6 Configuration

Installation and operation manual

23

RWEYQ8~RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452190-1A – 2017.04

X3M

X3M

YLW

a
b
c
d
e

ORG
RED
BRN
BLU
BLU
WHT
WHT

BLK
BLK

BLK

TW1

IN

TW2

OUT

WHT

BLU

BLU

BLU

YLW

ORG

RED

BRN

0

10

+ -

1 2 3 4 5 6 7 8 9 10

X2M

b

a

X2M

a

Relay (normally closed) (field supply)

b

Flow switch (field supply)

Multifunction outputs

To  monitor  the  outdoor  unit  operation  or  trigger  field  supplied
equipment connected to the outdoor unit, this RWEYQ*T9, series is
equipped with 5 output contacts.

General contact specifications: 220 V AC, 3 mA-0.5 mA.

To  connect  these  output  signals,  choose  the  applicable  contacts  in
the X3M terminal in the table below:

X3M

X3M

YLW

a
b

c
d
e

ORG
RED
BRN
BLU
BLU
WHT
WHT

BLK
BLK

Terminal

Function

a

Error on remote controller

b

Compressor operation

c

Heating operation

d

Cooling operation

e

Water pump operation request

6

Configuration

INFORMATION

It  is  important  that  all  information  in  this  chapter  is  read
sequentially  by  the  installer  and  that  the  system  is
configured as applicable.

DANGER: RISK OF ELECTROCUTION

6.1

Making field settings

6.1.1

About making field settings

To continue the configuration of the VRV IV heat recovery system, it
is  required  to  give  some  input  to  the  PCB  of  the  unit.  This  chapter
will  describe  how  manual  input  is  possible  by  operating  the  push
buttons  on  the  PCB  and  reading  the  feedback  from  the  7‑segment
displays.

Making settings is done via the master outdoor unit.

Next to making field settings it is also possible to confirm the current
operation parameters of the unit.

Push buttons

Performing  special  actions  (automatic  refrigerant  charge,  test  run,
etc.)  and  making  field  settings  (demand  operation,  low  noise,  etc.)
happens by way of operating the push buttons.

See also:

"6.1.2 Field setting components" on page 23

"6.1.3 To access the field setting components" on page 24

PC configurator

For VRV IV heat recovery system it is alternatively possible to make
several  commissioning  field  settings  through  a  personal  computer
interface  (for  this,  option  EKPCCAB  is  required).  The  installer  can
prepare the configuration (off-site) on PC and afterwards upload the
configuration to the system.

See  also: 

"6.1.9  To  connect  the  PC  configurator  to  the  outdoor

unit" on page 26

.

Mode 1 and 2

Mode

Description

Mode 1

(monitoring
settings)

Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
contents can be monitored as well.

Mode 2

(field settings)

Mode 2 is used to change the field settings of
the system. Consulting the current field setting
value and changing the current field setting
value is possible.

In general, normal operation can be resumed
without special intervention after changing field
settings.

Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.

See also:

"6.1.4 To access mode 1 or 2" on page 24

"6.1.5 To use mode 1" on page 24

"6.1.6 To use mode 2" on page 24

"6.1.7 Mode 1: Monitoring settings" on page 25

"6.1.8 Mode 2: Field settings" on page 25

6.1.2

Field setting components

Location of the 7‑segment displays, buttons and DIP switches:

a

b

BS1 BS2

DS1 DS2

BS3

X27A

BS1

MODE: For changing the set mode

BS2

SET: For field setting

BS3

RETURN: For field setting

DS1, DS2

DIP switches

a

7‑segment displays

b

Push buttons

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...

Page 34: ...r centralized control it shows that this is a slave user interface When the cool heat changeover remote control switch is installed and the display shows change over under centralized control this is...

Page 35: ...minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped This is because the crankcase heater is warming the compressor so that the compressor can start smoothly 14...