background image

Installation manual

6

RXYSQ4~6M7V3B

VRVII-S system air conditioner

4PW17806-1C

8.

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R-410A only when adding refrigerant
Installation tools:

Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R-410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.

Vacuum pump:

Use a 2-stage vacuum pump with a non-return valve

Make sure the pump oil does not flow oppositely into the system
while the pump is not working.

Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

For handling of stop valves, refer to 

"9.3. How to use the shut-off

valve" on page 7

.

Only use the flare nuts included with the unit. Using different
flare nuts may cause the refrigerant to leak.

Always use the supplied copper gasket when connecting the
gas pipe supplied with the unit. See 

"9. Refrigerant piping" on

page 7.

8.1.

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

8.2.

Cautions for flare connection

See the following table for flare part machining dimensions.

When connecting the flare nuts, apply refrigerant ether or ester
oil to the inside and outside of the flares and turn them three or
four times at first.

When loosening a flare nut, always use two wrenches in
combination. When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.

See the following table for tightening torque.
(Applying too much torque may cause the flares to crack.)

After all the piping has been connected, use nitrogen to perform
a gas leak check.

Installation period

Protection method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the 

pipe

Regardless of the 

period

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

2

3

4

5

6

6

Pipe size

Tightening 

Torque (N•m)

A (mm)

Flare shape

Ø9.5

32.7~39.9

12.8~13.2

Ø15.9

61.8~75.4

19.3~19.7

NOTE

You must use a torque wrench but if you are obliged to
install the unit without a torque wrench, you may follow
the installation method mentioned below.

After the work is finished, make sure to check that
there is no gas leak.

When you keep on tightening the flare nut with a
spanner, there is a point where the tightening torque
suddenly increases. From that position, further tighten
the flare nut within the angle shown below:

12 3

4

1

Piping union

2

Spanner

3

Flare nut

4

Torque wrench

R=0.4~0.8

45 

±

2

90 

±

2

A

Pipe size

Further tightening 

angle

Recommended 

arm length of tool

Ø9.5 (3/8")

60~90°

±200 mm

Ø15.9 (5/8")

30~60°

±300 mm

Summary of Contents for RXYSQ4M7V3B

Page 1: ...INSTALLATION MANUAL RXYSQ4M7V3B RXYSQ5M7V3B RXYSQ6M7V3B System air conditioner...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 100...

Page 3: ...V 1 2 3 2 3 4 1 4 5 5 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 2 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT A1P 3 11 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O...

Page 4: ...t w normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie ut...

Page 5: ...T YOUR LOCAL DAIKIN DEALER IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION WARNING If the warning is not observed it may cause serious casualties CAUT...

Page 6: ...leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depe...

Page 7: ...Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibilit...

Page 8: ...ly 5 2 Method for removing transport fittings The transportation fittings 2 yellow pieces are provided on the leg of the compressor for protecting the unit during transport Remove them as shown in fig...

Page 9: ...o use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply NOTE...

Page 10: ...sors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so th...

Page 11: ...lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling oper...

Page 12: ...or outer panels of the compressor When the outdoor unit is installed above the indoor unit the following can occur The condensated water on the stop valve can move to the indoor unit To avoid this ple...

Page 13: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor u...

Page 14: ...ant to be charged on page 9 and fill in the amount in the Additional refrigerant charge label attached to the unit Charging while the outdoor unit is at standstill After the vacuum drying is finished...

Page 15: ...hat cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the pip...

Page 16: ...nd wire Keep proper distance between power cable and control wiring 4 Clamp field supply 5 stop valve mounting plate 6 Ground 7 Electric parts box 8 Power cable 9 Ground cable yellow green 10 Fix the...

Page 17: ...iring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal boar...

Page 18: ...nd buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switches DS1 and DS2 WARNING ELECTRIC SHOCK Caution when performing service to...

Page 19: ...when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P led is off...

Page 20: ...s the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller...

Page 21: ...refrigerant recovery operation vacuuming operation to ON After this is set do not reset the setting mode 2 until the vacuuming is finished The H1P led is on and the remote controller indicates test o...

Page 22: ...tion level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than ai...

Page 23: ...NOTES NOTES...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW17806 1C...

Reviews: