In case refrigerant was added by using the leak detection 
function

In the check operation, the following checks and judgements will
be performed:

Check of the stop valve opening

Check for wrong wiring

Judgement of piping length

Judgement of initial refrigerant state

It takes ±3 hours (if the outdoor temperature is low, it takes
±4 hours) to complete the check operation.

The system can not perform the judgement of initial refrigerant
state in the following cases:

The outdoor temperature is out of range 
(<0°C DB or >43°C DB)

The indoor temperature is out of range 
(<20°C DB or >32°C DB)

A forced OFF during the test operation

In this case, after performing the check operation, normal
operation is possible although the abnormality code 

U3

  is

displayed on the indoor remote controller and the refrigerant
leakage detection function can not be used. 
Perform the check operation again and complete the judgement
of initial refrigerant state.

Perform the test operation as decribed in the paragraph 

"Test

operation procedure" on page 28

.

In case refrigerant was added without using the leak 
detection function (charging in cooling mode)

In the check operation, the following checks and judgement will
be performed:

Check of the stop valve opening

Check for wrong wiring

Judgement of piping length

It takes ±30 minutes to complete the check operation.

Check operation procedure

1

Close the electric box lid and all front panels except the one on
the side of the electric box.

2

Turn on the power to the outdoor unit and all connected indoor
units. Be sure to turn the power ON at least 6 hours before
operation in order to have power running to the crank case
heater.

3

Make the field setting as needed using the push buttons on the
PCB (A1P) of the outdoor unit. Refer to 

"12.3. Field setting" on

page 25

.

4

Set the check operation (without initial refrigerant decision)
following setting mode 2 in the field setting and perform the
check operation. 

The system operates for ±30 minutes and automatically stops
the check operation. 

If no malfunction code is displayed on the remote controller
after the system has stopped, check if the operation is
completed. Normal operation will be possible after 5 minutes.

If a malfunction code is displayed on the remote controller,
correct the malfunction and perform the check operation
again as decribed in 

"Correcting after abnormal completion

of the test operation" on page 29

In case refrigerant was added without using the leak 
detection function (pre-charging, charging in heating mode)

In the check operation, the following checks and judgement will
be performed:

Check of the stop valve opening

Check for wrong wiring

Check of refrigerant overcharge

Judgement of piping length

It takes ±40 minutes to complete the check operation.

Perform the test operation as decribed in the paragraph 

"Test

operation procedure" on page 28

.

Test operation procedure

1

Close all front panels except the front panel of the electric box.

2

Turn ON the power to all outdoor units and the connected indoor
units.

Be sure to turn on the power 6 hours before operation in order to
have power running to the crank case heater and to protect the
compressor.

3

Make the field setting as described in the paragraph 

"12.3. Field

setting" on page 25

.

4

Press the 

 button once, and set to the SETTING

MODE (H1P LED = OFF).

5

Press and hold the 

 button down for 5 seconds or

more. The unit will start the test operation.

The test operation is automatically carried out in cooling
mode, the H2P LED will light up and the messages "Test
operation" and "Under centralized control" will display on the
remote controller.

It may take 10 minutes to bring the state of the refrigerant
uniform before the compressor starts.

During the test operation, the refrigerant running sound or
the magnetic sound of a solenoid valve may become loud
and the LED display may change, but these are not mal-
functions.

During the test operation, it is not possible to stop the unit
operation from a remote controller. To abort the operation,
press the 

 button. The unit will stop after

±30 seconds.

6

Close the front panel in order to let it not be the cause of
misjudgement.

7

Check the test operation results by the LED display on the
outdoor unit.

8

When the test operation is fully completed, normal operation will
be possible after 5 minutes. 

Otherwise, refer to 

"Correcting after abnormal completion of the

test operation" on page 29

  to take actions for correcting the

abnormality.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Normal completion

x

x w x

x

x

x

Abnormal completion

x w w x

x

x

x

BS1  MODE

BS4  TEST

BS3  RETURN

Summary of Contents for RXQ5P7W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...

Page 37: ...3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 30 13 14 3 5 4 2 1 7 8 9 6 10 10...

Page 38: ...4PW48461 1 Copyright Daikin...

Reviews: