RX(Y)Q5-10-1 RXQ RXYQ
RXYHQ1 RX(Y)Q14~18P7W1BA
VRVIII System air conditioner
4PW48461-1

Installation manual

2

1.1.

Combination

The indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R410A.
To  learn which models of indoor units are compatible with
R410A, refer to the product catalogs.

Pay attention when connecting outdoor units in multi
combination. RXYQ-M units are NOT compatible with
RXY(H)Q-P units.

Total capacity/quantity of indoor units

1.2.

Standard supplied accessories

See location 1 in 

figure 24

  for reference to where following

accessories are supplied with the unit.

See location 2 in 

figure 24

  for reference to where following

accessories are supplied with the unit.

Standard combination of outdoor units

Total 

capacity of 

indoor units

Total 

quantity of 

indoor units

RX(Y)Q5

(a)

(a) = main unit

62.5~162.5

12

RX(Y)Q8

(a)

100~260

20

RX(Y)Q10

(a)

125~325

25

RX(Y)Q12

(a)

150~390

30

RX(Y)Q14

(a)

175~455

35

RX(Y)Q16

(a)

200~520

40

RX(Y)Q18

(a)

225~585

45

RXYQ20

=

RXYQ8

+ RXYQ12

250~650

40

RXYQ22

=  RXYQ12

275~715

44

RXYQ24

=  RXYQ12

300~780

48

RXYQ26

=

RXYQ8

+ RXYQ18

325~845

52

RXYQ28

=  RXYQ18

350~910

56

RXYQ30

=  RXYQ18

375~975

60

RXYQ32

=  RXYQ18

400~1040

64

RXYQ34

=  RXYQ18

425~1105

64

RXYQ36

=  RXYQ18

450~1170

64

RXYQ38

=

RXYQ8

+  RXYQ18

475~1235

61

RXYQ40

=   RXYQ18

500~1300

64

RXYQ42

=   RXYQ18

525~1365

64

RXYQ44

=

RXYQ8

+  RXYQ18

550~1430

64

RXYQ46

=   RXYQ18

575~1495

64

RXYQ48

=   RXYQ18

600~1560

64

RXYQ50

=   RXYQ18

625~1625

64

RXYQ52

=   RXYQ18

650~1690

64

RXYQ54

=   RXYQ18

675~1755

64

Standard combination of outdoor units

Total 

capacity of 

indoor units

Total 

quantity of 

indoor units

RXYHQ12

(a)

(a) = main unit

150~390

30

RXYHQ16

=

RXYQ8

+

RXYQ8

200~520

32

RXYHQ18

=

RXYQ8

+ RXYQ10

225~585

36

RXYHQ20

=

RXYQ8

+ RXYHQ12

250~650

40

RXYHQ22

=  RXYHQ12

275~715

44

RXYHQ24

=

RXYQ8

+

RXYQ8

+

RXYQ8

300~780

39

RXYHQ26

=

RXYQ8

+

RXYQ8

+ RXYQ10

325~845

42

RXYHQ28

=

RXYQ8

+  RXYQ10

350~910

45

RXYHQ30

=

RXYQ8

+  RXYHQ12

375~975

48

RXYHQ32

=

RXYQ8

+ R RXYHQ12

400~1040

52

RXYHQ34

=  R RXYHQ12

425~1105

55

RXYHQ36

= R R RXYHQ12

450~1170

58

NOTE

The table above shows the possible total capacity
and number of possible indoor units when
configured in a standard combination.
Refer to the service manual for more details when
using a configuration other than a standard
combination.

If the total capacity of the connected indoor units
exceeds the capacity of the outdoor unit, cooling
and heating performance may drop when running
the indoor units.
Refer to the section on performance charac-
teristics in the Engineering Data Book for details.

There are restrictions on the refrigerant pipe
connection order between outdoor units during
installation in case of a multiple outdoor unit
system.
Install according to the following restrictions.
The capacities of outdoor units A, B, and C must
fulfill the following restriction conditions: A

B

C.

Installation manual 

1

Operation manual 

1

Fluorinated greenhouse gases label

1

Multilingual fluorinated greenhouse 
gases label

1

Gas side accessory pipe

(a)

(a) = main unit

Unit type

Item

Quantity

5~18 Hp

1

5~10 Hp

1

12~18 Hp

1

Liquid side accessory pipe

(a)

Unit type

Item

Quantity

5~18 Hp

1

5~10, 14, 16 Hp

1

12, 18 Hp

1

A

B

C

1 2

3

1

To indoor units

2

Outdoor unit multi connection piping kit (first 
branch)

3

Outdoor unit multi connection piping kit 
(second branch)

Summary of Contents for RXQ5P7W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...