background image

Installation manual

14

RXYSQ4~6M7V3B

VRVII-S system air conditioner

4PW17806-1C

11. B

EFORE

 

OPERATION

11.1. Service precautions

11.2. Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

Transportation fittings

Be sure that the transportation fittings are removed from the
compressor.

2

The position of the switches that require an initial setting

Make sure that switches are set according to your application
needs before turning the power supply on.

3

Power supply wiring and transmission wiring

Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

4

Pipe sizes and pipe insulation

Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

5

Additional refrigerant charge

The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.

6

Insulation test of the main power circuit

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

7

Stop valves

Be sure that the stop valves are open on both liquid and gas
side.

11.3. Field setting

If required, carry out any field setting according to the following
instructions. Refer to the service manual for more details.

Handling the switches

When carrying out field settings, operate the
switches with an insulated stick (such as a ball-
point pen) to avoid touching of live parts. 

Location of the dipswitches, leds and buttons

Led state

Throughout the manual the state of the leds is indicated as follows: 

 OFF

 ON

 blinking

Setting the dip switches DS1 and DS2

WARNING: ELECTRIC SHOCK 

Caution when performing service to inverter
equipment

Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.

Additionaly, measure the points as shown in the figure
with a tester and confirm that the voltage of the
capacitor in the main circuit is no more than 50 V DC.

Make sure that the power supply is turned off before
performing the maintenance work. The heater of the
compressor may operate even in stop mode.

Please note that some sections of the electric
component box are extremely hot.

In order to prevent damage to the PCB, first eliminate
static electricity by touching a metal part (e.g. stop
valve) with your hand. Then pull out the connector.

After measuring the residual voltage, pull out the
outdoor fan connector.

Make sure you do not touch a conductive section.

The outdoor fan may rotate due to strong backblow
wind, causing the capacitor to charge. This may result
in an electric shock.

After maintenance, make sure the outdoor fan connector is
connected again. Otherwise, the unit may break down.

Play it safe!

Touch a metal part by hand (such as the stop valve) in
order to eliminate static electricity and to protect the PCB
before performing service.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

C+ C-

A3P

A2P

L1R

B

1

A

B

1

Fan connections of outdoor unit

A

Front view

B

View B

1

Led H1P~H7P

2

Push button switches BS1~BS5

3

Dip switch 2 (DS2: 1~4)

4

Dip switch 1 (DS1: 1~4)

What to set with dip switch DS1

1

COOL/HEAT selector
(

 

= not installed = factory setting)

2~4

NOT USED
DO NOT CHANGE THE FACTORY SETTING.

What to set with dip switch DS2

1~4

NOT USED
DO NOT CHANGE THE FACTORY SETTING.

1
2
3

4

A1P

OFF

Summary of Contents for RXYSQ4M7V3B

Page 1: ...INSTALLATION MANUAL RXYSQ4M7V3B RXYSQ5M7V3B RXYSQ6M7V3B System air conditioner...

Page 2: ...H 0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 100...

Page 3: ...V 1 2 3 2 3 4 1 4 5 5 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 2 2 C H SELECTOR TO IN D UNIT TO OUT D UNIT A1P 3 11 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O...

Page 4: ...t w normalizacyjnych pod warunkiem e u ywane s zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie ut...

Page 5: ...T YOUR LOCAL DAIKIN DEALER IF UNSURE OF INSTALLATION PROCEDURES OR USE ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION WARNING If the warning is not observed it may cause serious casualties CAUT...

Page 6: ...leakage and make the furnitures get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depe...

Page 7: ...Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibilit...

Page 8: ...ly 5 2 Method for removing transport fittings The transportation fittings 2 yellow pieces are provided on the leg of the compressor for protecting the unit during transport Remove them as shown in fig...

Page 9: ...o use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply NOTE...

Page 10: ...sors in the refrigerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so th...

Page 11: ...lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling oper...

Page 12: ...or outer panels of the compressor When the outdoor unit is installed above the indoor unit the following can occur The condensated water on the stop valve can move to the indoor unit To avoid this ple...

Page 13: ...If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 15 9 19 1 RXYSQ6 19 1 22 2 A Piping between outdoor u...

Page 14: ...ant to be charged on page 9 and fill in the amount in the Additional refrigerant charge label attached to the unit Charging while the outdoor unit is at standstill After the vacuum drying is finished...

Page 15: ...hat cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in figure 9 so that it does not come in contact with the pip...

Page 16: ...nd wire Keep proper distance between power cable and control wiring 4 Clamp field supply 5 stop valve mounting plate 6 Ground 7 Electric parts box 8 Power cable 9 Ground cable yellow green 10 Fix the...

Page 17: ...iring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal boar...

Page 18: ...nd buttons Led state Throughout the manual the state of the leds is indicated as follows OFF ON blinking Setting the dip switches DS1 and DS2 WARNING ELECTRIC SHOCK Caution when performing service to...

Page 19: ...when the wiring is changed or when an additional indoor unit is installed NOTE If you get confused in the middle of the setting process push the button Then it returns to setting mode 1 H1P led is off...

Page 20: ...s the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller...

Page 21: ...refrigerant recovery operation vacuuming operation to ON After this is set do not reset the setting mode 2 until the vacuuming is finished The H1P led is on and the remote controller indicates test o...

Page 22: ...tion level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than ai...

Page 23: ...NOTES NOTES...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW17806 1C...

Reviews: