background image

Installation manual

16

RXYSQ4~6M7V3B

VRVII-S system air conditioner

4PW17806-1C

Confirmation of the set mode

The following items can be confirmed by setting mode 1 (H1P
led is off)

Check the led indication in the field marked 

.

1

Indication of the present operation state

-

 normal

-

 abnormal

-

 under preparation or under test operation

2

Indication of COOL/HEAT selection setting

3

Indication of low noise operation state 

 

-

 standard operation (= factory setting)

-

 

 operation

4

Indication of power consumption limitation setting 

 

-

 standard operation (= factory setting)

-

 

 operation

11.4. Test operation

Check the stop valves
Make sure to open the gas and liquid line stop valves.

After installation, perform the test operation.
Unless the test operation is performed, the error code "

U3

" is

shown on the remote controller and the unit cannot be operated.

Performing the test operation

1

To  protect the compressor, make sure to turn on the power
supply 6 hours before starting operation.

2

Set to setting mode 1 (H1P led is off) (refer to 

"Setting mode 1"

on page 15

).

3

Press the 

 button for 5 seconds when the unit is at

standstill. The test operation starts when the H2P led blinks and
the remote controller indicates 

 (test operation) and 

(external control). 

It may take 10 minutes to bring the state of refrigerant uniform
before the compressor starts, but that is not a malfunction.
The test operation is automatically carried out in cooling mode
during 15~30 minutes.
Depending on the situation, the refrigerant running sound or the
sound of a magnetic solenoid valve may rise during this
operation.
The following items are automatically checked:
-

Check for miswiring

-

Check if stop valves are open

-

Check of refrigerant charge

-

Automatic judgement of piping length

4

After the test operation (maximum 30 minutes), the unit
automatically stops.Check the operation results by the outdoor
unit led indication.

5

Measure to be taken when operation finishes abnormally

1.

Confirm the error code on the remote controller.

2.

Correct what is abnormal.
(See the installation manual and operation manual or contact
your dealer.)

3.

After the abnormality is corrected, press the 
button and reset the error code.

4.

Start the unit again to confirm that the problem is properly
solved.

5.

If no error code is indicated on the remote controller, it is
possible to start operation after 5 minutes.

1

When set to COOL/HEAT change-over by each individual 
outdoor unit circuit (= factory setting).

2

Indication on master unit when COOL/HEAT change-over is 
carried out by outdoor units connected in multiple system-
combination.

3

Indication on slave unit when COOL/HEAT change-over is 
carried out by outdoor units connected in multiple system-
combination

(*)

(*) This setting = factory setting.

NOTE

After turning on the power supply, the unit can not be
started until the H2P initialisation led goes off
(maximum 12 minutes).

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1

(*)

(*)

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

2

3

L.N.O.P

L.N.O.P

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

DEMAND

DEMAND

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

NOTE

When you want to terminate the test operation,
press the 

 button. The unit will keep

running for 30 seconds and then stops. During
test operation it is impossible to stop the unit with
the remote controller.

normal

abnormal

Indoor units cannot be checked individually. After the
test operation is finished, check the indoor units
individually via the remote controller.

The led indication changes during this operation, but
that is not abnormal.

Please attach the front plate of the outdoor unit in
order to prevent incorrect judgement during operation.

BS4  TEST

BS3  RETURN

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

BS3  RETURN

Summary of Contents for RXYSQ4M7V3B

Page 1: ...INSTALLATION MANUAL RXYSQ4M7V3B RXYSQ5M7V3B RXYSQ6M7V3B System air conditioner...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 100...

Page 3: ...V 1 2 3 2 3 4 1 4 5 5 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 2 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT A1P 3 11 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O...

Page 4: ...t w normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie ut...

Page 5: ...T YOUR LOCAL DAIKIN DEALER IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION WARNING If the warning is not observed it may cause serious casualties CAUT...

Page 6: ...leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depe...

Page 7: ...Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibilit...

Page 8: ...ly 5 2 Method for removing transport fittings The transportation fittings 2 yellow pieces are provided on the leg of the compressor for protecting the unit during transport Remove them as shown in fig...

Page 9: ...o use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply NOTE...

Page 10: ...sors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so th...

Page 11: ...lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling oper...

Page 12: ...or outer panels of the compressor When the outdoor unit is installed above the indoor unit the following can occur The condensated water on the stop valve can move to the indoor unit To avoid this ple...

Page 13: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor u...

Page 14: ...ant to be charged on page 9 and fill in the amount in the Additional refrigerant charge label attached to the unit Charging while the outdoor unit is at standstill After the vacuum drying is finished...

Page 15: ...hat cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the pip...

Page 16: ...nd wire Keep proper distance between power cable and control wiring 4 Clamp field supply 5 stop valve mounting plate 6 Ground 7 Electric parts box 8 Power cable 9 Ground cable yellow green 10 Fix the...

Page 17: ...iring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal boar...

Page 18: ...nd buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switches DS1 and DS2 WARNING ELECTRIC SHOCK Caution when performing service to...

Page 19: ...when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P led is off...

Page 20: ...s the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller...

Page 21: ...refrigerant recovery operation vacuuming operation to ON After this is set do not reset the setting mode 2 until the vacuuming is finished The H1P led is on and the remote controller indicates test o...

Page 22: ...tion level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than ai...

Page 23: ...NOTES NOTES...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW17806 1C...

Reviews: