background image

Installation manual

21

RX(Y)Q5-10-1 RXQ RXYQ

RXYHQ1 RX(Y)Q14~18P7W1BA

VRVIII System air conditioner

4PW48461-1

4

If the calculated amount of pre-charging is reached, close
valve C.

5

After pre-charging, perform the refrigerant charge operation as
shown below and charge the remaining refrigerant of the
additional charging amount through valve A.

(See figure 29)

1.

Start of automatic charging refrigerant
-

Open the liquid and gas side stop valves and the service port 
stop valve. (Valves A, B and C must be closed.)

-

Close all frontpanels except the electric box frontpanel and 
turn the power ON.

-

Make sure all indoor units are connected, refer to 

"11.4. How 

to check how many units are connected" on page 19

.

-

If the H2P LED is not flashing (in 12 minutes time after 
turning on the power), make sure it is displayed as shown in 
the 

"3 Normal system display" on page 24

.

If the H2P LED is flashing, check the malfunction code on the
remote controller

 

"4 Remote controller malfunction code

display" on page 24

.

2.

Press the 

 button once if the LEDs combination is not

as in the figure below.

3.

Press the 

 button once.

4.

Hold the 

 button down for 5 seconds or more.

5.

Charging mode judgement
For automatic charging, the charging must be done in cooling
mode.
However, if the indoor temperature is 20°C DB or lower, in some
cases the unit will first charge in heating mode to increase the
indoor temperature. 
The unit will automatically select the cooling mode or heating
mode for charging.

Continue with the automatic charging in cooling
mode OR in heating mode.

Charging in heating mode

 (not for cooling only models)

6.

Start up
Wait while the unit is preparing for charging in heating mode.

7.

Ready

Press the 

 button once within 5 minutes.

If the 

 button is not pushed within 5 minutes, 

P2

 will be

displayed on the remote controller. Refer to 

"4 Remote controller

malfunction code display" on page 24

.

8.

Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.

*

 = The state of this LED is not important.

9.

Complete
If the calculated amount of refrigerant minus 10 kg is reached,
close valve A and press the 

 button once.

As long as the 

 button is not pressed, the system

will remain in heating mode. This can be required to increase the
indoor temperature.

10. Press the 

 button to perform the temperature range

check
Out of range:

In these cases, press the 

 button once and follow the

procedure as 

"5 Final adjustment of the amount of refrigerant"

on page 24

.

At least the unit should be charged with its original amount
of refrigerant (refer to the nameplate on the unit), before
starting the automatic charging.

1

Measuring instrument

2

Tank (siphon system)

3

Charge hose

4

Liquid line stop valve

5

Gas line stop valve

6

Stop valve service port

7

Valve B

8

Valve C

9

Valve A

10

Outdoor unit

11

Refrigerant charge port

12

Field piping

13

Refrigerant flow

14

Indoor unit

NOTE

For a multi outdoor unit system, it is not required
to connect all charge ports to a refrigerant tank.

The refrigerant will be charged with ±22 kg in
1 hour time at an outdoor temperature of 30°C DB
or with ±6 

kg at an outdoor temperature of

0°C DB.

If you need to speed up in case of a multiple
outdoor system, connect the refrigerant tanks to
each outdoor unit as shown in 

figure 29

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

x

x w x

x

x

x

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w w w w w w w

BS1  MODE

BS4  TEST

BS4  TEST

During charging in heating mode, a person must
manually close valve A before complete charging is
finished. The required amount is the the calculated
amount (see 

"6.6. Example of connection" on page 9

)

minus 10 kg, therefore, the weight must be monitored
constantly.

For the cooling only models, heating mode can not be
selected. In this case, the LED display will indicate out
of range. Refer to the procedure as described in

"5 Final adjustment of the amount of refrigerant" on
page 24

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Pressure control 
(for the first minute)

x c x

x

x

x w

Start up control 
(for the next 2 minutes)

c c x

x

x w x

Waiting for stable 
heating conditions 
(for the next ±15 
minutes (according to 
the system))

c c x

x

x w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c x

x w x w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c

*

*

*

*

*

When a malfunction occurs, check the display of the
remote controller and refer to 

"4 Remote  controller

malfunction code display" on page 24

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c c w w w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Out of outdoor 
temperture range

w c c c w x

x

Out of indoor 
temperture range

w c c c x w x

BS4  TEST

BS4  TEST

BS3  RETURN

BS3  RETURN

BS4  TEST

BS1  MODE

Summary of Contents for RXQ5P7W1B

Page 1: ...ION MANUAL RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA RXYQ5P7W1B RXYQ8P8W1B RXYQ10P7W1B RXYQ12P7W1B RXYHQ12P8W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA System air co...

Page 2: ...Q16 36 RX Y Q5 RX Y Q8 18 RXYHQ12 2 1 h1 h2 a 10 mm b 300 mm c 10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 5...

Page 3: ...UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 P1 P2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O...

Page 4: ...a 16 megfelelnek az al bbi szabv ny ok nak vagy egy b ir nyad dokumentum ok nak ha azokat el r s szerint haszn lj k 17 spe niaj wymogi nast puj cych norm i innych dokument w normalizacyjnych pod warun...

Page 5: ...yll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmi...

Page 6: ...ndoor units for air conditioning purposes and suitable for R410A The present installation manual describes the procedures for unpacking installing and connecting the RX Y Q P RXYHQ units Installation...

Page 7: ...Q54 RXYQ18 RXYQ18 RXYQ18 675 1755 64 Standard combination of outdoor units Total capacity of indoor units Total quantity of indoor units RXYHQ12 a a main unit 150 390 30 RXYHQ16 RXYQ8 RXYQ8 200 520 32...

Page 8: ...ave obstacles the wall heights have no influence on any indicated service space dimensions 3 Make sure that there is no danger of fire due to leakage of inflammable gas 4 Ensure that water can not cau...

Page 9: ...fore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc See figure 2 In places with weak reception keep distances of 3 m...

Page 10: ...is to be installed on a frame install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit When installed in a corros...

Page 11: ...as shown in the figure 2 Removing the pinched piping When connecting refrigerant piping to the outdoor unit first remove the pinched piping Do not vent gases into the atmosphere Removing of the pinche...

Page 12: ...into the piping side Pattern 1 Pattern 2 Prohibited patterns change to pattern 1 or 2 To avoid the risk of oil retention to the outmost outdoor unit always connect the stop valve and the piping betwe...

Page 13: ...stallation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level d...

Page 14: ...kits can only be used with R410A How to select the refnet joint When using refnet joints at the first branch counted from the outdoor unit side Choose from the following table in accordance with the c...

Page 15: ...YQ34P 1x 16 1x 18 If the outdoor unit is RXYQ34P and the piping lengths are as below B A C D E B B Outdoor unit capacity type Piping size outer diameter mm Gas pipe Liquid pipe RX Y Q5 15 9 9 5 RX Y Q...

Page 16: ...ength of above pipes must be doubled except main pipe and the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p...

Page 17: ...lator R10 Resistor current sensor A4P A8P R31T 33T Thermistor discharge M1C M3C R50 59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure swi...

Page 18: ...mm2 RXYQ30 3 N 50 Hz 400 V 55 2 A 63 A 0 75 1 25 mm2 RXYQ32 3 N 50 Hz 400 V 63 0 A 80 A 0 75 1 25 mm2 RXYQ34 3 N 50 Hz 400 V 64 0 A 80 A 0 75 1 25 mm2 RXYQ36 3 N 50 Hz 400 V 65 0 A 80 A 0 75 1 25 mm2...

Page 19: ...bnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of...

Page 20: ...h protective tape in order to prevent damage to the wires put the wires through field supplied protective wire conduits at that location or install suitable field supplied wire nipples or rubber bushi...

Page 21: ...ow the limits below If the unit to unit cables are beyond these limits it may result in malfunction of transmission Maximum wiring length 1000 m Total wiring length 2000 m Maximum interunit wiring len...

Page 22: ...are established When disconnecting the power supply cord the current carrying connections must be separated before the earth connection is Length of the conductors between the power supply cord anchor...

Page 23: ...additional charging For charging the additional refrigerant follow the procedure as described in this chapter 11 1 Important information regarding the refrigerant used This product contains fluorinat...

Page 24: ...uid refrigerant with the cylinder in upright position Charge the liquid refrigerant with the cylinder in up side down position Charging with an unsuitable substance may cause explosions and accidents...

Page 25: ...ing function the refrigerant leak detection function can not be used When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your...

Page 26: ...d press the button once As long as the button is not pressed the system will remain in heating mode This can be required to increase the indoor temperature 10 Press the button to perform the temperatu...

Page 27: ...nd B and the stop valves must be left closed and charge the required amount of refrigerant through the liquid side stop valve service port When the required amount of refrigerant is fully charged clos...

Page 28: ...hown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure When the charging amount is little the PE code may not be displayed...

Page 29: ...ing refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded LED display Default status before delivery Micro computer operation monitor M...

Page 30: ...sulated stick such as a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution w...

Page 31: ...n wiring and cool heat selection on page 16 not installed factory setting 2 4 NOT USED DO NOT CHANGE THE FACTORY SETTING What to set with dip switch DS2 1 4 NOT USED DO NOT CHANGE THE FACTORY SETTING...

Page 32: ...n level setting via the external control adapter F power consumption limitation setting via the external control adapter G enabling function of the low noise operation level setting and or power consu...

Page 33: ...f the operation is completed Normal operation will be possible after 5 minutes If a malfunction code is displayed on the remote controller correct the malfunction and perform the check operation again...

Page 34: ...gerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of...

Page 35: ...n level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done...

Page 36: ...NOTES NOTES...

Page 37: ...3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 30 13 14 3 5 4 2 1 7 8 9 6 10 10...

Page 38: ...4PW48461 1 Copyright Daikin...

Reviews: