2-19
2.5 Alarm Code
●
Alarm grouping
F---
:
Alarm that stops the unit
E---
:
Alarm that restarts the unit or continues the backup operation
T---
:
Alarm during PTI (Refer to paragraph 3.3.2.)
F5---
:
Alarm that stops the unit related to inverter
E5---
:
Alarm that restarts the unit related to inverter
Alarm
grade
Alarm
Controller action at the generating of alarm
A
F ---
F5 --
Uncontrollable state makes the unit to stop.
The problem requires inspection/repair.
Wait for the environment of supplied power to recover.
B
E ---
E5 --
The unit stops, but resumes the operation when the conditions return to be met.
*
E ---
:
Restart after waiting for three minutes, then retry nine times.
Then retry after waiting for four hours.
*
E5 --
:
Restart after waiting for three minutes, then retry infinitely.
(Some jump to F5--- after four or five times of retry.)
C
E ---
Unit continues operation by back-up operation.
D
E ---
Alarm display only. Unit continues operation.
Alarm LED and Alarm Code Display
Alarm
Alarm LED (Red)
Alarm code display
F Alarm
Blinking
Press
or
key to display alarm code.
E Alarm
OFF
(E807, E304 are blinking)
●
F Alarm
Diagnosis
Alarm
code
Alarm content
Controller action
001
F101
HPS activates within 30 sec. after starting operation
UNIT stops
002
F109
LPT remains at -72kPa or less within 2 sec. after starting operation
UNIT stops
003
F301
Temperature setting requirement
UNIT stops
004
F401
Multiple sensor (SS, DSS, RS) failure in chilled mode
UNIT stops
004
F405
Multiple sensor (HPT, DCHS1, DCHS2) failure
UNIT stops
004
F407
Multiple sensor (HPT and LPT) failure
UNIT stops
004
F409
Multiple sensor (LPT, DCHS1, DCHS2) failure
UNIT stops
005
F701
Abnormal power voltage is detected within 2 sec. after power ON
(C/B ON) (
≧
530V or
≦
300V)
One of R, S or T phase missing after power on. (C/B ON)
UNIT stops
006
F703
Abnormal power phase
UNIT stops
007
F705
One of R, S on T phase missing
UNIT stops
008
F707
Fuse F2U blown (I/O board)
UNIT stops
009
F809
E809 is generated 2 times (shortage of refrigerant)
UNIT stops