background image

10 About the system

Installation and operation manual

28

4BY1

Air-cooled refrigeration condensing unit

4P495373-1 – 2017.07

For the user

10

About the system

NOTICE

For future modifications or expansions of your system:

A  full  overview  of  allowable  combinations  (for  future
system  extensions)  is  available  in  technical  engineering
data  and  should  be  consulted.  Contact  your  installer  to
receive more information and professional advice.

10.1

System layout

c

b

d

a

a

Outdoor unit (ZEAS condensing unit)

b

Refrigerant piping

c

Indoor unit (Blower coil)

d

Indoor unit (Showcase)

11

Operation

11.1

Operation range

Use  the  system  in  the  following  temperature  ranges  for  safe  and
effective operation.

Cooling

Outdoor temperature

–20~43°C DB

Evaporating temperature

–20~5°C

11.2

Operating the system

11.2.1

About operating the system

▪ To  start  and  stop  operation  of  the  outdoor  unit,  use  the  external

operation switch.

▪ If the main power supply is turned off during operation, operation

will restart automatically after the power turns back on again.

12

Maintenance and service

NOTICE

Never  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work.

WARNING

Never replace a fuse with a fuse of a wrong ampere ratings
or  other  wires  when  a  fuse  blows  out.  Use  of  wire  or
copper wire may cause the unit to break down or cause a
fire.

CAUTION

Do not insert fingers, rods or other objects into the air inlet
or  outlet.  Do  not  remove  the  fan  guard.  When  the  fan  is
rotating at high speed, it will cause injury.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

Water pressure

Check whether the water pressure is above 1 bar. If it is lower, add
water.

12.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do not use the system until a service person confirms that
the portion where the refrigerant leaks is repaired.

12.2

After-sales service and warranty

12.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

12.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

Summary of Contents for LRMEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...label 16 5 6 Connecting the electrical wiring 17 5 6 1 Field wiring Overview 17 5 6 2 Guidelines when knocking out knockout holes 18 5 6 3 Guidelines when connecting the electrical wiring 18 5 6 4 To...

Page 6: ...accessories from the outdoor unit 1 Remove the service cover See 5 1 1 To open the outdoor unit on page 9 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precaut...

Page 7: ...to top When the copper piping or fan is corroded When the heat exchanger is contaminated Foreign materials including oils for fabrication must be 30 mg 10 m Reuse allowed In other cases than above yo...

Page 8: ...e diameter of the outdoor unit stop valve 15 9 mm to that of the field piping 19 1 mm B C b c Piping between piping branching Use diameters depending on the total capacity of the indoor units connecte...

Page 9: ...The operation switch is located in the switchbox see illustration below R E M O T E OFF O N The operation switch can be set to the following three positions Operation switch setting Function OFF Unit...

Page 10: ...ng the paint field supply 4 Attach the cable s ends Tighten those ends 5 3 Connecting the refrigerant piping DANGER RISK OF BURNING 5 3 1 Using the stop valve and service port To handle the stop valve...

Page 11: ...w Check for refrigerant leaks after tightening the service port cover NOTICE Thread locking fluid Before reattaching the service port cover apply thread locking fluid to the screw thread NOT to the co...

Page 12: ...the unit without a dryer installed Possible consequence Equipment malfunction Install a dryer on the liquid piping Dryer type 80 g 100 molecular sieve equivalent DML083 DML083S Danfoss made Where how...

Page 13: ...example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make con...

Page 14: ...ion of the system higher than the design pressure of the indoor unit 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use...

Page 15: ...e stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves B and C 3 Pre charge refrigerant until the determined additional refrigerant amount is reached or pre charging is not pos...

Page 16: ...to charge the unit even if the opening of the liquid line stop valve is adjusted If this is the case replace the cylinder with one that has more refrigerant remaining If the piping length is long repl...

Page 17: ...1M S1T Y1S Ry 0 S2T NC TeS1 No T1 T1 E1H t Ry0 t Ry 1 K1M S1T H1P P1 P2 W1 C C1 R X3M X1M L2 N L1 L3 B X2M A D C F1 F2 Ry 0 Ry 0 K1M Ry 0 Ry 0 Ry 0 K1M Ry 1 Y1S 3D111889 A e c a b i j k h f b d B B b...

Page 18: ...es when knocking out knockout holes NOTICE Precautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and ar...

Page 19: ...power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break down NOTICE Output signals The outdoor un...

Page 20: ...de 1 and 2 Mode Description Mode 1 monitoring settings Mode 1 can be used to monitor the current situation of the outdoor unit Some field setting contents can be monitored as well Mode 2 field setting...

Page 21: ...information See 6 1 7 Mode 1 and default situation Monitoring settings on page 21 Example 7 LEDs display Mode 1 See 8 1 1 To display the error codes of the latest malfunctions on page 24 6 1 6 To use...

Page 22: ...ating temperature during low noise operation With this setting the target evaporating temperature set with settings 2 0 and 2 1 can be corrected for low noise operation see setting 2 18 default 1 C 2...

Page 23: ...nsulation test of the main power circuit Using a megatester for 500 V check that the insulation resistance of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and eart...

Page 24: ...ly completed normal operation is possible 7 3 3 Correcting after abnormal completion of the test run The test operation is only completed if no malfunction occurs In case of a malfunction perform corr...

Page 25: ...t the switch properly Replace defective component Outdoor fan motor signal failure Abnormal position of signal of 1 fan motor 4 Caution Abnormal fan motor signal circuit error Broken short or disconne...

Page 26: ...acle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction sid...

Page 27: ...microcurrent 1 mA 12 V DC For instructions on how to use the remote switch refer to the technical engineering data 7 The initial state of SW1 is open normal mode To activate low noise mode close the...

Page 28: ...result in injury Water pressure Check whether the water pressure is above 1 bar If it is lower add water 12 1 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gase...

Page 29: ...make sure the air can flow freely Malfunction Measure The system operates but cooling is insufficient Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remove any obs...

Page 30: ...it fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 Relocation Contact your dealer for removing and reinstalling the total unit Moving un...

Page 31: ......

Page 32: ...4P495373 1 2017 07 Copyright 2016 Daikin 4P495373 1 0000000T...

Reviews: