background image

English

6

REFRIGERANT PIPING WORK 

See the installation manual supplied with the outdoor unit.

1.

FLARING THE PIPE END

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

Warning

Do not use mineral oil on flared part.
Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
Do never install a drier to this R410A unit in order to guarantee its lifetime.
The drying material may dissolve and damage the system.
Incomplete flaring may cause refrigerant gas leakage.

2.

REFRIGERANT PIPING

1) To prevent gas leakage, apply refrigeration machine oil on both 

inner and outer surfaces of the flare. (Use refrigeration oil for 
R410A)

2) Align the centres of both flares and tighten the flare nuts 3 or 4 

turns by hand. Then tighten them fully with the torque wrenches. 
• Use torque wrenches when tightening the flare nuts to prevent 

damage to the flare nuts and escaping gas.

Caution

Overtightening may damage the flare and cause leaks.

A

A

(Cut exactly at right angles.)

Remove burrs

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in a 
perfect circle.

Make sure that the 
flare nut is fitted.

Check

0 ~ 0.5 mm

1.0 ~ 1.5 mm

1.5 ~ 2.0 mm

Set exactly at the position shown below.

Clutch-type

Flare tool for R410A

Clutch-type (Rigid-type) Wing-nut type (Imperial-type)

Conventional flare tool

Flaring

Die

Flare nut tightening torque

Gas side

Liquid side

3/8 inch

1/2 inch

1/4 inch

32.7~39.9N•m

(333~407kgf•cm)

49.5~60.3N•m

(505~615kgf•cm)

14.2~17.2N•m

(144~175kgf•cm)

01_EN_3P132003-2N.fm  Page 6  Tuesday, December 5, 2006  2:02 PM

Summary of Contents for Inverter FDXS25CVMB

Page 1: ...KS60CVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Monta...

Page 2: ...ita ku Osaka 530 8323 Japan 3P132004 2C FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS50CVMB CDXS60CVMB CDKS50CVMB CDKS60CVMB FDXS25CAVMB FDXS35CAVMB FDKS25CAVMB FDKS35CAVMB Noboru Murata Manager Qu...

Page 3: ...be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrica...

Page 4: ...he conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to suppo...

Page 5: ...pressure is not exceeded See the technical documentation for the range of the external static pressure setting Open the installation hole Pre set ceilings Once the installation hole is opened in the c...

Page 6: ...d in one room one of the two wireless remote controllers can be easily set for another addresses Air inlet 3 Air discharge Air discharge Air inlet Anti sweat material included with the product Anti sw...

Page 7: ...tch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver...

Page 8: ...REFRIGERANT PIPING 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten...

Page 9: ...he refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the fo...

Page 10: ...er to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping connections Do no...

Page 11: ...y is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape o...

Page 12: ...xt pull the wires into the unit through the wiring through hole and connect to the power wiring terminal block 4P Warning Do not use tapped wires stand wires extensioncords or starbust connections as...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0701 HT 3P132003 2N M04B108D Two dimensional bar code is a code for manufacturing...

Reviews: