background image

RX(Y)Q5-10-1 RXQ RXYQ
RXYHQ1 RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1

Installation manual

14

When using residual current operated circuit breakers, be sure to use
a high-speed type 300 mA rated residual operating current.

Point for attention regarding quality of the public electric power
supply

This equipment complies with respectively:

EN/IEC 61000-3-11

(1)

 provided that the system impedance Z

sys

is less than or equal to Z

max

 and

EN/IEC 61000-3-12

(2)

  provided that the short-circuit power S

sc

is greater than or equal to the minimum S

sc

 value

at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
respectively:

Z

sys

 less than or equal to Z

max

 and

S

sc

 greater than or equal to the minimum S

sc

 value.

Be sure to install a main switch for the complete system.

8.4.

General cautions 

Up to 3 units can be connected by crossover power source
wiring between outdoor units. However, units of smaller capacity
must be connected downstream. For details, refer to the
technical data.

When connecting several units in VRV combination, the power
supply of each outdoor unit can also be connected separately.
Refer to the field wiring on the engineering data book for further
details.

Make sure to connect the power source wire to the power
source terminal block and to clamp it as shown in 

figure 21

 and

described in chapter 

"8.8. Field line connection: power wiring"

on page 17

.

For conditional connections, refer to the Technical Data.

As this unit is equipped with an inverter, installing a phase
advancing capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating accident due to high-frequency waves. Therefore, never
install a phase advancing capacitor.

Keep power imbalance within 2% of the supply rating.

Large imbalance will shorten the life of the smoothing
capacitor.

As a protective measure, the product will stop operating and
an error indication will be made, when power imbalance
exceeds 4% of the supply rating.

Follow the "electrical wiring diagram" supplied with the unit when
carrying out any electrical wiring.

Only proceed with wiring work after all power is shut off.

Always ground wires. (In accordance with national regulations of
the pertinent country.)

Do not connect the ground wire to gas pipes, sewage pipes,
lightning rods, or telephone ground wires. This may cause
electric shock.

Combustion gas pipes: can explode or catch fire if there is a
gas leak.

Sewage pipes: no grounding effect is possible if hard plastic
piping is used.

Telephone ground wires and lightning rods: dangerous when
struck by lightning due to abnormal rise in electrical potential
in the grounding.

This unit uses an inverter, and therefore generates noise, which
will have to be reduced to avoid interfering with other devices.
The outer casing of the product may take on an electrical charge
due to leaked electrical current, which will have to be discharged
with the grounding.

Be sure to install an earth leakage breaker. (One that can
handle high-frequency electrical noise.)
(This unit uses an inverter, which means that an earth leakage
breaker capable of handling high-frequency electrical noise
must be used in order to prevent malfunctioning of the earth
leakage breaker itself.)

Earth leakage breakers that are especially designed for
protecting ground-faults must be used in conjunction with main
switch and fuse for use with wiring.

Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase. If you
connect in reversed phase, replace two of the three phases.

(1) European/International Technical Standard setting the limits for voltage changes, 

voltage fluctuations and flicker in public low-voltage supply systems for equipment 
with rated current 

75 A.

(2) European/International Technical Standard setting the limits for harmonic currents 

produced by equipment connected to public low-voltage systems with input 
current >16 A and 

75 A per phase.

Z

max

 (

)

Minimum S

sc

 

value

RX(Y)Q5

RX(Y)Q8

1218 kVA

RX(Y)Q10

0.27

  928 kVA

RX(Y)Q12

0.27

  944 kVA

RX(Y)Q14

0.24

1114 kVA

RX(Y)Q16

0.24

1114 kVA

RX(Y)Q18

0.24

1171 kVA

RXYQ20

=

RXYQ8

+ RXYQ12

0.27

2162 kVA

RXYQ22

=  RXYQ12

0.25

1872 kVA

RXYQ24

=  RXYQ12

0.25

1888 kVA

RXYQ26

=

RXYQ8

+ RXYQ18

0.24

2389 kVA

RXYQ28

=  RXYQ18

0.23

2099 kVA

RXYQ30

=  RXYQ18

0.23

2115 kVA

RXYQ32

=  RXYQ18

0.22

2284 kVA

RXYQ34

=  RXYQ18

0.22

2284 kVA

RXYQ36

=  RXYQ18

0.22

2342 kVA

RXYQ38

=

RXYQ8

+  RXYQ18

0.23

3333 kVA

RXYQ40

=   RXYQ18

0.22

3043 kVA

RXYQ42

=   RXYQ18

0.22

3059 kVA

RXYQ44

=

RXYQ8

+  RXYQ18

0.22

3560 kVA

RXYQ46

=   RXYQ18

0.22

3270 kVA

RXYQ48

=   RXYQ18

0.22

3286 kVA

RXYQ50

=   RXYQ18

0.22

3455 kVA

RXYQ52

=   RXYQ18

0.22

3455 kVA

RXYQ54

=   RXYQ18

0.22

3513 kVA

Z

max

 (

)

Minimum S

sc

 

value

RXYHQ12

0.27

1114 kVA

RXYHQ16

=

RXYQ8

+

RXYQ8

2436 kVA

RXYHQ18

=

RXYQ8

+ RXYQ10

0.27

2146 kVA

RXYHQ20

=

RXYQ8

+ RXYHQ12

0.27

2332 kVA

RXYHQ22

=  RXYHQ12

0.25

2042 kVA

RXYHQ24

=

RXYQ8

+

RXYQ8

+

RXYQ8

3654 kVA

RXYHQ26

=

RXYQ8

+

RXYQ8

+ RXYQ10

0.27

3364 kVA

RXYHQ28

=

RXYQ8

+  RXYQ10

0.25

3074 kVA

RXYHQ30

=

RXYQ8

+  RXYHQ12

0.25

3260 kVA

RXYHQ32

=

RXYQ8

+ R RXYHQ12

0.25

3446 kVA

RXYHQ34

=  R RXYHQ12

0.24

3156 kVA

RXYHQ36

= R R RXYHQ12

0.24

3342 kVA

NOTE

Select the power supply cable in accordance with
relevant local and national regulations.

Wire size must comply with the applicable local
and national code.

Specifications for local wiring power cord and
branch wiring are in compliance with IEC60245.

WIRE TYPE H05VV(*)
*Only in protected pipes (use H07RN-F when
protected pipes are not used).

Summary of Contents for RXQ5P7W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...

Page 37: ...3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 30 13 14 3 5 4 2 1 7 8 9 6 10 10...

Page 38: ...4PW48461 1 Copyright Daikin...

Reviews: