background image

5 Installation

Installation and operation manual

22

RWEYQ8~RWEYQ8~14T9Y1B

VRV IV water-cooled system air conditioner

4P452190-1A – 2017.04

A1P

5.8.6

To connect the power supply

The power supply must be clamped to the plastic bracket using field
supplied clamp material.

The  green  and  yellow  striped  wire  must  be  used  for  earthing  only
(refer to the figure below).

e

i

f

b

a

c

d

h

e

g

a

Power supply (380~415 V - 3N~ 50 Hz 

OR

 400 V -

3N~ 60 Hz)

b

Fuse

c

Earth leakage protector

d

Earth wire

e

Power supply terminal block

f

Connect each power wire: RED to L1, WHT to L2, BLK to
L3 and BLU to N

g

Earth wire (GRN/YLW). When connecting the earth wire, it
is recommended to perform curling.

h

Clamp the power supply to the bracket using a field
supplied clamp to prevent external force being applied to
the terminal.

i

Cup washer.

Multiple outdoor units

To connect the power supply for multiple outdoor units to each other,
ring tongues have to be used. No bare cable can be used.

In  that  case,  the  ring  washer  that  is  installed  by  default  should  be
removed.

Attach both cables to the power supply terminal as indicated below:

L1 L2 L2 N

5.8.7

To connect the optional wiring

For  the  optional  wiring  use  insulated  wires  of  a  rated  voltage  of
250 V or higher and a minimal cross section of 1.25 mm² for single
core wires and 0.75 mm² for multicore wires.

Variable water flow

The variable water flow output signal is a low voltage control signal
which generates an output of 2~10 V DC depending on the required
water  flow  rate  through  the  plate  heat  exchanger.  For  more
information, see 

"4.3.3 About the water flow rate" on page 11

.

NOTICE

The  maximum  output  power  of  the  2~10  V  DC  output
signal  is  50  mW.  Exceeding  this  power  can  result  in
damage of the system.

Always use shielded cables with a minimal cross section of
0.75 mm² and a length limited to 100 m.

The control line of the valve/pump should be connected to the X2M
connector in the electrical switchbox. To connect the valve/pump to
the  outdoor  unit,  also  provide  a  separate  12  V  DC  power  supply
(with an output power of at least 50 mW) to the X2M connector.

Connect the valve/pump to: X2M terminals 2 and 3.

Connect  the  power  source  to  X2M  terminals  1  and  3  (respect  the
polarity).

BLK

INTER

LOCK

TW1

IN

TW2

OUT

WHT

BLU

BLU

BLU

YLW

ORG

RED

BRN

+ –

1 2 3 4 5 6 7 8 9 10

X2M

+

2~10 V DC

12 V DC

a

b

X2M

a

Valve/pump

b

Power supply

NOTICE

Make  sure  to  connect  a  flow  switch  to  your  water-cooled
VRV IV system. Running the system with a flow rate below
the  minimum  requirement  can  result  in  damage  of  the
system.

Interlock

It is mandatory to connect a flow switch to the interlock circuit of the
outdoor  unit.  Running  the  system  with  a  flow  rate  below  the
minimum requirement can result in damage of the system. The flow
switch should be installed in the main water circuit between the plate
heat exchanger and the closed valve. Select a flow switch contact of
at least 15 V DC, 1 mA.

Connect the flow switch to: X2M terminals 5 and 6.

In  case  of  a  multi  outdoor  unit  system,  install  one  or  more  flow
switches  depending  on  the  installation  of  the  water  system  so  that
water flow is guaranteed under every condition.

NOTICE

If  the  flow  switch  is  installed  in  a  variable  water  flow
system, take into account the inertia of the water flow. If a
variable water flow system is used, the flow switch control
should  be  linked  to  the  compressor  operation  using  the
multifunction output terminal "b".

Failure to do so will result in unintended "forced thermo off"
conditions.

Example:

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...

Page 34: ...r centralized control it shows that this is a slave user interface When the cool heat changeover remote control switch is installed and the display shows change over under centralized control this is...

Page 35: ...minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped This is because the crankcase heater is warming the compressor so that the compressor can start smoothly 14...

Page 36: ...4P452190 1A 2017 04 Copyright 2017 Daikin 4P452190 1 A 0000000Y...

Reviews: