5 Installation

Installation and operation manual

12

4BY1

Air-cooled refrigeration condensing unit

4P495373-1 – 2017.07

3

Recover  gas  and  oil  from  the  pinched  piping  by  using  a
recovery unit.

CAUTION

Do not vent gases into the atmosphere.

4

When  all  gas  and  oil  is  recovered  from  the  pinched  piping,
disconnect the charge hose and close the service ports

5

Cut  off  the  lower  part  of  the  gas  and  liquid  stop  valve  pipes
along the black line. Use an appropriate tool (e.g. a pipe cutter,
a pair of nippers).

WARNING

Never remove the pinched piping by brazing.

Any gas or oil remaining inside the stop valve may blow off
the pinched piping.

6

Wait  until  all  oil  is  dripped  out  before  continuing  with  the
connection  of  the  field  piping  in  case  the  recovery  was  not
complete.

5.3.3

Guidelines when installing a sight glass

Install a sight glass on the liquid piping:

Diameter

9.5 mm

Where/how

Install the sight glass before the dryer, as near
to the outdoor unit as possible. Install
horizontally.

a b

a

 Sight glass

b

 Dryer

When brazing

Follow the brazing instructions in the sight
glass manual.

5.3.4

Guidelines when installing a dryer

NOTICE

Do  NOT  operate  the  unit  without  a  dryer  installed.

Possible consequence: 

Equipment malfunction.

Install a dryer on the liquid piping:

Dryer type

80 g (100% molecular sieve equivalent)

(DML083/DML083S: Danfoss made)

Where/how

Install the dryer after the sight glass, as near to
the outdoor unit as possible. Install
horizontally.

a b

a

 Sight glass

b

 Dryer

When brazing

Follow the brazing instructions in the dryer
manual.

Remove the dryer cap immediately before
brazing (to prevent absorption of airborne
moisture).

If dryer paint burnt during brazing, repair it. For
repair paint details, contact the manufacturer.

Flow direction

If the dryer specifies a flow direction, install
accordingly.

5.3.5

To connect the refrigerant piping to the
outdoor unit

NOTICE

▪ Be  sure  to  use  the  supplied  accessory  pipes  when

carrying out piping work in the field.

▪ Be  sure  that  the  field  installed  piping  does  not  touch

other pipes, the bottom panel or side panel. Especially
for  the  bottom  and  side  connection,  be  sure  to  protect
the  piping  with  suitable  insulation,  to  prevent  it  from
coming into contact with the casing.

1

Do the following:

▪ Remove the service cover (a) with screw (b).
▪ Remove the piping intake plate (c) with screw (d).

c

a

b

d

2

Choose a piping route (a, b, or c).

a

b

c

3

If you have chosen the downwards piping route:

▪ Drill (a, 4×) and remove the knockout hole (b).
▪ Cut out the slits (c) with a metal saw.

Summary of Contents for LRMEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...label 16 5 6 Connecting the electrical wiring 17 5 6 1 Field wiring Overview 17 5 6 2 Guidelines when knocking out knockout holes 18 5 6 3 Guidelines when connecting the electrical wiring 18 5 6 4 To...

Page 6: ...accessories from the outdoor unit 1 Remove the service cover See 5 1 1 To open the outdoor unit on page 9 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precaut...

Page 7: ...to top When the copper piping or fan is corroded When the heat exchanger is contaminated Foreign materials including oils for fabrication must be 30 mg 10 m Reuse allowed In other cases than above yo...

Page 8: ...e diameter of the outdoor unit stop valve 15 9 mm to that of the field piping 19 1 mm B C b c Piping between piping branching Use diameters depending on the total capacity of the indoor units connecte...

Page 9: ...The operation switch is located in the switchbox see illustration below R E M O T E OFF O N The operation switch can be set to the following three positions Operation switch setting Function OFF Unit...

Page 10: ...ng the paint field supply 4 Attach the cable s ends Tighten those ends 5 3 Connecting the refrigerant piping DANGER RISK OF BURNING 5 3 1 Using the stop valve and service port To handle the stop valve...

Page 11: ...w Check for refrigerant leaks after tightening the service port cover NOTICE Thread locking fluid Before reattaching the service port cover apply thread locking fluid to the screw thread NOT to the co...

Page 12: ...the unit without a dryer installed Possible consequence Equipment malfunction Install a dryer on the liquid piping Dryer type 80 g 100 molecular sieve equivalent DML083 DML083S Danfoss made Where how...

Page 13: ...example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make con...

Page 14: ...ion of the system higher than the design pressure of the indoor unit 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use...

Page 15: ...e stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves B and C 3 Pre charge refrigerant until the determined additional refrigerant amount is reached or pre charging is not pos...

Page 16: ...to charge the unit even if the opening of the liquid line stop valve is adjusted If this is the case replace the cylinder with one that has more refrigerant remaining If the piping length is long repl...

Page 17: ...1M S1T Y1S Ry 0 S2T NC TeS1 No T1 T1 E1H t Ry0 t Ry 1 K1M S1T H1P P1 P2 W1 C C1 R X3M X1M L2 N L1 L3 B X2M A D C F1 F2 Ry 0 Ry 0 K1M Ry 0 Ry 0 Ry 0 K1M Ry 1 Y1S 3D111889 A e c a b i j k h f b d B B b...

Page 18: ...es when knocking out knockout holes NOTICE Precautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and ar...

Page 19: ...power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break down NOTICE Output signals The outdoor un...

Page 20: ...de 1 and 2 Mode Description Mode 1 monitoring settings Mode 1 can be used to monitor the current situation of the outdoor unit Some field setting contents can be monitored as well Mode 2 field setting...

Page 21: ...information See 6 1 7 Mode 1 and default situation Monitoring settings on page 21 Example 7 LEDs display Mode 1 See 8 1 1 To display the error codes of the latest malfunctions on page 24 6 1 6 To use...

Page 22: ...ating temperature during low noise operation With this setting the target evaporating temperature set with settings 2 0 and 2 1 can be corrected for low noise operation see setting 2 18 default 1 C 2...

Page 23: ...nsulation test of the main power circuit Using a megatester for 500 V check that the insulation resistance of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and eart...

Page 24: ...ly completed normal operation is possible 7 3 3 Correcting after abnormal completion of the test run The test operation is only completed if no malfunction occurs In case of a malfunction perform corr...

Page 25: ...t the switch properly Replace defective component Outdoor fan motor signal failure Abnormal position of signal of 1 fan motor 4 Caution Abnormal fan motor signal circuit error Broken short or disconne...

Page 26: ...acle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction sid...

Page 27: ...microcurrent 1 mA 12 V DC For instructions on how to use the remote switch refer to the technical engineering data 7 The initial state of SW1 is open normal mode To activate low noise mode close the...

Page 28: ...result in injury Water pressure Check whether the water pressure is above 1 bar If it is lower add water 12 1 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gase...

Page 29: ...make sure the air can flow freely Malfunction Measure The system operates but cooling is insufficient Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remove any obs...

Page 30: ...it fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 Relocation Contact your dealer for removing and reinstalling the total unit Moving un...

Page 31: ......

Page 32: ...4P495373 1 2017 07 Copyright 2016 Daikin 4P495373 1 0000000T...

Reviews: