TRIAL OPERATION AND TESTING

(1) Measure the supply voltage and make sure that it falls in the specified range.
(2) Trial operation should be carried out in either cooling or heating mode.

For Heat pump.
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature.

• Trial operation may be disabled in either mode depending on the room temperature.
• After trial operation is complete, set the temperature to a normal level (26°C to 28°C in cooling mode, 20°C to 24°C in 

heating mode).

• For protection, the system disables restart operation for 3 minutes after it is turned off.

For Cooling only.
Select the lowest programmable temperature.

• Trial operation in cooling mode may be disabled depending on the room temperature.

Use the remote control for trial operation as described below.

• After trial operation is complete, set the temperature to a normal level (26

°

C to 28

°

C).

• For protection, the unit disables restart operation for 3 minutes after it is turned off.

(3) Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts, are working 

properly.
* The air conditioner requires a small amount of power in its standby mode.  If the system is not to be used for some time after 

installation, shut off the circuit breaker to eliminate unnecessary power consumption.

* If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode when 

the circuit breaker is turned on again.

Trial operation and testing

(1) Press ON/OFF button to turn on the system.
(2) Simultaneously press center of TEMP button and MODE button.
(3) Press MODE button twice.

(“    ” will appear on the display to indicate that Trial Operation mode is selected.)

(4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial operation, press 

ON/OFF button.

Trial operation from remote controller

Test items

Check

Symptom

(diagnostic display on RC)

Test items

Indoor and outdoor units are installed properly on solid bases.

No refrigerant gas leaks.

Refrigerant gas and liquid pipes and indoor drain hose 

extension are thermally insulated.

Draining line is properly installed.

System is properly earthed.

The specified wires are used for interconnecting wire 

connections.

Indoor or outdoor unit’s air inlet or discharge has clear path of air.

Shut-off valves are opened.

Indoor unit properly receives remote controller commands.

Fall, vibration, noise

Incomplete cooling/heating 

function

Water leakage

Water leakage

Electrical leakage

Inoperative or burn damage

Incomplete cooling/heating 

function

Inoperative

01_EN_3P132003-2N.fm  Page 11  Tuesday, December 5, 2006  2:02 PM

Summary of Contents for Inverter FDXS25CVMB

Page 1: ...KS60CVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Monta...

Page 2: ...ita ku Osaka 530 8323 Japan 3P132004 2C FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS50CVMB CDXS60CVMB CDKS50CVMB CDKS60CVMB FDXS25CAVMB FDXS35CAVMB FDKS25CAVMB FDKS35CAVMB Noboru Murata Manager Qu...

Page 3: ...be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrica...

Page 4: ...he conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to suppo...

Page 5: ...pressure is not exceeded See the technical documentation for the range of the external static pressure setting Open the installation hole Pre set ceilings Once the installation hole is opened in the c...

Page 6: ...d in one room one of the two wireless remote controllers can be easily set for another addresses Air inlet 3 Air discharge Air discharge Air inlet Anti sweat material included with the product Anti sw...

Page 7: ...tch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver...

Page 8: ...REFRIGERANT PIPING 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten...

Page 9: ...he refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the fo...

Page 10: ...er to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping connections Do no...

Page 11: ...y is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape o...

Page 12: ...xt pull the wires into the unit through the wiring through hole and connect to the power wiring terminal block 4P Warning Do not use tapped wires stand wires extensioncords or starbust connections as...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0701 HT 3P132003 2N M04B108D Two dimensional bar code is a code for manufacturing...

Reviews: