CHOOSING A SITE

• Before choosing the installation site, obtain user approval.

Caution

• When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs.  Do not exert any pressure on 

other parts, especially the refrigerant piping, drain piping and flange parts.
Wear protective gears (gloves and so on) when installing the unit.

• If you think the humidity inside the ceiling might exceed 30°C and RH80%, reinforce the insulation on the unit body.

Use glass wool or polyethylene foam as insulation so that the thickness is more than 10mm and fits inside the ceiling opening.

• Optimum air distribution is ensured.
• The air passage is not blocked.
• Condensate can drain properly.
• The ceiling is strong enough to bear the weight of the indoor unit.
• A false ceiling does not seem to be at an incline.
• Sufficient clearance for maintenance and servicing is ensured.
• Piping between the indoor and outdoor units is within the allowable limits. 

(Refer to the installation manual for the outdoor unit.)

• The indoor unit, outdoor unit, power supply wiring and transmission wiring is at least 1 

meter away from televisions and radios. This prevents image interference and noise in 
electrical appliances. (Noise may be generated depending on the conditions under 
which the electric wave is generated, even if a one-meter allowance is maintained.)

Use suspension bolts to install the unit. Check whether or not the ceiling is 
strong enough to support the weight of the unit. If there is a risk that the 
ceiling is not strong enough, reinforce the ceiling before installing the unit.

 

(Installation pitch is marked on the carton box for installation. Refer to it to check 
for points requiring reinforcing.) Select the *H dimension such that a downward 
slope of at least 1/100 is ensured as indicated in 

“DRAIN PIPING WORK”

.

• The installation pitch is listed on the packing material, and should be 

checked when deciding whether to reinforce the location or not.

Wireless 

remote controller

1 pc.

AAA 

dry-cell batteries

Remote controller

holder

1 pc.

1 pc.

Air fillter

1 set

2 pcs.

[ Other ]

• Operation 
  manual

• Installation 
  manual

Clamp metal

1 pc.

1 pc.

Insulation 

for fitting

1 each

Sealing pad

Large and small

1 each

for gas pipe

for liquid pipe

Large

Small

24 pcs.

Washer for 

hanging bracket

8 pcs.

2 pcs.

6 pcs.

4 pcs.

Drain hose

Sealing

material

Clamp

Washer 

fixing plate

1 set

1 set

Screws for 

duct flanges

Stored in outlet vent

1 pc.

2 large

1 small

Hanger (right)
insulation

Mounting frame

Screws 
M4 

× 

25

Decorative 
cover

1 pc.

Receiver kit

1 pc.

2 pcs.

3 pcs.

(only for 50-60 type)

Indoor unit

Control box

Maintenance
space

300
or more

20 or more

2500 or more

*H=

240 or more

200

Ceiling

Floor surface

(length : mm)

If there is 

no ceiling

01_EN_3P132003-2N.fm  Page 2  Tuesday, December 5, 2006  2:02 PM

Summary of Contents for Inverter FDXS25CVMB

Page 1: ...KS60CVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Monta...

Page 2: ...ita ku Osaka 530 8323 Japan 3P132004 2C FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS50CVMB CDXS60CVMB CDKS50CVMB CDKS60CVMB FDXS25CAVMB FDXS35CAVMB FDKS25CAVMB FDKS35CAVMB Noboru Murata Manager Qu...

Page 3: ...be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrica...

Page 4: ...he conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to suppo...

Page 5: ...pressure is not exceeded See the technical documentation for the range of the external static pressure setting Open the installation hole Pre set ceilings Once the installation hole is opened in the c...

Page 6: ...d in one room one of the two wireless remote controllers can be easily set for another addresses Air inlet 3 Air discharge Air discharge Air inlet Anti sweat material included with the product Anti sw...

Page 7: ...tch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver...

Page 8: ...REFRIGERANT PIPING 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten...

Page 9: ...he refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the fo...

Page 10: ...er to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping connections Do no...

Page 11: ...y is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape o...

Page 12: ...xt pull the wires into the unit through the wiring through hole and connect to the power wiring terminal block 4P Warning Do not use tapped wires stand wires extensioncords or starbust connections as...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0701 HT 3P132003 2N M04B108D Two dimensional bar code is a code for manufacturing...

Reviews: