background image

RXYSQ4~6M7V3B
VRVII-S system air conditioner
4PW17806-1C

Installation manual

15

Setting the push button switch (BS1~5)

Function of the push button switch which is located on the outdoor
unit PCB (A1P):

The figure shows state of the led indications when the unit is shipped
from the factory.

Setting the mode

The set mode can be changed with the 

 button according

to the following procedure:

For setting mode 1: Press the 

 button once, the led

is off 

.

For setting mode 2:  Press the 

 button for

5 seconds, the H1P led is on 

.

If the H1P led is blinking 

 and the 

 button is puched

once, it will change to setting mode 1.

Setting mode 1

The H1P led is off (COOL/HEAT selection setting).

Setting procedure

1

Push the 

 button and adjust the led indication to either

one of the possible settings as shown below in the field marked

:

2

Push the 

 button and the setting is defined.

Setting mode 2

The H1P led is on.

Setting procedure

1

Push the 

 button according to the required function

(A~F). The led indication that matches the required function is
shown below in the field marked 

:

2

When the 

 button is pushed, it indicates the current

setting.

3

Push the 

 button according to the required setting

possibility as shown below in the field marked 

.

3.1 Possible settings for function A, B and F are 

 

(ON) or 

 

(OFF).

3.2 Possible settings for function C 

The noise of level 3 < level 2 < level 1 (

).

3.3 Possible settings for function D and E

For function D

  (

only: the noise of level 3 < level 2

< level 1 (

).

For function E 

(

only: the power consumption of

level 1< level 2 < level 3 (

).

4

Push the 

 button and the setting is defined.

5

When the 

 button is pushed again, the operation

starts according to the setting.

Refer to the service manual for more details and for other settings.

For changing the set mode

For field setting

For field setting

For test operation

For resetting the address when the wiring is changed or when 
an additional indoor unit is installed

NOTE

If you get confused in the middle of the setting
process, push the 

 button. Then it returns to

setting mode 1 (H1P led is off).

1

In case of COOL/HEAT setting by each individual outdoor unit 
circuit.

2

In case of COOL/HEAT setting by the master unit when outdoor 
units are connected in multiple-system combination

(*)

(*) It is necessary to use the optional external control adapter for 

outdoor unit (DTA104A61/62). See the instruction delivered with 
the adapter.

3

In case of COOL/HEAT setting by the slave unit when outdoor 
units are connected in multiple-system combination

(*)

.

IND

H3P

MASTER

H4P

L. N. O. P

H6P

SLAVE

H5P

DEMAND

H7P

MODE

H1P

TEST:

HWL:

H2P

C/H

SELECTOR

BS5

RESET

BS4

TEST

BS3

RETURN

BS2

SET

BS1

MODE

BS1  MODE

BS2  SET

BS3  RETURN

BS4  TEST

BS5  RESET

BS1  MODE

BS1  MODE

BS1  MODE

BS1  MODE

BS1  MODE

BS2  SET

1

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

2

3

BS3  RETURN

Possible functions

A

additional refrigerant charging operation.

B

refrigerant recovery operation/vacuuming operation.

C

automatic low noise operation setting at nighttime.

D

low noise operation level setting (

) via the external 

control adapter.

E

power consumption limitation setting (

) via the 

external control adapter.

F

enabling function of the low noise operation level setting 
(

) and/or power consumption limitation setting 

(

) via the external control adapter 

(DTA104A61/62). 

(*)

(*) This setting = factory setting

(*)

(*) This setting = factory setting

(*)

(*) This setting = factory setting

NOTE

When finished, please mark the settings of function C,
D and E in the "Records" part of the label on the
backside of the front plate.

BS2  SET

L.N.O.P

DEMAND

L.N.O.P
DEMAND

A

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

B

C

D

E

F

BS3  RETURN

BS2  SET

ON

OFF

ON

ON

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

OFF

OFF

(*)

(*)

1

OFF

OFF

(*)

(*)

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1
2
3

L.N.O.P

1

DEMAND

3

H1P

H1P

H2P

H2P

H3P

H3P

H4P

H4P

H5P

H5P

H6P

H6P

H7P

H7P

1
2

(*)

3

BS3  RETURN

BS3  RETURN

Summary of Contents for RXYSQ4M7V3B

Page 1: ...INSTALLATION MANUAL RXYSQ4M7V3B RXYSQ5M7V3B RXYSQ6M7V3B System air conditioner...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 100...

Page 3: ...V 1 2 3 2 3 4 1 4 5 5 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 2 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT A1P 3 11 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O...

Page 4: ...t w normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie ut...

Page 5: ...T YOUR LOCAL DAIKIN DEALER IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION WARNING If the warning is not observed it may cause serious casualties CAUT...

Page 6: ...leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depe...

Page 7: ...Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibilit...

Page 8: ...ly 5 2 Method for removing transport fittings The transportation fittings 2 yellow pieces are provided on the leg of the compressor for protecting the unit during transport Remove them as shown in fig...

Page 9: ...o use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply NOTE...

Page 10: ...sors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so th...

Page 11: ...lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling oper...

Page 12: ...or outer panels of the compressor When the outdoor unit is installed above the indoor unit the following can occur The condensated water on the stop valve can move to the indoor unit To avoid this ple...

Page 13: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor u...

Page 14: ...ant to be charged on page 9 and fill in the amount in the Additional refrigerant charge label attached to the unit Charging while the outdoor unit is at standstill After the vacuum drying is finished...

Page 15: ...hat cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the pip...

Page 16: ...nd wire Keep proper distance between power cable and control wiring 4 Clamp field supply 5 stop valve mounting plate 6 Ground 7 Electric parts box 8 Power cable 9 Ground cable yellow green 10 Fix the...

Page 17: ...iring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal boar...

Page 18: ...nd buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switches DS1 and DS2 WARNING ELECTRIC SHOCK Caution when performing service to...

Page 19: ...when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P led is off...

Page 20: ...s the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller...

Page 21: ...refrigerant recovery operation vacuuming operation to ON After this is set do not reset the setting mode 2 until the vacuuming is finished The H1P led is on and the remote controller indicates test o...

Page 22: ...tion level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than ai...

Page 23: ...NOTES NOTES...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW17806 1C...

Reviews: