English
4
(3)Attach sealing pad as shown in the figure below. (Stored in outlet vent)
(In order to take in the air inside the ceiling, and when not taking in air from outdoor air, it is not necessary to stick.)
• Attach the sealing pad (accessory) to
the plate metal sections which are not
covered by anti-sweat material.
• Make sure there are no gaps between
the different pieces of sealing pad.
(4)Attach the hanger (right) insulation to the right hanger. (Stored in outlet vent)
(See the below figure for the sticking base line.)
(5)Attach the air filter (accessory) in the manner shown in the diagram.
■
When two indoor units are installed in one room, one of the two wireless remote controllers can be easily
set for another addresses.
Air inlet
(3)
Air
discharge
Air
discharge
Air inlet
Anti-sweat material
included with the product
Anti-sweat material
included with the product
Sealing pad (Small)
For rear intake type
Sealing pad (Large)
Sealing pad (Small)
(accessory)
(accessory)
Sealing pad
(Large)
(accessory)
(accessory)
For bottom intake type
Hanger (right) insulation
Slit
Stic
king base line
Hanger bracket (right)
ARROW VIEW
In case of bottom side
In case of back side
Filter
Force
Force
Main unit
Attach the
filter to the
main unit
while
pushing
down on
the tabs.
(5)
J4
ADDRESS
EXIST
1
CUT
2
Wireless
remote
controller
J4
PCB in the indoor unit
• Cut the jumper
JA on PCB.
• Cut the jumper J4.
Wireless remote controller
1
2
3
JA
ADDRESS:
CUT
EXIST
1
2
ADDRESS
JA
JB
JC
01_EN_3P132003-2N.fm Page 4 Tuesday, December 5, 2006 2:02 PM