12 Operation

Installation and operation manual

31

RWEYQ8~RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452190-1A – 2017.04

12

Operation

12.1

Operation range

Use the system in the following temperature and humidity ranges for
safe and effective operation.

Above operation range is only valid in case direct expansion indoor
units are connected to the VRV IV system.

Special operation ranges are valid in case of using Hydrobox units or
AHU.  They  can  be  found  in  the  installation/operation  manual  of  the
dedicated  unit.  Latest  information  can  be  found  in  the  technical
engineering data.

12.2

Operating the system

12.2.1

About operating the system

▪ Operation  procedure  varies  according  to  the  combination  of

outdoor unit and user interface.

▪ To protect the unit, turn on the main power switch 6 hours before

operation.

▪ If the main power supply is turned off during operation, operation

will restart automatically after the power turns back on again.

12.2.2

About cooling, heating, fan only, and
automatic operation

▪ Changeover cannot be made with a user interface whose display

shows 

  "change-over  under  centralised  control"  (refer  to

installation and operation manual of the user interface).

▪ When  the  display 

  "change-over  under  centralised  control"

flashes,  refer  to 

"12.5.1  About  setting  the  master  user

interface" on page 32

.

▪ The fan may keep on running for about 1 minute after the heating

operation stops.

▪ The  air  flow  rate  may  adjust  itself  depending  on  the  room

temperature  or  the  fan  may  stop  immediately.  This  is  not  a
malfunction.

12.2.3

About the heating operation

It  may  take  longer  to  reach  the  set  temperature  for  general  heating
operation than for cooling operation.

The following operation is performed in order to prevent the heating
capacity from dropping or cold air from blowing.

Defrost operation

In  heating  operation,  freezing  of  the  outdoor  unit's  air  cooled  coil
increases  over  time,  restricting  the  energy  transfer  to  the  outdoor
unit's coil. Heating capability decreases and the system needs to go
into defrost operation to be able to deliver enough heat to the indoor
units.

In case of

Then

RWEYQ16~42 multi-
models

The indoor unit will continue heating
operation at a reduced level during defrost
operation. It will guarantee a decent comfort
level indoor.

RWEYQ8~14 single
models

The indoor unit will stop fan operation, the
refrigerant cycle will reverse and energy
from inside the building will be used to
defrost the outdoor unit coil.

The indoor unit will indicate defrost operation on the display 

.

Hot start

In order to prevent cold air from blowing out of an indoor unit at the
start  of  heating  operation,  the  indoor  fan  is  automatically  stopped.
The  display  of  the  user  interface  shows 

.  It  may  take  some

time before the fan starts. This is not a malfunction.

12.2.4

To operate the system (WITHOUT cool/
heat changeover remote control switch)

1

Press the operation mode selector button on the user interface
several times and select the operation mode of your choice.

Cooling operation

Heating operation

Fan only operation

2

Press the ON/OFF button on the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

12.2.5

To operate the system (WITH cool/heat
changeover remote control switch)

Overview of the changeover remote control switch

a

b

a

FAN ONLY/AIR CONDITIONING
SELECTOR SWITCH

Set the switch to 

 for fan only

operation or to 

 for heating or

cooling operation.

b

COOL/HEAT CHANGEOVER SWITCH

Set the switch to 

 for cooling or to 

for heating

To start

1

Select operation mode with the cool/heat changeover switch as
follows:

Cooling operation

 

1

1

Heating operation

 

1

1

Fan only operation

1

2

Press the ON/OFF button on the user interface.

Result: 

The  operation  lamp  lights  up  and  the  system  starts

operating.

To stop

3

Press the ON/OFF button on the user interface once again.

Result: 

The  operation  lamp  goes  out  and  the  system  stops

operating.

NOTICE

Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...

Page 34: ...r centralized control it shows that this is a slave user interface When the cool heat changeover remote control switch is installed and the display shows change over under centralized control this is...

Page 35: ...minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped This is because the crankcase heater is warming the compressor so that the compressor can start smoothly 14...

Page 36: ...4P452190 1A 2017 04 Copyright 2017 Daikin 4P452190 1 A 0000000Y...

Reviews: