Installation manual

25

RX(Y)Q5-10-1 RXQ RXYQ

RXYHQ1 RX(Y)Q14~18P7W1BA

VRVIII System air conditioner

4PW48461-1

12. B

EFORE

 

OPERATION

12.1.

Service precautions

Pay attention to the fan. It is dangerous to inspect the unit while the
fan is running. Be sure to turn off the main switch and to remove the
fuses from the control circuit located in the outdoor unit.

12.2. Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

The position of the switches that require an initial setting

Make sure that switches are set according to your application
needs before turning the power supply on.

2

Power supply wiring and transmission wiring

Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

3

Pipe sizes and pipe insulation

Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

4

Air tight test and vacuum drying

Make sure the air tight test and vacuum drying were completed.

5

Additional refrigerant charge

The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.

6

Insulation test of the main power circuit

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

7

Installation date and field setting

Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.

12.3. Field setting

If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.

Opening the switch box and handling the switches

When carrying out field settings, remove
the inspection cover (1).

Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.

Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.

WARNING: ELECTRIC SHOCK 

Caution when performing service to inverter
equipment

1

Do not open the electric box cover for 10 minutes after
the power supply is turned off.

2

Measure the voltage between terminals on the
terminal block for power supply with a tester and
confirm that the power supply is shut off.

In addition, measure the points, as shown in the figure
below, with a tester and confirm that the voltage of the
capacitor in the main circuit is less than 50 V DC.

3

To  prevent damaging the PC-board, touch a
noncoated metal part to eliminate static electricity
before pulling out or plugging in connectors.

4

The performing of the service to the inverter
equipment must be started after the junction
connectors X1A, X2A, X3A, X4A (X3A and X4A are
for R RX(Y)Q14~18 unit type only) for the
fan motors in the outdoor unit are been pulled out. Be
carefull not to touch the live parts.

(If a fan rotates due to strong wind, it may store
electricity in the capacitor or in the main circuit and
cause electric shock.)

5

After the service is finished, plug the junction
connecter back in. Otherwise the error code 

E7

 will be

displayed on the remote controller and normal
operation will not be performed.

For details refer to the wiring diagram labeled on the back
of the electric box cover.

NOTE

Play it safe!

For protection of the PCB, touch the switch box casing
by hand in order to eliminate static electricity from your
body before performing service.

A2P

A2P

A1P

A3P

TP1 TP2

NOTE

Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

NOTE

Make sure that all outside panels, except for the panel
on the electric box, are closed while working.

Close the lid of the electric box firmly before turning on
the power.

2

1

Summary of Contents for RXQ5P7W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...

Page 37: ...3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 30 13 14 3 5 4 2 1 7 8 9 6 10 10...

Page 38: ...4PW48461 1 Copyright Daikin...

Reviews: