4 Preparation

Installation and operation manual

10

RWEYQ8~RWEYQ8~14T9Y1B

VRV IV water-cooled system air conditioner

4P452190-1A – 2017.04

▪ Concerning  refnet  headers,  choose  from  the  following  table  in

accordance with the total capacity of all the indoor units connected
below the refnet header.

Indoor unit capacity

index

2 pipes

3 pipes

<200

KHRQ22M29H

KHRQ23M29H

200≤x<290

290≤x<640

KHRQ22M64H

(a)

KHRQ23M64H

(a)

≥640

KHRQ22M75H

KHRQ23M75H

(a)

If the pipe size above the refnet header is Ø34.9 mm or
more, KHRQ22M75H is required.

INFORMATION

Maximum 8 branches can be connected to a header.

▪ How  to  choose  an  outdoor  multi  connection  piping  kit.  Choose

from the following table in accordance with the number of outdoor
units.

Number of outdoor units

Branch kit name

2

BHFQ22P1007

3

BHFQ22P1517

INFORMATION

Reducers or T-joints are field supplied.

NOTICE

Refrigerant branch kits can only be used with R410A.

4.2.4

Multiple outdoor units: Possible layouts

▪ The  piping  between  the  outdoor  units  must  be  routed  level  or

slightly upward to avoid the risk of oil retention into the piping.

Pattern 1

a

b

Pattern 2

a

b

a

b

a

b

a

To indoor unit

b

Piping between outdoor units

X

Not allowed (oil remains in piping)

O

Allowed

▪ If the piping length between the outdoor unit connecting pipe kit or

between the outdoor units exceeds 2 m, create a rise of 200 mm
or more in the gas line within a length of 2 m from the kit.

▪ For the gas piping (both discharge and suction gas piping in case

of  the  heat  recovery  system)  after  the  branch,  install  a  trap  of
200  mm  or  more  using  the  piping  included  in  the  piping  kit  for
connecting the outdoor unit. Otherwise, the refrigerant may stay in
the piping, causing damage to the outdoor unit.

≥200 mm

If

Then

≤2 m

≤2 m

b

a

>2 m

≤2 m

≤2 m

≥200 mm

≥200 mm

>2 m

>2 m

b

a

a

To indoor unit

b

Piping between outdoor units

NOTICE

There  are  restrictions  on  the  refrigerant  pipe  connection
order between outdoor units during installation in case of a
multiple  outdoor  unit  system.  Install  according  to  following
restrictions.  The  capacities  of  outdoor  units  A,  B  and  C
must fulfill the following restriction conditions: A≥B≥C.

a

c

b

A

B

C

a

 To indoor units

b

 Outdoor unit multi connecting piping kit (first branch)

c

 Outdoor unit multi connecting piping kit (second branch)

4.3

Preparing water piping

4.3.1

Water circuit requirements

NOTICE

In  case  of  plastic  pipes,  make  sure  they  are  fully  oxygen
diffusion  tight  according  to  DIN  4726.  The  diffusion  of
oxygen into the piping can lead to excessive corrosion.

Connecting piping – Legislation.

 Make all piping connections in

accordance  with  the  applicable  legislation  and  the  instructions  in
the "Installation" chapter, respecting the water inlet and outlet.

Connecting  piping  –  Force.

  Do  NOT  use  excessive  force  when

connecting  the  piping.  Deformation  of  the  piping  can  cause
malfunctioning of the unit.

Connecting  piping  –  Tools.

  Only  use  appropriate  tooling  to

handle  brass,  which  is  a  soft  material.  If  NOT,  pipes  will  get
damaged.

Connecting  piping  –  Stainless  steel.

  Only  use  stainless  steel

material to connect the water piping to the unit. If NOT, pipes will
get  corroded.  Take  preventive  measures,  for  example  by
insulating the connection on the water pipe.

Connecting piping – Air, moisture, dust.

 If air, moisture or dust

gets into the circuit, problems may occur. To prevent this:

▪ Only use clean pipes

▪ Hold the pipe end downwards when removing burrs.

▪ Cover the pipe end when inserting it through a wall, to prevent

dust and/or particles entering the pipe.

▪ Use a decent thread sealant to seal connections.

Piping  work

  – 

Dripping

.  The  outdoor  unit  is  intended  for  indoor

installation.  Carry  out  piping  work  in  such  a  way  that  no  water
drips on the outdoor unit.

Outlets.

 Do NOT connect the 

drain

 outlet to the 

water

 outlet.

Summary of Contents for RWEYQ10T9Y1B

Page 1: ...lation and operation manual VRV IV water cooled system air conditioner English Installation and operation manual VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ1...

Page 2: ...8 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platno...

Page 3: ...S vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplot...

Page 4: ...19 5 7 Connecting the water piping 20 5 7 1 About connecting the water piping 20 5 7 2 To connect the water piping 20 5 7 3 To fill the water circuit 20 5 7 4 To insulate the water piping 20 5 8 Conn...

Page 5: ...ed installers end users Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing...

Page 6: ...it This installation manual concerns the VRV IV water cooled system air conditioner The unit is full inverter driven and can be used for cooling heat pump and heat recovery applications Model line up...

Page 7: ...er 4 Preparation 4 1 Preparing installation site 4 1 1 Installation site requirements of the outdoor unit Mind the spacing guidelines See the Technical data chapter CAUTION Appliance not accessible to...

Page 8: ...termine the proper size using the following tables and reference figure only for indication In case of heat pump mode A B B B C D F G E x y b a 3 1 2 4 5 1 2 VRV DX indoor unit 3 BP box 4 5 RA DX indo...

Page 9: ...meter size mm 18 22 15 9 19 1 24 26 34 19 1 22 2 36 42 F Piping between refrigerant branch kit and BP unit Heat pump mode in case of single outdoor unit Pipe size for direct connection on BP unit must...

Page 10: ...b a a To indoor unit b Piping between outdoor units NOTICE There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit...

Page 11: ...it MUST be handled in a different manner Install a water filter at the water inlet in order to prevent foreign materials such as dust sand from entering the plate heat exchanger Scale can stick to the...

Page 12: ...ow rate D Model D RWEYQ8 12 120 l min RWEYQ14 190 l min 3 Hydronic flow rate E The value E is the design flow rate calculated by the hydronic engineer when designing the building system Correct valve...

Page 13: ...ic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment failure 4 SW8 2 1 5 2 Mounting the outdoor unit 5 2 1 To provide the installation structur...

Page 14: ...m of straight section can be ensured 120 mm 500 mm 5 3 4 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the...

Page 15: ...umstances Use the following procedure to remove the pinched piping 1 Remove the valve cover and make sure that the stop valves are fully closed a c d b a Service port and service port cover b Stop val...

Page 16: ...nt in the refrigerant piping for example water may have entered the piping first carry out the vacuum drying procedure below until all moisture has been removed All piping inside the unit has been fac...

Page 17: ...k the vacuum by pressurising with nitrogen gas to a gauge pressure of 0 05 MPa 0 5 bar and repeat steps 1 to 3 until all moisture has been removed 4 Depending on whether you want to immediately charge...

Page 18: ...CR 100 charge an additional 0 5 kg of refrigerant per outdoor unit In case of heat recovery mode Formula R X1 22 2 0 37 X2 19 1 0 26 X3 15 9 0 18 X4 12 7 0 12 X5 9 5 0 059 X6 6 4 0 022 1 04 A C R Addi...

Page 19: ...t the refrigerant tanks to each outdoor unit NOTICE The refrigerant charging port is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so b...

Page 20: ...he water circulation system otherwise the plate heat exchanger will freeze 4 Check if the water flow rate is correct otherwise the plate heat exchanger will freeze Measure any water pressure loss befo...

Page 21: ...oor unit PCB A1P b Unit A master outdoor unit c Unit B slave outdoor unit d Unit C slave outdoor unit e Outdoor unit other system transmission F1 F2 f Outdoor outdoor unit transmission Q1 Q2 g Indoor...

Page 22: ...f the 2 10 V DC output signal is 50 mW Exceeding this power can result in damage of the system Always use shielded cables with a minimal cross section of 0 75 mm and a length limited to 100 m The cont...

Page 23: ...refrigerant charge test run etc and making field settings demand operation low noise etc happens by way of operating the push buttons See also 6 1 2 Field setting components on page 23 6 1 3 To access...

Page 24: ...shed and normal the 7 segment display indication state will be as below default situation when shipped from factory Stage Display When turning on the power supply flashing as indicated First checks on...

Page 25: ...ws 1 5 The current Te target parameter position 1 6 The current Tc target parameter position 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system 1 17 1 18 1 19 Sh...

Page 26: ...operation not only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous NOTICE Be sure to turn on the power 6 ho...

Page 27: ...lves opening Judgement of piping length In case Hydrobox units are present in the system the pipe length check and the refrigerant situation check will not be performed Make sure to carry out the syst...

Page 28: ...oor units 8 Troubleshooting 8 1 Solving problems based on error codes In case of a displayed malfunction code perform correcting actions as explained in the malfunction code table After correcting the...

Page 29: ...L 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoid...

Page 30: ...reless user interface m Water system connection Heat pump system g c g g h g g c c c d f e i j b a a Unit b Refrigerant piping c VRV DX indoor unit d LT Hydrobox unit e BP box required to connect Resi...

Page 31: ...over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor unit...

Page 32: ...s the air flow direction adjust button only for double flow multi flow corner ceiling suspended and wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 5 Press t...

Page 33: ...nd in order to ensure the best possible maintenance of your units we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities Our network of dealers has ac...