2-30
014
E207
Alarm
Logic
Defrost can not be completed within 90 minutes.
(The condition EOS
≧
10
℃
was not satisfied five defrosting times continuously during 90-minute
counting).
Possible
Causes
*
Excessive frost on the evaporator coil. Frost partially remains.
*
Setting time of defrosting interval is too long.
*
Temperature of hot-gas for defrosting is low. Insufficient hot-gas circulation.
Trouble
Shooting
1. Defrost remaining frost by manual defrosting.
Also, check whether defrost completion condition (EOS
≧
30
℃
& RS
≧
15
℃
) are reached
within 90 minutes on the LCD screen (
※
3 Sensor Information in paragraph 2.3).
*
If the read reaches to completion condition, it is normal. Wait and see.
*
If the read does not reach to completion condition, there may be low hot-gas temperature,
insufficient hot-gas circulation, and so forth.
Controller
Action
E207
Alarm display only
015
E304
Alarm
Logic
Setting error of reheat coil
Possible
Causes
Setting error in Configuration Set (
*
12 Configuration Set in paragraph 2.3)
*
Reheat Coil is set to "OFF" for the unit with dehumidification control (reheat coil installed).
Trouble
Shooting
For the unit with dehumidification control (reheat coil installed), change the Reheat Coil setting
from "OFF" to "ON" in the configuration setting (
*
12 Configuration Set in paragraph 2.3).
Controller
Action
E304
Alarm display only (Alarm LED is blinking.)