2-41
102
F52E
・
F52F
E52D
・
E52E
・
E52F
Alarm
Logic
&
Possible
Causes
Alarm Logic
Possible Causes
E52D
:
Fin temperature sensor failure
Inverter board failure
(
Fin temperature
sensor
)
(
Fin temperature
≧
175
℃
or -45
≦℃)
F52E
:
E52E is generated 4 times.
E52E
:
Instantaneous overcurrent failure
Inverter board failure
(
IPM part
)
IPM
:
Intelligent Power Module
F52F
:
E52F is generated 4 times.
E52F
:
Compressor current sensor failure
Inverter board failure
(
Current detection
part
)
Trouble
Shooting
Replacing of inverter board
Controller
Action
F52E, F52F
Unit stop
E52D
Restart after 3 minutes standby (Permanent retry
)
E52E, E52F
Restart after 3 minutes standby (F52E, F52F is generated at 4 times retry.
)