13 Maintenance and service

Installation and operation manual

32

RWEYQ8~RWEYQ8~14T9Y1B

VRV IV water-cooled system air conditioner

4P452190-1A – 2017.04

To adjust

For programming temperature, fan speed and air flow direction refer
to the operation manual of the user interface.

12.3

Using the dry program

12.3.1

About the dry program

▪ The  function  of  this  program  is  to  decrease  the  humidity  in  your

room with minimal temperature decrease (minimal room cooling).

▪ The  micro  computer  automatically  determines  temperature  and

fan speed (cannot be set by the user interface).

▪ The system does not go into operation if the room temperature is

low (<20°C).

12.3.2

To use the dry program (WITHOUT cool/
heat changeover remote control switch)

To start

1

Press the operation mode selector button on the user interface
several times and select 

 (program dry operation).

2

Press the ON/OFF button of the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

3

Press  the  air  flow  direction  adjust  button  (only  for  double-flow,
multi-flow,  corner,  ceiling-suspended  and  wall-mounted).  Refer
to 

"12.4 Adjusting the air flow direction" on page 32

 for details.

To stop

4

Press the ON/OFF button on the user interface once again.

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

12.3.3

To use the dry program (WITH cool/heat
changeover remote control switch)

To start

1

Select  cooling  operation  mode  with  the  cool/heat  changeover
remote control switch.

1

1

2

Press the operation mode selector button on the user interface
several times and select 

 (program dry operation).

3

Press the ON/OFF button of the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

4

Press  the  air  flow  direction  adjust  button  (only  for  double-flow,
multi-flow,  corner,  ceiling-suspended  and  wall-mounted).  Refer
to 

"12.4 Adjusting the air flow direction" on page 32

 for details.

To stop

5

Press the ON/OFF button on the user interface once again.

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

12.4

Adjusting the air flow direction

Refer to the operation manual of the user interface.

12.4.1

About the air flow flap

Double flow+multi-flow units

Corner units

Ceiling suspended units

Wall-mounted units

For  the  following  conditions,  a  micro  computer  controls  the  air  flow
direction which may be different from the display.

The air flow direction can be adjusted in one of the following ways:

▪ The air flow flap itself adjusts its position.

▪ The air flow direction can be fixed by the user.

▪ Automatic 

 and desired position  .

WARNING

Never touch the air outlet or the horizontal blades while the
swing  flap  is  in  operation.  Fingers  may  become  caught  or
the unit may break down.

NOTICE

▪ The  movable  limit  of  the  flap  is  changeable.  Contact

your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).

▪ Avoid operating in the horizontal direction 

. It may

cause dew or dust to settle on the ceiling or flap.

12.5

Setting the master user interface

12.5.1

About setting the master user interface

The  displays  of  slave  user  interfaces  show 

  (change-over

under  centralised  control)  and  slave  user  interfaces  automatically
follow the operation mode directed by the master user interface.

Only the master user interface can select heating or cooling mode.

13

Maintenance and service

NOTICE

Never  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work.

WARNING

Never replace a fuse with a fuse of a wrong ampere ratings
or  other  wires  when  a  fuse  blows  out.  Use  of  wire  or
copper wire may cause the unit to break down or cause a
fire.

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...

Page 34: ...r centralized control it shows that this is a slave user interface When the cool heat changeover remote control switch is installed and the display shows change over under centralized control this is...

Page 35: ...minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped This is because the crankcase heater is warming the compressor so that the compressor can start smoothly 14...

Page 36: ...4P452190 1A 2017 04 Copyright 2017 Daikin 4P452190 1 A 0000000Y...

Reviews: