13 Troubleshooting

Installation and operation manual

29

4BY1
Air-cooled refrigeration condensing unit
4P495373-1 – 2017.07

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

13

Troubleshooting

If system malfunctions are likely to degrade the articles in the room/
showcase,  you  can  ask  your  installer  to  install  an  alarm  (example:
lamp). For more information, contact your installer.

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.

Turn off the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work
well.

Turn off the power.

If  the  system  does  not  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

The system stops
immediately after
starting operation.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

Malfunction

Measure

The system operates
but cooling is
insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the indoor unit is not frosted up.

Defrost  the  unit  manually,  or  shorten  the
defrost operation cycle.

▪ Check  if  there  are  not  too  many  articles

inside  the  room/showcase.  Remove  a
couple of articles.

▪ Check  if  there  is  smooth  air  circulation

inside  the  room/showcase.  Reorganise
the articles inside the room/showcase.

▪ Check  if  there  is  not  too  much  dust  on

the 

outdoor 

unit 

heat 

exchanger.

Remove the dust with a brush or vacuum
cleaner, 

without 

using 

water. 

If

necessary, consult your dealer.

▪ Check  if  there  is  cold  air  leaking  outside

of  the  room/showcase.  Stop  the  air  from
leaking outside.

▪ Check  if  you  did  not  set  the  indoor  unit

setpoint  temperature  too  high.  Set  the
setpoint appropriately.

▪ Check  if  there  are  no  high-temperature

articles  stored  in  the  room/showcase.
Always  store  articles  after  they  have
cooled down.

▪ Check if the door is not opened too long.

Reduce the opening time of the door.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

13.1

Symptoms that are NOT system
malfunctions

The following symptoms are NOT system malfunctions:

13.1.1

Symptom: The system does not operate

▪ The system does not start immediately after it is turned ON again.

If the operation lamp lights, the system is in normal condition. To
prevent overloading of the compressor motor, the system starts 5
minutes after it is turned ON again in case it was turned OFF just
before.

▪ The  system  does  not  start  immediately  after  the  power  supply  is

turned  on.  Wait  one  minute  until  the  micro  computer  is  prepared
for operation.

13.1.2

Symptom: The unit does not stop
immediately when operation is stopped

This  is  to  prevent  components  from  being  damaged.  The  unit  will
stop in a little while.

13.1.3

Symptom: Noise (Outdoor unit)

▪ A  continuous  low  hissing  sound  is  heard  when  the  system  is  in

cooling  operation.  This  is  the  sound  of  refrigerant  gas  flowing
through both indoor and outdoor units.

▪ A  hissing  sound  which  is  heard  at  the  start  or  immediately  after

stopping operation. This is the noise of refrigerant caused by flow
stop or flow change.

Summary of Contents for LRMEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...label 16 5 6 Connecting the electrical wiring 17 5 6 1 Field wiring Overview 17 5 6 2 Guidelines when knocking out knockout holes 18 5 6 3 Guidelines when connecting the electrical wiring 18 5 6 4 To...

Page 6: ...accessories from the outdoor unit 1 Remove the service cover See 5 1 1 To open the outdoor unit on page 9 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precaut...

Page 7: ...to top When the copper piping or fan is corroded When the heat exchanger is contaminated Foreign materials including oils for fabrication must be 30 mg 10 m Reuse allowed In other cases than above yo...

Page 8: ...e diameter of the outdoor unit stop valve 15 9 mm to that of the field piping 19 1 mm B C b c Piping between piping branching Use diameters depending on the total capacity of the indoor units connecte...

Page 9: ...The operation switch is located in the switchbox see illustration below R E M O T E OFF O N The operation switch can be set to the following three positions Operation switch setting Function OFF Unit...

Page 10: ...ng the paint field supply 4 Attach the cable s ends Tighten those ends 5 3 Connecting the refrigerant piping DANGER RISK OF BURNING 5 3 1 Using the stop valve and service port To handle the stop valve...

Page 11: ...w Check for refrigerant leaks after tightening the service port cover NOTICE Thread locking fluid Before reattaching the service port cover apply thread locking fluid to the screw thread NOT to the co...

Page 12: ...the unit without a dryer installed Possible consequence Equipment malfunction Install a dryer on the liquid piping Dryer type 80 g 100 molecular sieve equivalent DML083 DML083S Danfoss made Where how...

Page 13: ...example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make con...

Page 14: ...ion of the system higher than the design pressure of the indoor unit 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use...

Page 15: ...e stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves B and C 3 Pre charge refrigerant until the determined additional refrigerant amount is reached or pre charging is not pos...

Page 16: ...to charge the unit even if the opening of the liquid line stop valve is adjusted If this is the case replace the cylinder with one that has more refrigerant remaining If the piping length is long repl...

Page 17: ...1M S1T Y1S Ry 0 S2T NC TeS1 No T1 T1 E1H t Ry0 t Ry 1 K1M S1T H1P P1 P2 W1 C C1 R X3M X1M L2 N L1 L3 B X2M A D C F1 F2 Ry 0 Ry 0 K1M Ry 0 Ry 0 Ry 0 K1M Ry 1 Y1S 3D111889 A e c a b i j k h f b d B B b...

Page 18: ...es when knocking out knockout holes NOTICE Precautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and ar...

Page 19: ...power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break down NOTICE Output signals The outdoor un...

Page 20: ...de 1 and 2 Mode Description Mode 1 monitoring settings Mode 1 can be used to monitor the current situation of the outdoor unit Some field setting contents can be monitored as well Mode 2 field setting...

Page 21: ...information See 6 1 7 Mode 1 and default situation Monitoring settings on page 21 Example 7 LEDs display Mode 1 See 8 1 1 To display the error codes of the latest malfunctions on page 24 6 1 6 To use...

Page 22: ...ating temperature during low noise operation With this setting the target evaporating temperature set with settings 2 0 and 2 1 can be corrected for low noise operation see setting 2 18 default 1 C 2...

Page 23: ...nsulation test of the main power circuit Using a megatester for 500 V check that the insulation resistance of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and eart...

Page 24: ...ly completed normal operation is possible 7 3 3 Correcting after abnormal completion of the test run The test operation is only completed if no malfunction occurs In case of a malfunction perform corr...

Page 25: ...t the switch properly Replace defective component Outdoor fan motor signal failure Abnormal position of signal of 1 fan motor 4 Caution Abnormal fan motor signal circuit error Broken short or disconne...

Page 26: ...acle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction sid...

Page 27: ...microcurrent 1 mA 12 V DC For instructions on how to use the remote switch refer to the technical engineering data 7 The initial state of SW1 is open normal mode To activate low noise mode close the...

Page 28: ...result in injury Water pressure Check whether the water pressure is above 1 bar If it is lower add water 12 1 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gase...

Page 29: ...make sure the air can flow freely Malfunction Measure The system operates but cooling is insufficient Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remove any obs...

Page 30: ...it fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 Relocation Contact your dealer for removing and reinstalling the total unit Moving un...

Page 31: ......

Page 32: ...4P495373 1 2017 07 Copyright 2016 Daikin 4P495373 1 0000000T...

Reviews: