background image

5 Installation

Installation and operation manual

11

4BY1
Air-cooled refrigeration condensing unit
4P495373-1 – 2017.07

1

2

3

4

To close the stop valve

1

Remove the stop valve cover.

2

Insert  a  hexagon  wrench  into  the  stop  valve  and  turn  the  stop
valve clockwise.

3

When the stop valve cannot be turned any further, stop turning.

Result: 

The valve is now closed.

Closing direction:

To handle the stop valve cover

▪ The  stop  valve  cover  is  sealed  where  indicated  by  the  arrow.  Do

NOT damage it.

▪ After  handling  the  stop  valve,  tighten  the  stop  valve  cover

securely,  and  check  for  refrigerant  leaks.  For  the  tightening
torque, refer to the table below.

NOTICE

Thread-locking  fluid

.  Before  reattaching  the  stop  valve

cover, apply thread-locking fluid to the screw thread (NOT
to  the  cover  or  sealing  part).  Otherwise,  condensation
water  might  enter  and  freeze. 

Possible  consequence:

Deformation, 

refrigerant 

leakage 

and 

compressor

malfunction.

a

b

b

c

a

Cover (do NOT apply thread-locking fluid)

b

Sealing part (do NOT apply thread-locking fluid)

c

Screw thread with thread-locking fluid

To handle the service port

▪ Always  use  a  charge  hose  equipped  with  a  valve  depressor  pin,

since the service port is a Schrader type valve.

▪ After  handling  the  service  port,  make  sure  to  tighten  the  service

port  cover  securely.  For  the  tightening  torque,  refer  to  the  table
below.

▪ Check for refrigerant leaks after tightening the service port cover.

NOTICE

Thread-locking  fluid

.  Before  reattaching  the  service  port

cover, apply thread-locking fluid to the screw thread (NOT
to  the  cover  or  sealing  part).  Otherwise,  condensation
water  might  enter  and  freeze. 

Possible  consequence:

Deformation, 

refrigerant 

leakage 

and 

compressor

malfunction.

c

b

a

a

Cover (do NOT apply thread-locking fluid)

b

Sealing part (do NOT apply thread-locking fluid)

c

Screw thread with thread-locking fluid

Tightening torques

Stop valve

size (mm)

Tightening torque N•m (turn clockwise to close)

Shaft

Valve body Hexagonal

wrench

Cap (valve

lid)

Service

port

Ø9.5

5.4~6.6

4 mm

13.5~16.5

11.5~13.9

Ø15.9

13.5~16.5

6 mm

22.5~27.5

5.3.2

To remove the pinched pipes

WARNING

Any gas or oil remaining inside the stop valve may blow off
the pinched piping.

Failure  to  observe  the  instructions  in  procedure  below
properly may result in property damage or personal injury,
which may be serious depending on the circumstances.

Use the following procedure to remove the pinched piping:

1

Remove the valve cover and make sure that the stop valves are
fully closed.

c
d

a

b

 

 

a

Service port and service port cover

b

Stop valve

c

Field piping connection

d

Stop valve cover

2

Connect the vacuuming/recovery unit through a manifold to the
service port of all stop valves.

p< p>

R410A

N2

b

c

e

a

f

g

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

Summary of Contents for LRMEQ3BY1

Page 1: ...Installation and operation manual Air cooled refrigeration condensing unit English Installation and operation manual Air cooled refrigeration condensing unit LRMEQ3BY1 LRMEQ4BY1...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m zn n Smjernice kako je izmijenjeno ir nyelv ek s...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...label 16 5 6 Connecting the electrical wiring 17 5 6 1 Field wiring Overview 17 5 6 2 Guidelines when knocking out knockout holes 18 5 6 3 Guidelines when connecting the electrical wiring 18 5 6 4 To...

Page 6: ...accessories from the outdoor unit 1 Remove the service cover See 5 1 1 To open the outdoor unit on page 9 2 Remove the accessories a 1 b 1 c 1 d 1 a 1 b 1 c 1 d 1 e 1 f 1 g 1 a General safety precaut...

Page 7: ...to top When the copper piping or fan is corroded When the heat exchanger is contaminated Foreign materials including oils for fabrication must be 30 mg 10 m Reuse allowed In other cases than above yo...

Page 8: ...e diameter of the outdoor unit stop valve 15 9 mm to that of the field piping 19 1 mm B C b c Piping between piping branching Use diameters depending on the total capacity of the indoor units connecte...

Page 9: ...The operation switch is located in the switchbox see illustration below R E M O T E OFF O N The operation switch can be set to the following three positions Operation switch setting Function OFF Unit...

Page 10: ...ng the paint field supply 4 Attach the cable s ends Tighten those ends 5 3 Connecting the refrigerant piping DANGER RISK OF BURNING 5 3 1 Using the stop valve and service port To handle the stop valve...

Page 11: ...w Check for refrigerant leaks after tightening the service port cover NOTICE Thread locking fluid Before reattaching the service port cover apply thread locking fluid to the screw thread NOT to the co...

Page 12: ...the unit without a dryer installed Possible consequence Equipment malfunction Install a dryer on the liquid piping Dryer type 80 g 100 molecular sieve equivalent DML083 DML083S Danfoss made Where how...

Page 13: ...example a to prevent snow and small animals from entering the system a WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make con...

Page 14: ...ion of the system higher than the design pressure of the indoor unit 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use...

Page 15: ...e stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves B and C 3 Pre charge refrigerant until the determined additional refrigerant amount is reached or pre charging is not pos...

Page 16: ...to charge the unit even if the opening of the liquid line stop valve is adjusted If this is the case replace the cylinder with one that has more refrigerant remaining If the piping length is long repl...

Page 17: ...1M S1T Y1S Ry 0 S2T NC TeS1 No T1 T1 E1H t Ry0 t Ry 1 K1M S1T H1P P1 P2 W1 C C1 R X3M X1M L2 N L1 L3 B X2M A D C F1 F2 Ry 0 Ry 0 K1M Ry 0 Ry 0 Ry 0 K1M Ry 1 Y1S 3D111889 A e c a b i j k h f b d B B b...

Page 18: ...es when knocking out knockout holes NOTICE Precautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and ar...

Page 19: ...power supply is pulled loose from the stress relief NOTICE Never connect the power supply to terminal blocks X2M or X3M Otherwise the entire system may break down NOTICE Output signals The outdoor un...

Page 20: ...de 1 and 2 Mode Description Mode 1 monitoring settings Mode 1 can be used to monitor the current situation of the outdoor unit Some field setting contents can be monitored as well Mode 2 field setting...

Page 21: ...information See 6 1 7 Mode 1 and default situation Monitoring settings on page 21 Example 7 LEDs display Mode 1 See 8 1 1 To display the error codes of the latest malfunctions on page 24 6 1 6 To use...

Page 22: ...ating temperature during low noise operation With this setting the target evaporating temperature set with settings 2 0 and 2 1 can be corrected for low noise operation see setting 2 18 default 1 C 2...

Page 23: ...nsulation test of the main power circuit Using a megatester for 500 V check that the insulation resistance of 2 M or more is attained by applying a voltage of 500 V DC between power terminals and eart...

Page 24: ...ly completed normal operation is possible 7 3 3 Correcting after abnormal completion of the test run The test operation is only completed if no malfunction occurs In case of a malfunction perform corr...

Page 25: ...t the switch properly Replace defective component Outdoor fan motor signal failure Abnormal position of signal of 1 fan motor 4 Caution Abnormal fan motor signal circuit error Broken short or disconne...

Page 26: ...acle E in the direction of obstacle D HU Height of the unit HB HD Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction sid...

Page 27: ...microcurrent 1 mA 12 V DC For instructions on how to use the remote switch refer to the technical engineering data 7 The initial state of SW1 is open normal mode To activate low noise mode close the...

Page 28: ...result in injury Water pressure Check whether the water pressure is above 1 bar If it is lower add water 12 1 About the refrigerant This product contains fluorinated greenhouse gases Do NOT vent gase...

Page 29: ...make sure the air can flow freely Malfunction Measure The system operates but cooling is insufficient Check if air inlet or outlet of outdoor or indoor unit is not blocked by obstacles Remove any obs...

Page 30: ...it fan does not spin During operation The speed of the fan is controlled in order to optimise product operation 14 Relocation Contact your dealer for removing and reinstalling the total unit Moving un...

Page 31: ......

Page 32: ...4P495373 1 2017 07 Copyright 2016 Daikin 4P495373 1 0000000T...

Reviews: