installation manual

2

RXYSQ4~6M7V3B

VRVII-S system air conditioner

4PW17806-1C

2.

I

NTRODUCTION

2.1.

Combination

The indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R-410A.
To  learn which models of indoor units are compatible with
R-410A, refer to the product catalogs.

Total capacity/quantity of indoor units 

2.2.

Standard supplied accessories 

Location of accessories: refer to 

figure 1

.

2.3.

Optional accessories

To  install the above outdoor units, the following optional parts are
also required.

Refrigerant branching kit (for R-410A only: Always use an
appropriate kit dedicated for your system.)

To  select an optimum refrigerant branching kit, refer to 

"Refrigerant

branch kit selection" on page 9

.

2.4.

Technical and electrical specifications

Refer to the Engineering Data Book for the complete list of
specifications.

CAUTION

Ground the air conditioner.
Grounding resistance should be according to national
regulations
Do not connect the earth wire to gas or water
pipes, lightning conductor or telephone earth
wire.
Incomplete grounding may cause electric
shocks.

Gas pipe.
Ignition or explosion may occur if the gas leaks.

Water pipe.
Hard vinyl tubes are not effective grounds.

Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by a
lightning bolt.

Be sure to install an earth leak detector.
Failure to install an earth leak detector may cause
electric shocks or fire.

Install drain piping according to this installation manual
to ensure good drainage, and insulate the pipe to
prevent condensation.
Improper drain piping may cause water leakage, and
make the furnitures get wet.

Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions
or radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)

Do not rinse the outdoor unit.
This may cause electric shocks or fire.

Do not install the air conditioner in places such as the
following:

Where there is mist of mineral oil, oil spray or vapor
for example a kitchen.
Plastic parts may deteriorate, and cause them to fall
out or water to leak.

Where corrosive gas, such as sulfurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.

Where there is machinery which emits
electromagnetic waves.
Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.

Where flammable gases may leak, where carbon
fiber or ignitable dust is suspended in the air or
where volatile flammables, such as thinner or
gasoline, are handled.
Such gases may cause a fire.

Where the air contains high levels of salt such as
that near the ocean.

Where voltage fluctuates a lot, such as that in
factories.

In vehicles or vessels.

Where acidic or alkaline vapoure is present.

Do not allow a child to mount on the outdoor unit or
avoid placing any object on the unit.
Falling or tumbling may result in injury.

Do not touch any refrigerant which has leaked out of
refrigerant piping connections.
This may result in frostbite.

Outdoor unit

Total capacity of 

indoor units

Total quantity of 

indoor units

RXYSQ4

50~130

6

RXYSQ5

62.5~162.5

8

RXYSQ6

70~182

9

Gas line piping (1)

(*)

 + copper gasket

(*)

Only for RXYSQ6.

1

Gas line piping (2)

(*)

1

Gas line piping (3)

(*)

1

Installation manual
Operation manual

1
1

1

Accessories

Refnet header

Refnet joint

KHRQ22M29H

KHRQ22M20T

+

Summary of Contents for RXYSQ4M7V3B

Page 1: ...INSTALLATION MANUAL RXYSQ4M7V3B RXYSQ5M7V3B RXYSQ6M7V3B System air conditioner...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 100...

Page 3: ...V 1 2 3 2 3 4 1 4 5 5 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 2 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT A1P 3 11 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O...

Page 4: ...t w normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie ut...

Page 5: ...T YOUR LOCAL DAIKIN DEALER IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION WARNING If the warning is not observed it may cause serious casualties CAUT...

Page 6: ...leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depe...

Page 7: ...Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibilit...

Page 8: ...ly 5 2 Method for removing transport fittings The transportation fittings 2 yellow pieces are provided on the leg of the compressor for protecting the unit during transport Remove them as shown in fig...

Page 9: ...o use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply NOTE...

Page 10: ...sors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so th...

Page 11: ...lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling oper...

Page 12: ...or outer panels of the compressor When the outdoor unit is installed above the indoor unit the following can occur The condensated water on the stop valve can move to the indoor unit To avoid this ple...

Page 13: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor u...

Page 14: ...ant to be charged on page 9 and fill in the amount in the Additional refrigerant charge label attached to the unit Charging while the outdoor unit is at standstill After the vacuum drying is finished...

Page 15: ...hat cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the pip...

Page 16: ...nd wire Keep proper distance between power cable and control wiring 4 Clamp field supply 5 stop valve mounting plate 6 Ground 7 Electric parts box 8 Power cable 9 Ground cable yellow green 10 Fix the...

Page 17: ...iring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal boar...

Page 18: ...nd buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switches DS1 and DS2 WARNING ELECTRIC SHOCK Caution when performing service to...

Page 19: ...when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P led is off...

Page 20: ...s the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller...

Page 21: ...refrigerant recovery operation vacuuming operation to ON After this is set do not reset the setting mode 2 until the vacuuming is finished The H1P led is on and the remote controller indicates test o...

Page 22: ...tion level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than ai...

Page 23: ...NOTES NOTES...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW17806 1C...

Reviews: