background image

4 Preparation

Installation and operation manual

11

RWEYQ8~RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452190-1A – 2017.04

Filter.

 Install the filter in the water piping inlet within a distance of

1.5  m  from  the  outdoor  unit.  If  sand,  waste  or  rust  particles  are
mixed in the water circulation system, metal materials will become
corroded.

Insulation.

 Insulate up to the base of the heat exchanger.

80 mm

b

l

g

d

e

e

a

i

j

c

k

h

f

a

Air purge (field supply)

b

Water outlet

c

Water inlet

d

Shut-off valve (field supply)

e

Water connection

f

Water piping (field supply)

g

Insulation (field supply)

h

Heat exchanger

i

Filter (accessory)

j

Drain valve (field supply)

k

Drain connection

l

Insulation cover

Water  pump.

  After  filling  the  water  piping,  run  the  water  pump

(field  supply)  to  flush  the  water  piping.  After  flushing,  clean  the
filter.

Freeze.

 Protect against freezing.

Water pipes.

 ALWAYS comply with local and national regulations.

Water  piping 

  Tightening  torque

.  Securely  tighten  the  water

piping with a tightening torque of ≤300 N•m. Overtightening results
in damage to the unit.

Field  supply  components  –  Water.

  Only  use  materials  that  are

compatible  with  water  used  in  the  system  and  with  the  materials
used in the outdoor unit.

Field supply components – Water pressure and temperature.

Check  that  all  components  in  the  field  piping  can  withstand  the
water pressure and water temperature.

Water pressure.

 The maximum water pressure is 37 bar. Provide

adequate  safeguards  in  the  water  circuit  to  ensure  that  the
maximum pressure is NOT exceeded.

Drainage – Low points.

 Provide drain taps at all low points of the

system in order to allow complete drainage of the water circuit.

Drainage  –  Clogging.

  Make  sure  that  the  water  runs  smoothly

without any clogging by dirt.

Drainage 

  Lateral  length

.  Lateral  length  of  drainage  should  be

as  short  as  possible  (≤400  mm)  and  installed  in  a  downward
direction. The diameter of the drain pipe must be the same as the
diameter of the pipe on the outdoor unit.

Non-brass  metallic  piping.

  When  using  non-brass  metallic

piping,  insulate  the  brass  and  non-brass  properly  so  that  they  do
NOT  make  contact  with  each  other.  This  to  prevent  galvanic
corrosion.

4.3.2

Handling the brazed plate heat exchanger

INFORMATION

A  brazed  plate  heat  exchanger  is  used.  Because  of  a
different  structure  from  a  conventional  heat  exchanger,  it
MUST be handled in a different manner.

▪ Install  a  water  filter  at  the  water  inlet  in  order  to  prevent  foreign

materials  such  as  dust,  sand,…  from  entering  the  plate  heat
exchanger.

▪ Scale  can  stick  to  the  plate  heat  exchanger  depending  on  water

quality.  To  remove  scale,  cleaning  is  necessary  at  regular
intervals using chemicals. Install a shut-off valve at the end in the
water  piping.  Install  a  piping  connection  port  on  the  piping
between  this  shut-off  valve  and  the  outdoor  unit  for  cleaning  by
chemicals.

▪ For cleaning and water draining of the outdoor unit (long period of

non-use or during non-use in winter), install an air purge plug (for
joint  use  with  cleaning  port)  (field  supply)  and  a  water  draining
plug at the inlet/outlet ports of the water piping. Additionally, install
an  automatic  air  purge  valve  (field  supply)  at  the  top  of  rising
piping or at the top of a portion where air tends to stay.

▪ Install  an  additional  cleanable  filter  (field  supply)  in  front  of  the

pump inlet.

▪ Carry  out  complete  cooling/thermal  insulation  of  the  water  piping

and the outdoor unit drain piping. If insulation has not been carried
out,  the  unit  may  sustain  damage  during  severe  winters  due  to
freezing, in addition to thermal loss.

▪ When  you  stop  the  unit  during  night  or  winter,  take  measures  to

prevent  water  circuits  from  natural  freezing  in  areas  where  the
ambient temperature drops below 0°C (by water drain off, keeping
the  circulation  pump  running,  warming  up  by  a  heater,…).
Freezing of water circuits may result in damage to the plate heat
exchanger.  Therefore,  take  appropriate  measures  depending  on
the circumstances.

a

b

c

d

e  

a

Water inlet piping

b

Filter (accessory)

c

Air purge plug (for joint use with cleaning port) (field
supply)

d

Cleaning device

e

Filter for pump (field supply)

f

Automatic air purge valve (field supply)

g

Water outlet piping

h

Joint use with water draining plug

i

Plate heat exchanger

4.3.3

About the water flow rate

The RWEYQ*T9Y1B models are equipped with the logic to operate
with a variable water flow rate function.

a
b

c

a

Constant flow

b

Flow regulating valve (field supply)

c

Inverter pump (field supply)

A system can either be configured as a constant flow system (a), a
variable  flow  system  with  valve  (b)  or  a  variable  flow  system  with  a
pump (c).

▪ Constant  flow  system  (a):  the  variable  water  flow  rate  function  is

not used.

▪ A  pressure  independent  flow  regulating  valve  (b):  the  valve

controls  the  flow  rate  of  a  centralized  inverter  pump  through  the
unit.

▪ Inverter  pump  (c):  the  pump  directly  controls  the  water  flow  rate

through the unit.

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...

Page 34: ...r centralized control it shows that this is a slave user interface When the cool heat changeover remote control switch is installed and the display shows change over under centralized control this is...

Page 35: ...minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped This is because the crankcase heater is warming the compressor so that the compressor can start smoothly 14...

Page 36: ...4P452190 1A 2017 04 Copyright 2017 Daikin 4P452190 1 A 0000000Y...

Reviews: