1-3
1.2 Set Point and Protection Device
Component Name
Detector Symbol
Setting Value
Alarm
High pressure switch
HPS
OFF
≧
2400kPa
(
24.47kg/cm
2
)
ON
≦
1900kPa
(
19.37kg/cm
2
)
E101
F101
Pressure control valve
PCV
Open
≧
2450kPa
(
25.0kg/cm
2
)
−
Fusible plug
−
95
〜
100
℃(
203
〜
212
℉)
−
Built-in thermal protector
for condenser fan motor
Q1M
OFF
≧
135
℃±
5
℃(
275
℉±
41
℉)
ON
≦
86
℃±
15
℃(
187
℉±
59
℉)
−
Built-in thermal protector
for evaporator fan motor
−
OFF
≧
145
℃±
5
℃(
293
℉±
41
℉)
ON
≦
94
℃±
15
℃(
201
℉±
59
℉)
−
Circuit breaker (with ear th leakage
breaker)
CB
30A
−
Inverter
circuit
Fin temperature
(IPM protection)
VOT
ON
>
90
℃
E52C
Instantaneous overcurrent
NIDC
ON 51Ap
±
10%
E52E
F52E
Electronic thermal 1
(Compressor overcurrent
protection 1)
ON
>
22.5A, OFF
≦
0.3A
E523
Electronic thermal 2
(Compressor overcurrent
protection 2)
ON
>
30A, OFF
≦
1A
E524
Lightning detection
VDC
ON
≧
125r/s (actual r/s - designated r/s)
E526
Power-supply voltage imbalance
ON
≧
DC35V (Ripple voltage)
E531
Undervoltage
ON
≦
DC290V
E532
Overvoltage
ON
≧
DC790V
●
Fuse and Protection Circuit
Board
Fuse
Type
Protection Circuit
Alarm
I/O board
(
EC2
)
F1U
F10A 250V
fast-acting type
I/O board control power
(
DC13.5V, 5V, 3.3V
)
−
F2U
PCC1, PCC2, CFH, CFL, EFH, EFL
HSV, RSV, LSV, ESV
F703
F707
E115
E117
F3U Spare
−
PT/CT
board
(
EC7
)
F11U
8A 600V
PT/CT board control power
−
Noise filter
board
(
EC9
)
F5U
12.5A 300A
Surge absorber 1 (Lightning protection)
−
F6U
Surge absorber 2 (Lightning protection)
−
F7U
Surge absorber 3 (Lightning protection)
−
F8U
8A 600V
Inverter control circuit
−
I/O board
(
EC2
)
TH1
2.5A 72V
Automatic reset
RM (Remote Monitoring) circuit
−
TH2
TransFresh circuit
−