2-29
012
E202
Alarm
Logic
Automatic pumpdown failure
HPT
≧
2300kPa or DCHS
≧
120
℃
during automatic pump-down.
*
This alarm is a reminder before replacing drier after auto pump-down completion.
Possible
Causes
Refrigerant overcharged.
(All refrigerant can not accumulated in condenser and receiver by pump down.)
Trouble
Shooting
Collect refrigerant from service port
③
until the pressure between LSV and EEV becomes 0kPa
- 350kPa. (The circuit between LSV and EEV is closed.)
Then, replace drier. (Refer to paragraph 4.2)
Controller
Action
E202
Alarm display only
013
E203
Alarm
Logic
Overcooling in chilled mode
SS
≦
SP
ー
3.0
℃
& 5 minutes elapsed (prevention of over cooling) during modulated control.
Possible
Causes
Cooling load changes rapidly. (load small)
Trouble
Shooting
Check for the cause of sudden reduction of the load.
*
Example 1: Set the ventilation outlet from OPEN to CLOSE.
*
Example 2: The door is opened at the low ambient temperature(<SP).
Controller
Action
E203
Restart after 3 minutes standby