background image

7 Commissioning

Installation and operation manual

30

RYYQ+RYMQ+RXYQ8~20T7Y1B

VRV IV system air conditioner

4P370473-1C – 2016.07

Additional refrigerant charge

The amount of refrigerant to be added to the unit shall be
written  on  the  included  "Added  refrigerant"  plate  and
attached to the rear side of the front cover.

Installation date and field setting

Be  sure  to  keep  record  of  the  installation  date  on  the
sticker  on  the  rear  of  the  upper  front  panel  according  to
EN60335‑2‑40 and keep record of the contents of the field
setting(s).

7.3

About test run

The  procedure  below  describes  the  test  operation  of  the  complete
system. This operation checks and judges following items:

▪ Check of wrong wiring (communication check with indoor units).

▪ Check of the stop valves opening.

▪ Judgement of piping length.

▪ Gathering  reference  data  for  leak  detection  functionality.  If  the

leak  detection  functionality  is  required,  the  test  run  needs  to  be
executed  including  a  detailed  refrigerant  situation  check.  If  the
leak detection functionality is NOT required, the test run can skip
the  detailed  refrigerant  situation  check.  This  can  be  defined  by
setting [2‑88].

INFORMATION

The  refrigerant  situation  check  cannot  be  performed
beyond the following limits:

▪ Outdoor temperature: 0~43°C DB

▪ Indoor temperature: 20~32°C DB

Value [2‑88]

Description

0

The test run will be executed including the
detailed refrigerant situation check. After the
test run, the unit will be prepared for leak
detection functionality (for more details, see

"6.2 Using the leak detection function" on
page 29

).

1

The test run will be executed without the
detailed refrigerant situation check. After the
test run, the unit will NOT be prepared for leak
detection functionality.

INFORMATION

▪ When  [2‑88]=0,  the  test  operation  time  can  take  up  to

4 hours.

▪ When  [2‑88]=0  and  the  test  operation  was  aborted

before the end, the 

 warning code will be visible on

the user interface. It is possible to operate the system.
Leak  detection  function  will  NOT  be  available.  It  is
recommended to re-execute the test operation.

▪ If  the  autocharge  function  was  used,  the  unit  informs

the  user  in  case  unfavourable  ambient  conditions  are
present  to  gather  detailed  refrigerant  situation  data.
When  this  is  the  case,  the  accuracy  of  leak  detection
operation  will  drop.  It  is  recommended  in  such  a  case
to  perform  the  test  operation  again  on  another  more
favourable  moment.  In  case  no  "

"  or  "

"

information  was  displayed  during  the  autocharging
procedure, it is possible to have reliable data gathering
during the test operation. See ambient limitations in the
information  table  on 

"5.6.6  Step  6a:  To  automatically

charge refrigerant" on page 21

.

In  case  Hydrobox  units  or  RA  DX  indoor  units  are  present  in  the
system, the pipe length check and the refrigerant situation check will
not be performed.

▪ Make  sure  to  carry  out  the  system  test  operation  after  the  first

installation. Otherwise, the malfunction code 

 will be displayed

on the user interface and normal operation or individual indoor unit
test run cannot be carried out.

▪ Abnormalities  on  indoor  units  cannot  be  checked  for  each  unit

separately.  After  the  test  operation  is  finished,  check  the  indoor
units one by one by performing a normal operation using the user
interface.  Refer  to  the  indoor  unit  installation  manual  for  more
details (e.g., Hydrobox) concerning the individual test run.

INFORMATION

▪ It may take 10 minutes to achieve a uniform refrigerant

state before the compressor starts.

▪ During the test operation, the refrigerant running sound

or the magnetic sound of a solenoid valve may become
loud and the display indication may change. These are
not malfunctions.

7.4

To perform a test run

1

Close  all  front  panels  in  order  to  not  let  it  be  the  cause  of
misjudgement  (except  the  electrical  component  box  inspection
opening service cover).

2

Make  sure  all  field  settings  you  want  are  set;  see 

"6.1  Making

field settings" on page 25

.

3

Turn  ON  the  power  to  the  outdoor  unit  and  the  connected
indoor units.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

4

Make  sure  the  default  (idle)  situation  is  existing;  see 

"6.1.4  To

access  mode  1  or  2"  on  page  26

.  Push  BS2  for  5  seconds  or

more. The unit will start test operation.

Result: 

The  test  operation  is  automatically  carried  out,  the

outdoor unit display will indicate "

" and the indication "Test

operation"  and  "Under  centralised  control"  will  display  on  the
user interface of indoor units.

Steps during the automatic system test run procedure:

Step

Description

Control before start up (pressure equalisation)

Cooling start up control

Cooling stable condition

Communication check

Stop valve check

Pipe length check

Refrigerant amount check

In case [2‑88]=0, detailed refrigerant situation
check

Pump down operation

Unit stop

Note: 

During  the  test  operation,  it  is  not  possible  to  stop  the  unit

operation  from  a  user  interface.  To  abort  the  operation,  press  BS3.
The unit will stop after ±30 seconds.

5

Check the test operation results on the outdoor unit 7‑segment
display.

Completion

Description

Normal completion No indication on the 7‑segment display (idle).

Summary of Contents for RXYQ10T7Y1B

Page 1: ...ration manual VRV IV system air conditioner RYYQ8T7Y1B RYYQ10T7Y1B RYYQ12T7Y1B RYYQ14T7Y1B RYYQ16T7Y1B RYYQ18T7Y1B RYYQ20T7Y1B RYMQ8T7Y1B RYMQ10T7Y1B RYMQ12T7Y1B RYMQ14T7Y1B RYMQ16T7Y1B RYMQ18T7Y1B RY...

Page 2: ...muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s m dos t saik rendelkez seit z p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z...

Page 3: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Mini...

Page 4: ...rror codes when charging refrigerant 22 5 6 9 Checks after charging refrigerant 22 5 6 10 To fix the fluorinated greenhouse gases label 22 5 7 Connecting the electrical wiring 22 5 7 1 Field wiring Ov...

Page 5: ...accessories are available in the unit a d 1 1 e 1 3P328191 1 BE SURE TO FILL OUT THE BLANKS WHICH ARE NEEDED FOR AFTER SALE SERVICES REQUESTFORTHEINDICATIONOFINSTALLATIONINFORMATION 1 RECORD OF INDOOR...

Page 6: ...t operation Depending on the type of outdoor unit which is chosen some functionality will or will not exist It will be indicated throughout this installation manual and brought to your attention Certa...

Page 7: ...l oils or moisture should be prevented from getting mixed into the system NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamles...

Page 8: ...ing length is allowed to be more than 90 m b Pipe size up is NOT allowed The pipe thickness of the refrigerant piping shall comply with the applicable legislation The minimal pipe thickness for R410A...

Page 9: ...e of 3 multi units the connection diameter of outdoor to T joint has to be kept In case of 2 multi units the connection pipe has to have the largest diameter There is never a connection of the equalis...

Page 10: ...harged to the system Total system refrigerant charge Z O R P O Standard factory charge of outdoor unit R Additional refrigerant charge according to liquid piping diameter length and outdoor unit speci...

Page 11: ...n wiring exceeds these limits it may result in communication error For non standard combinations Calculate the recommended fuse capacity Formula Calculate by adding the minimum circuit amps of each us...

Page 12: ...red installation is on a solid longitudinal foundation steel beam frame or concrete The foundation must be larger than the grey marked area 729 613 929 AB AA a mm Minimum foundation a Anchor point 4 H...

Page 13: ...ion label a attached to the joint comes to the top Do not tilt the joint more than 7 5 see view A Do not install the joint vertically see view B a a A B 7 5 7 5 a Caution label X Not allowed O Allowed...

Page 14: ...ise to close Shaft Valve body Hexagonal wrench Cap valve lid Service port 9 5 5 4 6 6 4 mm 13 5 16 5 11 5 13 9 12 7 8 1 9 9 18 0 22 0 15 9 13 5 16 5 6 mm 23 0 27 0 19 1 27 0 33 0 8 mm 22 5 27 5 25 4 5...

Page 15: ...outdoor unit has finished the initialisation to apply setting 2 21 Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant piping Performing v...

Page 16: ...bar 5 Torr 2 Check that with the vacuum pump turned off the target vacuum is maintained for at least 1 hour 3 Should you fail to reach the target vacuum within 2 hours or maintain the vacuum for 1 ho...

Page 17: ...ems recommended to first pre charge a portion of refrigerant through the liquid line before proceeding with the actual automatic or manual charging This step is included in below procedure see 5 6 5 T...

Page 18: ...frigerant to reach R Q Step 2 3 Open valves C D and B to the liquid and equalising line Charge the equalising line to maximally 0 05 MPa then close valve C and disconnect its connection to the manifol...

Page 19: ...Open valve A Charge remaining amount of refrigerant P kg R Q P Depending on ambient conditions the unit will decide to perform autocharge operation in heating or cooling mode Close valve A Push BS3 to...

Page 20: ...ppear e 2 indoor temperature out of range and e 3 outdoor temperature out of range Push BS1 to leave program Charging is finished Fill in the amount on the additional refrigerant charge label Input th...

Page 21: ...is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant do not for...

Page 22: ...Indoor unit is out of temperature range for leak detection operation Retry when ambient conditions are satisfied Outdoor unit is out of temperature range for leak detection operation Retry when ambie...

Page 23: ...ed wire nipples or rubber bushings into the knockout holes a b c d a Knockout hole b Burr c Remove burrs d If there are any possibilities that small animals enter the system through the knockout holes...

Page 24: ...onnecting wiring for the indoor units is connected The base unit is the outdoor unit to which the interconnecting wiring for the indoor units is connected 5 7 5 To finish the transmission wiring After...

Page 25: ...Perform special actions automatic refrigerant charge testrun etc Perform field settings demand operation low noise etc DIP switches By operating the DIP switches it is possible to DS1 1 COOL HEAT sel...

Page 26: ...all indoor units When the communication between indoor units and outdoor unit s is established and normal the 7 segment display indication state will be as below default situation when shipped from fa...

Page 27: ...nd last malfunction code 1 19 The 3rd last malfunction code 1 29 1 30 1 31 Shows the estimated leaked refrigerant amount kg based on 1 29 The latest leak detection operation 1 30 The 2nd last leak det...

Page 28: ...ctivated 2 20 Description 1 Activated To stop the manual additional refrigerant charge operation when the required additional refrigerant amount is charged push BS3 If this function was not aborted by...

Page 29: ...finished field piping electrical wiring air purge See installation manual of the indoor units for details 7 2 Checklist before commissioning After the installation of the unit first check the followin...

Page 30: ...to have reliable data gathering during the test operation See ambient limitations in the information table on 5 6 6 Step 6a To automatically charge refrigerant on page 21 In case Hydrobox units or RA...

Page 31: ...out the malfunction code The malfunction code will be displayed intermittent Example Code Example Main code Sub code With an interval of 1 second the display will switch between main code and sub code...

Page 32: ...after subcool HE malfunction R5T A1P X30A Check connection on PCB or actuator Liquid temperature sensor coil malfunction R4T A1P X30A Check connection on PCB or actuator Gas temperature sensor after...

Page 33: ...onfirm indoor unit mix is allowed Connection malfunction over indoor units or type mismatch R410A R407C RA Hydrobox etc Check if other indoor units have malfunction and confirm indoor unit mix is allo...

Page 34: ...e for servicing and the minimum space for air inlet and air outlet is available refer to the figure below and choose one of the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a...

Page 35: ...TION For a legend explaining the figures below refer to the end of this topic Piping diagram RYYQ8 12 sv sv M HPS INV M1C R3T S1NPL S1NPH S1PH R6T R5T R7T R1T M1F R4T R8T 10 12HP R21T j g i o p k m a...

Page 36: ...ct your installer to receive more information and professional advice 10 1 System layout Your VRV IV heat pump series outdoor unit can be one of following models Model Description RYYQ Single continuo...

Page 37: ...ll continue heating operation at a reduced level during defrost operation It will guarantee a decent comfort level indoor A heat storage element in the outdoor unit will provide the energy to de ice t...

Page 38: ...ion on page 38 for details To stop 5 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTICE Do not turn off power immediately...

Page 39: ...ire of a burner a heater or a cooker may result in a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do not use the system u...

Page 40: ...cking all above items it is impossible to fix the problem yourself contact your installer and state the symptoms the complete model name of the unit with manufacturing number if possible and the insta...

Page 41: ...changeover is controlled by the cool heat changeover remote control switch Ask your dealer where the remote control switch is installed 14 2 3 Symptom Fan operation is possible but cooling and heatin...

Page 42: ...used for the first time in a long time This is because dust has gotten into the unit 14 2 13 Symptom The units can give off odours The unit can absorb the smell of rooms furniture cigarettes etc and...

Page 43: ......

Page 44: ...4P370473 1 C 0000000 4P370473 1C 2016 07 Copyright 2014 Daikin...

Reviews: